7454
|
Mon Oct 1 09:02:17 2012 |
Steve | Update | VAC | pumpdown reached vacuum normal |
Quote: |
The new cold cathode gauge CC1 is in place. We were at atmosphere for 28 days ......more later
|
cc1 = 2.3e-5 Torr at day 6 vacuum normal |
Attachment 1: pd73md6.png
|
|
Attachment 2: pd73md6b.png
|
|
7461
|
Tue Oct 2 09:13:16 2012 |
Steve | Update | VAC | RGA scan at day 7 |
Quote: |
Quote: |
The new cold cathode gauge CC1 is in place. We were at atmosphere for 28 days ......more later
|
cc1 = 2.3e-5 Torr at day 6 vacuum normal
|
|
Attachment 1: pd73md7.png
|
|
7491
|
Fri Oct 5 14:40:55 2012 |
Steve | Update | VAC | RGA scan after power outage |
Quote: |
All the front end machines are back up after the outage. It looks like none of the front end machines came back up once power was restored, and they all needed to be powered manually. One of the things I want to do in the next CDS upgrade is put all the front end computers in one rack, so we can control their power remotely.
c1sus was the only one that had a little trouble. It's timing was for some reason not syncing with the frame builder. Unclear why, but after restarting the models a couple of times things came back.
There's still a little red, but it mostly has to do with the fact that c1oaf is busted and not running (it actually crashes the machine when I tried to start it, so this needs to be fixed!).
|
The RGA was not effected by the short power outage. |
Attachment 1: afterpoweroutaged10.png
|
|
Attachment 2: pd73m10d.png
|
|
7545
|
Mon Oct 15 08:12:45 2012 |
Steve | Update | VAC | blank vac monitor |
VME crate blew its fuse and the fuse housing is hard to access. |
Attachment 1: blankvac.png
|
|
7547
|
Mon Oct 15 13:07:51 2012 |
jamie | Update | VAC | vacuum VME crate broken, replaced, minor vacuum mayhem ensues |
Steve and I managed to access the fuse in the vacuum VME crate, but replacing it did not bring it back up. We decided to replace the entire crate.
We manually checked that the most important valves, VC1, VM1 and V1, were all closed. We disconnected their power so that they would automatically close, and we wouldn't have to worry about them accidentally opening when we rebooted the system.
We noted where all the cables were, disconnected everything, and removed the crate. We noted that one of the values switched when we disconnected one of the IPC cables from a VME card. We'll note which one it was in a followup post. We thought that was a little strange, since the VME crate was completely unpowered.
Anyway, we removed the crate, swapped in a spare, replaced all the cards and connections, double checked everything, then powered up the crate. That's when minor chaos ensued.
When the system came back online after about 20 seconds, we heard a whole bunch of valves switching. Luckily we were able to get the medm screens back up so that we could see what was going on.
Apparently all of the ION pump valves (VIPEE, VIPEV, VIPSV, VIPSE) opened, which vented the main volume up to 62 mTorr. All of the annulus valves (VAVSE, VAVSV, VAVBS, VAVEV, VAVEE) also appeared to be open. One of the roughing pumps was also turned on. Other stuff we didn't notice? Bad.
We ran around and manually unplugged all of the ION pump valves, since I couldn't immediately pull up the vacuum control screen. Once that was done and we could see that the main volume was closed off we went back to figure out what was going on.
We got the medm vacuum control screen back (/cvs/cds/caltech/medm/c0/ve/VacControl_BAK.adl. really??) There was a lot of inconsistency between the readback states of the valves and the switch settings. Toggling the switches seemed to bring things back in line. At this point it seemed that we had control of the system again. The epics readings were consistent with what we were seeing in the vacuum rack.
We went through and closed everything that should have been closed. The line pressure between the big turbo pump TP1 and the rest of the pumps was up at atmosphere, 700 Torr. We connected the roughing pumps and pumped down the lines so that we could turn the turbos back on. Once TP2 and TP3 were up to speed, we turned on TP1 and opened V1 to start pumping the main volume back town. The main volume is at 7e-4 Torr right now.
So there are a couple of problems with the vacuum system.
- Why the hell did valves open when we rebooted the VME crate? That's very bad. That should never happen. If the system is set to come up to an unsafe state that needs to be fixed ASAP. The ION pump valves should never have opened. Nor the annulus valves.
- Why were the switches and the readbacks showing different states?
- Apparently there is no control of the turbo pumps through MEDM. This should be fixed.
