Entry  Wed Mar 27 11:27:00 2019, Aidan, Lab Infrastructure, HVAC, HVAC temperature gradients in the QIL 
    Reply  Wed Apr 24 14:19:55 2019, awade, Lab Infrastructure, HVAC, HVAC QIL: two actuators tied to one sensor now 
       Reply  Wed Apr 24 19:30:55 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends QIL_temperature_190424.tgz
          Reply  Sun May 5 20:58:20 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends HVAC-B265B.pdfplotTemp.tgz
             Reply  Fri May 10 18:39:10 2019, rana, Lab Infrastructure, HVAC, howto get temperature trends 
                Reply  Tue May 14 13:10:36 2019, rana, Lab Infrastructure, HVAC, HVAC debuggin HVAC-B265B.pdf
                Reply  Tue Feb 4 14:18:24 2020, Ian MacMillan, Lab Infrastructure, HVAC, Recent temperature fluctuations HVAC-B265B_20200402.pdfQil_Lab_Temperature.zipHVAC-B265B.pdf
                   Reply  Thu Feb 13 11:04:47 2020, Ian MacMillan, Lab Infrastructure, HVAC, Recent temperature fluctuations HVAC-B265B.pdfJan_2020_Qil_Temp_Measurments.zip
Message ID: 2330     Entry time: Wed Apr 24 19:30:55 2019     In reply to: 2329     Reply to this: 2335
Author: rana 
Type: Lab Infrastructure 
Category: HVAC 
Subject: howto get temperature trends 

We need to get the temperature data from the sensors that Aidan setup. I have got it by downloading a sketchy HOBO app onto my phone. In order for this to work you have to go stand next to the sensors and download via bluetooth. There is no "pairing" required - the app seems to recognize the sensors nearly immediately.

and please, Aidan and everyone else, please do not use double-sticky tape or glue or bubble gum to attach sensors in a clean optical setup. We're going to have to make a mess to remove these.

I've just downloaded more data (attached). The lab seemed sort of cold and the south HEPA output was blowing colder air than the north HEPA output.

I've changed the temperature from 70F to 73F at 7:45 PM today. Lets see how it goes.