Author: Aidan 
Type: Summary 
Category: Computers 
Subject: Rebooted VME and added sitemap 

Aidan

Aidan rebooted the Sun machine and VME. It took a while to get the EPICS channels to work again. The following seemed to work:

  1. Reboot Sun machine.
  2. Reboot the VME crate by depressing the reboot button on the top of the crate.
  3. Log into VME (psl1) at 10.0.0.2 from the Sun machine.
  4. Check the existence of various channels with dbpr "C3:PSL-RCAV_RCPID_SETPOINT"
  5. On the Sun, cd to /usr1/epics/psl/scripts and run "perl rcav_PID_2012_06_15.pl"
  6. Confirmed that PID values started updating on the Sun screen.

Aidan also added a sitemap (~/sitemap.adl), see attached image, for the CTN lab. Aidan added an alias to /home/controls/.bashrc

Aidan

The alias is:

alias sitemap="medm -x /home/controls/sitemap.adl"

Aidan

 