I connect belledona, the laptop at the vacuum station to the wired network, so that it's connection would be less flaky.
|
7549
|
Mon Oct 15 17:08:01 2012 |
Steve | Update | VAC | vacuum is back with some disabled valves |
Quote: |
Quote: |
Apparently all of the ION pump valves (VIPEE, VIPEV, VIPSV, VIPSE) opened, which vented the main volume up to 62 mTorr. All of the annulus valves (VAVSE, VAVSV, VAVBS, VAVEV, VAVEE) also appeared to be open. One of the roughing pumps was also turned on. Other stuff we didn't notice? Bad.
|
Several of the suspensions were kicked pretty hard (600+ mV on some sensors) as a result of this quick vent wind. All of the suspensions are damped now, so it doesn't look like we suffered any damage to suspensions.
|
CLOSE CALL on the vacuum system:
Jamie and I disabled V1, VM2 and VM3 gate valves by disconnecting their 120V solenoid actuator before the swap of the VME crate.
The vacuum controller unexpectedly lost control over the swap as Jamie described it. We were lucky not to do any damage! The ion pumps were cold and clean. We have not used them for years so their outgassing possibly accumulated to reach ~10-50 Torr
I disconnected_ immobilized and labelled the following 6 valves: the 4 large ion pump gate valves and VC1, VC2 of the cryo pump. Note: the valves on the cryo pump stayed closed. It is crucial that a warm cry pump is kept closed!
This will not allow the same thing to happen again and protect the IFO from warm cryo contamination.
The down side of this that the computer can not identify vacuum states any longer.
This vacuum system badly needs an upgrade. I will make a list. |
Attachment 1: VMEcrateout.png
|
|
Attachment 2: IMG_1725.JPG
|
|
Attachment 3: warning.png
|
|
Attachment 4: shortcomings.jpg
|
|
7564
|
Wed Oct 17 08:04:31 2012 |
Steve | Update | VAC | Roughing pumps on for oil change |
PR1, PR2 and RP3 turned on for warming up for oil change. Oil changed with 3.2L of MVT-19 fluid in each. This substitute for HE-175 will be used at the next oil change - it has 1E-6 Torr vapor pressure.
To finish this job tomorrow: 1, check oil creeping upstream 2, change air filter of air purge if pressure drops <350 mTorr 3, measure venting time of pump |
7582
|
Fri Oct 19 16:45:39 2012 |
Steve | Update | VAC | vent has started |
Quote: |
VENT NOW and FIX ALIGNMENT!
|
PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now. Jenne is taking over here. |
7584
|
Fri Oct 19 19:26:42 2012 |
Jenne | Update | VAC | vent has started |
Quote: |
PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now. Jenne is taking over here.
|
Valves closed, 500 torr. Steve will finish off Monday morning, then we'll take off doors and get to work. |
7587
|
Mon Oct 22 09:10:07 2012 |
Steve | Update | VAC | @750Torr |
Quote: |
Quote: |
PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now. Jenne is taking over here.
|
Valves closed, 500 torr. Steve will finish off Monday morning, then we'll take off doors and get to work.
|
We are almost at atm. P1 750 Torr, We are slowly reaching equilibrium. |
Attachment 1: ventOct222012.png
|
|
7594
|
Tue Oct 23 08:45:00 2012 |
Steve | Update | VAC | vent day 3 |
Quote: |
Quote: |
Quote: |
PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now. Jenne is taking over here.
|
Valves closed, 500 torr. Steve will finish off Monday morning, then we'll take off doors and get to work.
|
We are almost at atm. P1 750 Torr, We are slowly reaching equilibrium.
|
The access connector was removed, BS and ITMY chambers were opened yesterday.
New one piece aluminum shell access connector installed. Jenne lowered the PSL out put into MC to ~100mW |
Attachment 1: ventd4.png
|
|
Attachment 2: IMG_1743.JPG
|
|
7597
|
Tue Oct 23 16:18:03 2012 |
Steve | Update | VAC | Roughing pumps on for oil change |
Leybold D30AQuote: |
PR1, PR2 and RP3 turned on for warming up for oil change. Oil changed with 3.2L of MVT-19 fluid in each. This substitute for HE-175 will be used next time.
To finish this job tomorrow: 1, check oil creeping upstream 2, change air filter of air purge if pressure drops <350 mTorr 3, measure venting time of pump
|
. Leybold D30A manual is here. Exhaust filter traps were drained. No oil creeping was found. The pump venting time is < 1 minute.
