ID |
Date |
Author |
Type |
Category |
Subject |
7071
|
Wed Aug 1 16:38:46 2012 |
steve | Update | SUS | spare SRMU 03 optic moved |
SOS optics prepared to be hanged are moved from the South Flow Bench to S15 Clean Cabinet.
SRMU 03 (1-25-2010) specification summery E080460-05-D, older vintage SRM 01 and PRM 02 (need more specification)
There was one NOT MARKED SOS with two broken magnets on its face. This is labeled ???
This was done to prepare clean space for TIP-TILT drive- test set up.
The existing cable from 1X5 can reach only to the south end: from whitening filter to satelite amp. This will be good for future test of suspensions.
We need to make new cable from 1 X 1 to the south end = 40m long |
Attachment 1: IMG_1464.JPG
|
|
Attachment 2: IMG_1465.JPG
|
|
Attachment 3: IMG_1466.JPG
|
|
7087
|
Mon Aug 6 07:59:33 2012 |
steve | Update | SUS | PRM oplevs servo is still bad |
Quote: |
Quote: |
Quote: |
Yuta claims he fixed the PRM oplev by centering it the other day, but no one has left it on and watched it for a long while, to make sure it's okay. We watched it now for ~2 min, and it was good, but we're leaving the oplevs off anyway for the night. Tomorrow we should restore PRM (it's currently restored), turn on the oplevs, and let it sit to make sure it doesn't go crazy.
|
PRM oplev servo was turned on with PITgain 0.5 and YAWgain -0.7
Note: gain settings were PIT 1.0 and YAW --0.5 on Jun 1, 2012 that I measured Feb 23, 2012
|
It is still oscillating. Gains turned down to zero.
|
Earthquake test our suspensions PRM damping restored. Oplev servo gains turned to zero. |
Attachment 1: PRMeq.png
|
|
7088
|
Mon Aug 6 09:46:31 2012 |
steve | Update | IOO | poweroutage turns laser off |
. Power outage turned off the PSL Innolight laser on Sunday afternoon. It was turned back on and locked happily right on. The green lasers were not effected.
CALIFORNIA INSTITUTE OF TECHNOLOGY
FACILITIES MANAGEMENT
UTILITY & SERVICE INTERRUPTION
**PLEASE POST**
Building: CAMPUS WIDE
Date: SUNDAY, AUGUST 6, 2012
Time: 3:41 PM
Interruption: ELECTRICAL POWER DISTRIBUTION
Contact: MIKE ANCHONDO, X-4999, OR TOM BRENNAN, X-4984
* THIS PAST SUNDAY AFTERNOON ABOUT 3:40 PM, PASADENA WATER AND POWER
EXPERIENCED A FAULT ON THEIR POWER DISTRIBUTION SYSTEM. THIS CAUSED
A SEVERE VOLTAGE SAG WHICH AFFECTED THE CALTECH CAMPUS. THE FAULT WAS
NOT ON A CALTECH CIRCUIT.
(If there is a problem with this Interruption, please notify
the Service Center X-4717 or the above Contact as soon as possible.
If no response is received we will proceed with the interruption.)
Jerry Thompson,
Interim Director of Campus Operations & Maintenance
|
7089
|
Mon Aug 6 10:53:32 2012 |
steve | Update | VAC | status: vauum normal |
The power outage did not have any effect on the vacuum system. I had to open VM1 to the RGA because of flaky CC1 cold cathode gauge fluctuations.
We are running on the vertically positioned CC1 again.
Note: rga scans with closed VM1 are back ground scans. |
Attachment 1: CCgauges.png
|
|
7091
|
Mon Aug 6 16:48:43 2012 |
steve | Update | SUS | SRM oplev is clipping |
The SRM oplev beam is clipping. |
7106
|
Tue Aug 7 16:11:23 2012 |
steve | Update | SUS | optical table box wall proposal |
Sanwiched wall as shown: 1" clear acrylic, 2 layers of 0.004" thick "window tint", 1 layer of 0.007" thermashield and 0.125" yellow acrylic
Visibility: 70 %, Transmission of 1064 nm 2-3 % at 0-50 degrees incident power density 0.7 W/mm2
Max power 100 mW
|
Attachment 1: IMG_1479.JPG
|
|
Attachment 2: IMG_1478.JPG
|
|
7154
|
Sun Aug 12 01:21:26 2012 |
steve | Update | SAFETY | exit door left unlocked |
Caltech security called me at 1am Sunday. Control room emergency exit door was found unlocked!
