40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  ATF eLog  Not logged in ELOG logo
Message ID: 2469     Entry time: Fri Dec 6 00:13:12 2019
Author: Chris 
Type: Computing 
Category: CDS 
Subject: arbitrary waveform streaming on the cymac 

Recently Duo wanted to make an arbitrary waveform excitation using the QIL cymac, but it wasn't working.  An excitation would die after 10 seconds or so, with awgtpman reporting that the data was too far in the future.

It turns out this was caused by a missing leap second in the RTS software.  It is now fixed upstream, and we're running a patched version of awgtpman on fb4, until the change propagates to the packaged version.
 

ELOG V3.1.3-