Entry  Wed Mar 27 11:27:00 2019, Aidan, Lab Infrastructure, HVAC, HVAC temperature gradients in the QIL 
    Reply  Wed Apr 24 14:19:55 2019, awade, Lab Infrastructure, HVAC, HVAC QIL: two actuators tied to one sensor now 
       Reply  Wed Apr 24 19:30:55 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends QIL_temperature_190424.tgz
          Reply  Sun May 5 20:58:20 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends HVAC-B265B.pdfplotTemp.tgz
             Reply  Fri May 10 18:39:10 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends 
                Reply  Tue May 14 13:10:36 2019, rana, Lab Infrastructure, HVAC, HVAC debuggin HVAC-B265B.pdf
                Reply  Tue Feb 4 14:18:24 2020, Ian MacMillan, Lab Infrastructure, HVAC, Recent temperature fluctuations HVAC-B265B_20200402.pdfQil_Lab_Temperature.zipHVAC-B265B.pdf
                   Reply  Thu Feb 13 11:04:47 2020, Ian MacMillan, Lab Infrastructure, HVAC, Recent temperature fluctuations HVAC-B265B.pdfJan_2020_Qil_Temp_Measurments.zip
Message ID: 2339     Entry time: Fri May 10 18:39:10 2019     In reply to: 2335     Reply to this: 2341   2484
Author: rana 
Type: Lab Infrastructure 
Category: HVAC 
Subject: howto get temperature trends 

Modesto came back this morning. We were still getting 1 hot blower and 1 cold blower.

As it turned out, although hot water was reaching the south heating coils input, it was not getting into the actual heating duct (as we could tell from touching those coils).

Modesto tapped the actuation valve with a hammer and it seemed to loosen it up. We will record temperature over the weekend.

Also we noted that the damper valve near the south-east vent was adjustable, but had no effect on the output air velocity so we assume its busted inside - Modesto will crack it open to investigate.

We also reduced the flow of hot water to the north blowers since they always seemed to be hotter. This may balance the actuators somewhat.

Modesto also replaced the thermostat on the west wall, but no real effect. I have adjusted the setpoint from 74 to 71F around 1800 today.