It is your responsibility to lock door if you unlocked it !
|
7160
|
Mon Aug 13 15:31:09 2012 |
steve | Update | General | larger optical tables at the ends |
I'm proposing larger optical tables at the ends to avoid the existing overcrowding. This would allow the initial pointing and optical level beams to set up correctly.
The existing table is 4 x 2 would be replaced by 4' x 3' We would lose only ~3" space toward exist door.
I'm working on the new ACRYLIC TABLE COVER for each end that will cost around $4k ea. The new cover should fit the larger table.
Let me know what you think. |
Attachment 1: ETMYtable.jpg
|
|
Attachment 2: ETMY4X3.jpg
|
|
7194
|
Wed Aug 15 16:01:47 2012 |
steve | Update | General | larger optical tables at the ends ? |
The drawing of the 4' x 2' table cover can be seen at entry #6190 The new proposed wall #7106 The yellow acrylic would be ~ 0.25" thick and it will be the inside. It is not shown on the drawing.
Question remaining: should get a larger table 4' x 3' as outlined by red lines and make new cover to fit this
The oplev beam path needs larger incident angle to get in and out of the chamber: REMOVE BOTTLENECK for easy traffic
Moving the existing table closer to ETMY chamber - as Jamie suggested- would help but there is no room for this solution.
The larger table solve this issue and leave more room for initial pointing, arm transmitted and future experiments.
Other benefits: no tube to make between table and chamber. It is easier to make the the larger box air tight.
The new isolation box with feed through, cover, seals will cost $4-5K ea
|
Attachment 1: bottleneck.jpg
|
|
7248
|
Wed Aug 22 11:41:20 2012 |
steve | Update | General | grout plate for optical table at the ends |
Reinforced concrete grout plate for existing carbon steel stands at the ends.
|
Attachment 1: IMG_1561.JPG
|
|
Attachment 2: 08231201.PDF
|
|
7458
|
Mon Oct 1 17:03:01 2012 |
steve | Update | SUS | ETMY oplev relayed |
Quote: |
Quote: |
Quote: |
The typical sign of a dying gas laser is that it glows for a few minutes only. The power supplies are fine.
Two new JDS - Uniphase 1103P lasers ( NT64-104 ) arriving on Monday, May 21
|
Yesterday I swapped in new He/Ne laser with output power 3.5 mW The return spot on qpd is large ~6mm in diameter and 20,500 counts
The spot size reduction require similar layout as ETMX oplev.
|
The oplev path is relayed and the spot size on the qpd is reduced. I still have to clean up and replace "Miki Mouse" lens holder.
There was no IP-ANG coming out of the chamber at this time!
|
I did relayed the oplev path with new f 500 mm lens |
Attachment 1: IMG_1673oplevETMY.jpg
|
|
7538
|
Fri Oct 12 16:59:26 2012 |
steve | Update | SUS | TT PITCH damping |
Quote: |
Quote: |
We can only decide the need of pitch damping when the coils are activated.
|
Could you tell us why? Are you thinking about induced current damping?
|
I was wrong The instability will be the same when the coils are actuated. |
7544
|
Mon Oct 15 08:08:33 2012 |
steve | Update | SUS | PRM damping restored |
Quote: |
Quote: |
Quote: |
Quote: |
Yuta claims he fixed the PRM oplev by centering it the other day, but no one has left it on and watched it for a long while, to make sure it's okay. We watched it now for ~2 min, and it was good, but we're leaving the oplevs off anyway for the night. Tomorrow we should restore PRM (it's currently restored), turn on the oplevs, and let it sit to make sure it doesn't go crazy.
|
PRM oplev servo was turned on with PITgain 0.5 and YAWgain -0.7
Note: gain settings were PIT 1.0 and YAW --0.5 on Jun 1, 2012 that I measured Feb 23, 2012
|
It is still oscillating. Gains turned down to zero.
|
Earthquake test our suspensions PRM damping restored. Oplev servo gains turned to zero.
