40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  ATF eLog  Not logged in ELOG logo
Entry  Wed Mar 27 11:27:00 2019, Aidan, Lab Infrastructure, HVAC, HVAC temperature gradients in the QIL 
    Reply  Wed Apr 24 14:19:55 2019, awade, Lab Infrastructure, HVAC, HVAC QIL: two actuators tied to one sensor now 
       Reply  Wed Apr 24 19:30:55 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends QIL_temperature_190424.tgz
          Reply  Sun May 5 20:58:20 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends HVAC-B265B.pdfplotTemp.tgz
             Reply  Fri May 10 18:39:10 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends 
                Reply  Tue May 14 13:10:36 2019, rana, Lab Infrastructure, HVAC, HVAC debuggin HVAC-B265B.pdf
                Reply  Tue Feb 4 14:18:24 2020, Ian MacMillan, Lab Infrastructure, HVAC, Recent temperature fluctuations HVAC-B265B_20200402.pdfQil_Lab_Temperature.zipHVAC-B265B.pdf
                   Reply  Thu Feb 13 11:04:47 2020, Ian MacMillan, Lab Infrastructure, HVAC, Recent temperature fluctuations HVAC-B265B.pdfJan_2020_Qil_Temp_Measurments.zip
Message ID: 2335     Entry time: Sun May 5 20:58:20 2019     In reply to: 2330     Reply to this: 2339
Author: rana 
Type: Lab Infrastructure 
Category: HVAC 
Subject: howto get temperature trends 

the temperature has stabilized, although the fact that there is a sign error in one of the HVAC actuators means that there is a big delta T in the lab. I will contact facilities again.

the change on April 24 is me adjusting the setpoint on the south wall from 70 to 73F.

Quote:

We need to get the temperature data from the sensors that Aidan setup. I have got it by downloading a sketchy HOBO app onto my phone. In order for this to work you have to go stand next to the sensors and download via bluetooth. There is no "pairing" required - the app seems to recognize the sensors nearly immediately.

and please, Aidan and everyone else, please do not use double-sticky tape or glue or bubble gum to attach sensors in a clean optical setup. We're going to have to make a mess to remove these.

I've just downloaded more data (attached). The lab seemed sort of cold and the south HEPA output was blowing colder air than the north HEPA output.

I've changed the temperature from 70F to 73F at 7:45 PM today. Lets see how it goes.

the python script in the attachment will now scrub the data file for bad lines and make this kind of plot. IT works on .csv files, but none of the other HOBO formats.

Attachment 1: HVAC-B265B.pdf  159 kB  | Hide | Hide all
HVAC-B265B.pdf
Attachment 2: plotTemp.tgz  72 kB
ELOG V3.1.3-