|
The PRM damping restored. Oplev PIT gain 0.15 and YAW gain -0.3 turned to zero. |
7652
|
Thu Nov 1 08:48:42 2012 |
steve | Update | Alignment | progress, then setback - trend of BS table shift |
Quote: |
But these jumps in the OSEMs are all at the level of 10-20 microns. Seems like that wouldn't be enough to account for anything; 20 microns / (pend length) ~ 50-60 microradians.
|
BS table and suspensions are fine. |
Attachment 1: alignmentstrugle2d.png
|
|
Attachment 2: alignmentstrugle2da.png
|
|
Attachment 3: befpd09252012.png
|
|
7831
|
Fri Dec 14 09:05:04 2012 |
steve | Update | PEM | TT after eq 6.1 |
SRM, ITMY and MC3 moved some what, but how are the TT? It may worth looking at them before we vent. |
Attachment 1: eq6.1.png
|
|
8240
|
Wed Mar 6 11:33:09 2013 |
steve | Update | SAFETY | safety audit 2013 |
Recommended correction list:
1, refill- upgrade first aid boxes
2, maintain 18" ceiling to bookshelf clearance so the ceiling fire sprinklers are not blocked: room 101
3, label chilled water supply & return valves in IFO room
4, calibrate bake room hoods annually
5, update safety sign at fenced storage
40m still to do list:
1, clean and measure all safety glasses
2, annual crane inspection is scheduled for 8am March 19, 1013
3, make PSL encloser shelf earthquake proof
Do you see something that is not safe? Add it to this list please.
|
Attachment 1: IMG_0010.JPG
|
|
8287
|
Wed Mar 13 16:04:24 2013 |
steve | Update | SAFETY | laser safety glasses checked |
All safety glasses were cleaned in soapy water by Bob. I measured their transmission at 1064 nm, 150 mW, beam diameter 1.5 mm They are in working order, no transmission.
Inventory:
10 pieces of KG-5, fit over, from Laser Safety
4 pieces of KG-5, std size, from Drever Lab, best visibility
1 piece of KG-5 coated for visible, std size, from Kentek
15 pieces of green-plastic LOTG-YAG, fit over, from UVEX
7 pieces of green-plastic B-D+S 137, std areo fit, from Sperian
3 pieces of green-plastic, old Thorlab, fit over
2 pieces of green-plastic, fit over, from Laservision
8 pieces of braun- plastic, fit over, for green & IR protection, from UVEX & Thorlabs |
Attachment 1: safetyglasseschecked.jpg
|
|
8309
|
Tue Mar 19 10:30:00 2013 |
steve | Update | SAFETY | crane inspection 2013 |
Professional crane inspector: Fred Goodbar found two small leaks at the Vertex trolley as he was conducting the annual inspection of the 40m cranes. Otherwise the cranes are in safe condition. |
Attachment 1: sippingOIL.jpg
|
|
Attachment 2: 03191301.PDF
|
|
8661
|
Fri May 31 10:25:17 2013 |
steve | Update | safety | first aid kits refilled |
Quote: |
Recommended correction list:
1, refill- upgrade first aid boxes
2, maintain 18" ceiling to bookshelf clearance so the ceiling fire sprinklers are not blocked: room 101
3, label chilled water supply & return valves in IFO room
4, calibrate bake room hoods annually
5, update safety sign at fenced storage
40m still to do list:
1, clean and measure all safety glasses
2, annual crane inspection is scheduled for 8am March 19, 1013
3, make PSL encloser shelf earthquake proof
Do you see something that is not safe? Add it to this list please.
|
Restocked First Aid Kits Location:
Main entrance, room 100
Drill press - above N2 cylinders, room 103
Control room, next to fire extinguisher, room 102
Vertex-north wall, IFO room 104
ETMY - right on ends light switches, IFO room 104_ east end
ETMX - on vertical I-beam of crane, IFO room 104_south end
Behind 1X3 Rack, on south wall - under instrument breakers panel PC-1, IFO room 104
Last thing remaining to be fixed from 2013 Safety Audit:
replace book shelf with 83" height
|
Attachment 1: refilledFAidK.jpg
|
|
8687
|
Thu Jun 6 16:33:19 2013 |
steve | Update | safety | updated laser inventory |
Updated laser inventory and operator list. They are posted in the 40m wiki and entry doors of the 40m IFO room.
Let me know if this list needs correction.
Lightwave M126N-1064-700 NPRO sn 337 in the PSL enclosure got connected to local emergency shut off switch. This is a LIGO operational safety requirement.
|
Attachment 1: ELSOconnected.jpg
|
|
9090
|
Fri Aug 30 08:08:29 2013 |
steve | Update | safety | fire horns-flashers tested OK |
We had fire alarm tests and evacuation drills at 1:30pm yesterday. All flashers and horns are functioning unbearably loud and bright including clean assembly room. |
9653
|
Wed Feb 19 08:07:01 2014 |
steve | Update | safety | annual laser safety glasses check |
All 40m laser safety glasses are cleaned and measured this morning. Bring your own safety glasses if you have to enter the 40m IFO room.
Glasses were washed in 1% Liquinox water solution and their transmission measured at 165 mW, 2 mm OD beam of 1064 nm |
Attachment 1: AA2014checked.jpg
|
|
Attachment 2: 2014check.jpg
|
|
9672
|
Tue Feb 25 16:54:57 2014 |
steve | Update | safety | safety audit 2014 |
We had our annual safety inspection today. Our SOPs are outdated. The full list of needed correction will be posted tomorrow.
The most useful found was that the ITMX-ISCT ac power is coming from 1Y1 rack. This should actually go to 1Y2 LSC rack ?
Please test this so we do not create more ground loops. |
9681
|
Thu Feb 27 13:11:13 2014 |
steve | Update | safety | safety audit correction |
Quote: |
We had our annual safety inspection today. Our SOPs are outdated. The full list of needed correction will be posted tomorrow.
The most useful found was that the ITMX-ISCT ac power is coming from 1Y1 rack. This should actually go to 1Y2 LSC rack ?
Please test this so we do not create more ground loops.
|
Linus-1, Nodus and others ac cords can be moved over to new blank yellow extension cord with multiple recepticals.
Remove two red extension cords going to Smart UPS |
Attachment 1: noDaisyChaining.jpg
|
|
Attachment 2: ZbThumbnail.info
|
9699
|
Thu Mar 6 11:43:17 2014 |
steve | Update | General | Guralp control unit |
CMG-40T handheld controller unit is missing its power supply. In order to zero the instrument one has to apply plus and minus DC voltage.
The wiring on this 10 pin Amphenol PT02E-12-10P is shown. |
Attachment 1: GuralpCU.jpg
|
|
Attachment 2: BAH.jpg
|
|
9704
|
Fri Mar 7 16:56:17 2014 |
steve | Update | IOO | IOO qpds centered |
Quote: |
Quote: |
The IMC has not been behaving well since this morning and totally not happy when Q was finishing his measurements. The WFS servo had large offsets in pitch. Looking back at the trend and using ezcaservo to restore the suspensions did not help.
I realigned the IMC and brought TRANS SUM to ~18000 and MCREFL to < 0.5. The spot positions are not very good; nearly 2 mm off in pitch on MC1 and MC3. But after the alignment of MC, the WFS servo offsets were below +/-20.
The MC has been locked stably with WFS servo ON for the last few hours.
P.S. I did not touch the WFS pointing or reset the WFS offsets.
|
MC remained locked with WFS enabled all through last night and this morning. Koji dropped by and looked at the MC. The MC WFS servo, though stable, was at the edge of becoming unstable. This was because I did not touch the WFS pointing on the QPDs yesterday after realigning. So I recentered the WFS, reset the WFS filterbank offsets and reenabled the servo.
I measured the spot positions on MC mirrors for reference.
Spot positions in mm (MC1,2,3 pit MC1,2,3 yaw): [1.405767579680834, 0.79369009503571208, 1.3220430681427462, -1.2937873599406551, -1.1704264340968924, -1.2518046122798692]
|
|
Attachment 1: IOOqpdCentered.png
|
|
9705
|
Mon Mar 10 09:28:48 2014 |
steve | Update | IOO | IOO pointing 2 days |
Morning seconds without adjustment.
|
Attachment 1: IOOpointing2d.png
|
|
Attachment 2: morningseconds.png
|
|
9725
|
Thu Mar 13 16:05:48 2014 |
steve | Update | safety | safety audit 2014 |
Quote: |
We had our annual safety inspection today. Our SOPs are outdated. The full list of needed correction will be posted tomorrow.
The most useful found was that the ITMX-ISCT ac power is coming from 1Y1 rack. This should actually go to 1Y2 LSC rack ?
Please test this so we do not create more ground loops.
|
Annual crane inspection is scheduled for 8-11am Monday, March 17, 2014
The control room Smart UPS has two red extension cords that has to be removed: Nodus and Linux1 |
Attachment 1: T1400198-v1-CIT-LIGO_Labs_Annual_Safety_Audit_2014.pdf
|
|
9730
|
Mon Mar 17 10:50:58 2014 |
steve | Update | safety | 2014 annual crane certification |
Quote: |
Quote: |
We had our annual safety inspection today. Our SOPs are outdated. The full list of needed correction will be posted tomorrow.
The most useful found was that the ITMX-ISCT ac power is coming from 1Y1 rack. This should actually go to 1Y2 LSC rack ?
Please test this so we do not create more ground loops.
|
Annual crane inspection is scheduled for 8-11am Monday, March 17, 2014
The control room Smart UPS has two red extension cords that has to be removed: Nodus and Linux1
|
KroneCrane Fred inspected and certified the 3 40m cranes for 2014. The vertex crane crane was load tested at fully extended position. |
Attachment 1: 2014craneCert.jpg
|
|
9743
|
Fri Mar 21 14:59:44 2014 |
steve | Update | PEM | controling dust |
Please take a look at the table top with the flashlight before removing it. If it is dusty, wipe it down with dry lint free cloth in the box.
There is one box with flash light and wiper at AP, ETMY & ETMX optical tables. |
Attachment 1: IMG_0044.JPG
|
|
9748
|
Mon Mar 24 22:13:37 2014 |
steve | Update | General | Power Failure |
Quote: |
I'm checking the status from home.
P1 is 8e-4 torr
nodus did not feel the power outage (is it APS supported?)
linux1 booted automatically
c1ioo booted automatically.
c1sus, c1lsc, c1iscex, c1iscey need manual power button push.
|
9:11pm closed PSL shutter, turned Innolight 2W laser on,
turned 3 IFO air cond on,
CC1 5.1e-5 torr, V1 is closed, Maglev has failed, valve configuration is " Vacuum Normal " with V1 & VM1 closed, RGA not running, c1vac1 and c1vac2 were saved by UPS,
(Maglev is not connected to the UPS because it is running on 220V)
reset & started Maglev.........I can not open V1 without the 40mars running...........
Rossa is the only computer running in the control room,
Nodus and Linux1 was saved by UPS,
turned on IR lasers at the ends, green shutters are closed
It is safe to leave the lab as is.
|
Attachment 1: poweroutage.png
|
|
9749
|
Tue Mar 25 14:52:57 2014 |
steve | Update | VAC | vacuum is recovered |
Out gassing plus leak rate 0.15 mTorr / hour
The pressure rose to 2.5 mTorr in 17 hours
V1 was opened at 1:56pm
VM2 opened at 2:10 so the RGA region is back to 1e-5 torr
|
Attachment 1: 17hrsNoPumping.png
|
|
9757
|
Fri Mar 28 16:26:20 2014 |
steve | Update | VAC | RGA scan after power failure |
Quote: |
Out gassing plus leak rate 0.15 mTorr / hour
The pressure rose to 2.5 mTorr in 17 hours
V1 was opened at 1:56pm
VM2 opened at 2:10 so the RGA region is back to 1e-5 torr
|
|
Attachment 1: afterPowerFailure.png
|
|
9802
|
Fri Apr 11 14:57:53 2014 |
steve | Update | LSC | congratulation |
|
Attachment 1: whenSheisHappy3h.png
|
|
Attachment 2: mc4hArms3hrs.png
|
|
9870
|
Mon Apr 28 17:27:29 2014 |
steve | Update | safety | safety audit 2014 |
Quote: |
Quote: |
We had our annual safety inspection today. Our SOPs are outdated. The full list of needed correction will be posted tomorrow.
The most useful found was that the ITMX-ISCT ac power is coming from 1Y1 rack. This should actually go to 1Y2 LSC rack ?
Please test this so we do not create more ground loops.
|
Annual crane inspection is scheduled for 8-11am Monday, March 17, 2014
The control room Smart UPS has two red extension cords that has to be removed: Nodus and Linux1
|
Last long extension cord removed from 1Y1 to ITMX-ISCT
The AC power strip at ITMX-ISCT is coming from wall L#26 |
9873
|
Tue Apr 29 00:11:03 2014 |
steve | Update | safety | safety audit 2014 |
Be aware that this may affect POP QPD and POP RF Thorlabs PD
Quote: |
Last long extension cord removed from 1Y1 to ITMX-ISCT
The AC power strip at ITMX-ISCT is coming from wall L#26
|
|
9895
|
Thu May 1 17:14:36 2014 |
steve | Update | PSL | thin window AR measured |
CVI broadband AR coating was measured at the PSL-enclosure table around 9-10am today. The 2W Innolight first PBS S polarization beam was used with an other 1/2 wave plate and PBS.
W2-PW1-1004-C-633-1064-0 This 0.045" thick window has 0.7- 0.8 % reflected beam on each sides at 5 degrees of incidence, P polarization.
The specification is R avg <0.5 % per surface at 0 degree
Rana wants The device would be useless with such a high R, but R 0.1% is OK so I will get V coating.
|
9900
|
Fri May 2 08:15:54 2014 |
steve | Update | safety | safety audit 2014 |
Late adition: CHECK all viewport covers.
A, transparent Lexan sheet is protecting glass windows in a horizontal position
B, metal housing protection is required on each viewport except signal ports
C, signal ports should be shielded by optical table enclosure
We have to cover this window-camera with implosion proof cover or just remove it and blank it.
Question number 2: Do our vertically positioned windows with flip able covers require protective lexan ? NO 5-5-2014 |
Attachment 1: solidCoverRequired.jpg
|
|
9902
|
Fri May 2 10:38:29 2014 |
steve | Update | PSL | thin window AR measured |
Quote: |
CVI broadband AR coating was measured at the PSL-enclosure table around 9-10am today. The 2W Innolight first PBS S polarization beam was used with an other 1/2 wave plate and PBS.
W2-PW1-1004-C-633-1064-0 This 0.045" thick window has 0.7- 0.8 % reflected beam on each sides at 5 degrees of incidence, P polarization.
The specification is R avg <0.5 % per surface at 0 degree
Rana wants The device would be useless with such a high R, but R 0.1% is OK so I will get V coating.
|
CVI V-AR coating at 1064 nm, 0 degree, catalog item is R< 0.25% on each sides,
R <0.1 % is custom at much higher prices.
This custom order should go with other orders that has similar need.
From CVI: 5-6-2014
I checked the trace info on the W2-PW1-1004-C-633-1064-0, BBAR coated window that you received. It is side 1, 0.42%R & side 2, 0.53%R @ 1064nm. And with the shift, I’m not too surprised you ended up with 0.7%. A V coat would start with <0.25% (and more typically coming in at ~0.1%) per surface. As far as stock options, I have a 1”dia x 4mmT, fused silica window that is recorded as side 1, R=0.09 and Side 2, R=0.08% @ 1064. Is this too think or will it work for you?
|
9914
|
Tue May 6 09:46:50 2014 |
steve | Update | PEM | cleaning day |
Keven and Steve,
We cleaned around the Vertex chambers, PSL and MC2 floor areas.
|
Attachment 1: 120d.png
|
|
9915
|
Tue May 6 10:22:28 2014 |
steve | Update | CDS | c1ioo dolphin fiber |
Quote: |
Steve and I nicely routed the dolphin fiber from c1ioo in the 1X2 rack to the dolphin switch in the 1X4 rack. I shutdown c1ioo before removing the fiber, but still all the dolphin connected models crashed. After the fiber was run, I brought back c1ioo and restarted all wedged models. Everything is green again:

|
I put label at the dolphin fiber end at 1X2 today. After this I had to reset it, but it failed. |
Attachment 1: dolphin1x2.png
|
|
9918
|
Tue May 6 18:32:14 2014 |
steve | Update | LSC | TRY 60Hz noise hunt |
This is an effort to get rid of our ground loops by isolating the electronic components from the optical table.
Aluminum mounting base plates of Thorlabs BA2 and Newport B-2 were replaced by plates or post made out of delrin material.
This is an insulator. DELRIN base plates were installed 6 places. The oplev-qpd has Nylon base plate.
The NPRO and HE/NE lasers are not isolated from the table. S8 and S9
I'm not sure about the doubling oven S10 
The optical table is grounded at G11 through ~1 Mohms to the ETMY chamber.
Alignment touch up needed at all D-marked component!
|
Attachment 1: ETMY-ISCT_EISOL.jpg
|
|
9921
|
Wed May 7 14:01:36 2014 |
steve | Update | LSC | TRY 60Hz noise hunt |
Quote: |
This is an effort to get rid of our ground loops by isolating the electronic components from the optical table.
Aluminum mounting base plates of Thorlabs BA2 and Newport B-2 were replaced by plates or post made out of delrin material.
This is an insulator. DELRIN base plates were installed 6 places. The oplev-qpd has Nylon base plate.
The NPRO and HE/NE lasers are not isolated from the table. S8 and S9
I'm not sure about the doubling oven S10 
The optical table is grounded at G11 through ~1 Mohms to the ETMY chamber.
Alignment touch up needed at all D-marked component!
|
Attachment appendix:
D: component delrin isolated
N: component nylon isolated ( or Delrin )
S: component shell is shorting to optical table (except oven)
G: optical table ground
I failed to maximize TRY the pds. |
9933
|
Thu May 8 17:25:17 2014 |
steve | Update | LSC | TRY 60Hz noise hunt |
I worked at the ETMY-ISCT this morning and late afternoon. I will continue the 60 Hz noise hunt tomorrow. |
9937
|
Fri May 9 11:23:11 2014 |
steve | Update | Green Locking | decreased X green light power |
Green light power decreased from 3 mW to 1 mW at the ETMX-ISCT shutter. More later. |
9941
|
Mon May 12 14:42:25 2014 |
steve | Update | endtable upgrade | optical table enclosure wall proposal and table at ETMY |
Quote: |
Sanwiched wall as shown: 1" clear acrylic, 2 layers of 0.004" thick "window tint", 1 layer of 0.007" thermashield and 0.125" yellow acrylic
Visibility: 70 %, Transmission of 1064 nm 2-3 % at 0-50 degrees incident, power density ~ 0.7 W/mm2
Max power 100 mW
|
More details about this east end " acrylic + " enclosure ( optical table cover ) can be found elog entry 6210, 7194 and 7106
Window tinted layer transmission plot is below.
We have a film which may meet your requirements and the values are shown below:
Wavelength (nm) Transmission Reflectance(front) Reflectance (back)
1060 .0772 .604 .759
1070 .0723 .615 .772
These values are taken from the LBNL Optics 6 program and if you have access to that program, the NFRC ID for the film is 202. If you do not have access to the program, I have a captured the graph which may be of some help. I apologize for the appearance of the graph but someone at LBNL decided it would look better with a dark gray background – the yellow is the transmission curve, the blue is the reflectance (front) and the green is the reflectance (back).

The film is referred to as “Hilite 70” and has a 72% visible light transmission. These results were obtained with the film mounted on 1/8” clear glass.
I
Saint-Gobain Performance Plastics
www.solargard.com
Please consider your environmental responsibility before printing this email.
|
|
|
|
Attachment 1: Hilite70.jpg
|
|
Attachment 2: ETMY-ISCT.jpg
|
|
Attachment 3: RoscoThermashield.pdf
|
|
9965
|
Fri May 16 16:08:12 2014 |
steve | Update | LSC | Isolating base plates |
Electronic components should be ISOLATED as they are installed on the optical tables.
This is essential to avoid ground loops, 60 Hz and harmonic peaks in the spectrum. We have just got some made.
Please only use it for this reason. Earlier black delrin base plates were used up in not needed places.
The anodized Aluminum base plates with magenets certainly will conduct.
|
Attachment 1: ISObaseplates.jpg
|
|
10007
|
Mon Jun 9 09:41:06 2014 |
steve | Update | safety | safety training |
2014 surf students Nichin and Akhil received 40m specific basic safety training last week. |
Attachment 1: 2014surfs.jpg
|
|
10069
|
Thu Jun 19 10:39:22 2014 |
steve | Update | safety | surf safety training |
Andres Medina and Andrew "Harry" Hall received 40m specific safety training. They did general safety already and their laser safety training will be this after noon. |
Attachment 1: 2014surfsAA.jpg
|
|
10071
|
Thu Jun 19 14:12:45 2014 |
steve | Update | safety | optical table scans |
PSL, AP, ETMY and ETMX optical tables were scanned for stay beam. |