PR-2 needs new secu-valve. PR1 & 2 are in excellent condition. |
Attachment 1: oilchange.jpg
|
|
7605
|
Wed Oct 24 09:15:12 2012 |
Steve | Update | VAC | vacuum rack 24V ps was current limited |
Quote: |
Quote: |
Quote: |
Apparently all of the ION pump valves (VIPEE, VIPEV, VIPSV, VIPSE) opened, which vented the main volume up to 62 mTorr. All of the annulus valves (VAVSE, VAVSV, VAVBS, VAVEV, VAVEE) also appeared to be open. One of the roughing pumps was also turned on. Other stuff we didn't notice? Bad.
|
Several of the suspensions were kicked pretty hard (600+ mV on some sensors) as a result of this quick vent wind. All of the suspensions are damped now, so it doesn't look like we suffered any damage to suspensions.
|
CLOSE CALL on the vacuum system:
Jamie and I disabled V1, VM2 and VM3 gate valves by disconnecting their 120V solenoid actuator before the swap of the VME crate.
The vacuum controller unexpectedly lost control over the swap as Jamie described it. We were lucky not to do any damage! The ion pumps were cold and clean. We have not used them for years so their outgassing possibly accumulated to reach ~10-50 Torr
I disconnected_ immobilized and labelled the following 6 valves: the 4 large ion pump gate valves and VC1, VC2 of the cryo pump. Note: the valves on the cryo pump stayed closed. It is crucial that a warm cry pump is kept closed!
This will not allow the same thing to happen again and protect the IFO from warm cryo contamination.
The down side of this that the computer can not identify vacuum states any longer.
This vacuum system badly needs an upgrade. I will make a list.
|
While I was doing the oil change of the roughing pumps I accidentally touched the 24 V adjustment knob on the power supply.
All valve closed to default condition. I realized that the current indicator was red at 0.2A and the voltage fluctuated from 3-13V
Increased current limiter to 0.4A and set voltage to 24V I think this was the reason for the caos of valve switching during the VME swap.
|
Attachment 1: currentlimited24V.jpg
|
|
7669
|
Mon Nov 5 10:34:48 2012 |
Steve | Update | VAC | existing vacuum documents |
Quote: |
Quote: |
Quote: |
Quote: |
Apparently all of the ION pump valves (VIPEE, VIPEV, VIPSV, VIPSE) opened, which vented the main volume up to 62 mTorr. All of the annulus valves (VAVSE, VAVSV, VAVBS, VAVEV, VAVEE) also appeared to be open. One of the roughing pumps was also turned on. Other stuff we didn't notice? Bad.
|
Several of the suspensions were kicked pretty hard (600+ mV on some sensors) as a result of this quick vent wind. All of the suspensions are damped now, so it doesn't look like we suffered any damage to suspensions.
|
CLOSE CALL on the vacuum system:
Jamie and I disabled V1, VM2 and VM3 gate valves by disconnecting their 120V solenoid actuator before the swap of the VME crate.
The vacuum controller unexpectedly lost control over the swap as Jamie described it. We were lucky not to do any damage! The ion pumps were cold and clean. We have not used them for years so their outgassing possibly accumulated to reach ~10-50 Torr
I disconnected_ immobilized and labelled the following 6 valves: the 4 large ion pump gate valves and VC1, VC2 of the cryo pump. Note: the valves on the cryo pump stayed closed. It is crucial that a warm cry pump is kept closed!
This will not allow the same thing to happen again and protect the IFO from warm cryo contamination.
The down side of this that the computer can not identify vacuum states any longer.
This vacuum system badly needs an upgrade. I will make a list.
|
While I was doing the oil change of the roughing pumps I accidentally touched the 24 V adjustment knob on the power supply.
All valve closed to default condition. I realized that the current indicator was red at 0.2A and the voltage fluctuated from 3-13V
Increased current limiter to 0.4A and set voltage to 24V I think this was the reason for the caos of valve switching during the VME swap.
|
I asked Jamie to read these docs so we can do some troubleshooting while at atmosphere. We have to have the all valve closed DEFAULT condition working-tested.
I'd like to reconnect all valves after this test so the state identification software could work, including interlocks.
Posted the following documents on 40m wiki.
http://www.ligo.caltech.edu/~ajw/40m/40mVaccum_T000054-00.pdf
http://www.ligo.caltech.edu/~ajw/40m/40mProcedures.doc
https://dcc.ligo.org/DocDB/0015/D000338/000/D000338-00.pdf |
7696
|
Mon Nov 12 09:21:10 2012 |
Steve | Update | VAC | pumpdown has started |
I'm looking for IOO steering mirror power supplies. I found two so far: one at 1Y3 as Kepco + 75V and one at OMC_North rack -150V
Are there any more? The OMC is off.
ANSWER: only one of the steering PZT can be driven, so see their power supplies |
Attachment 1: beforepd.png
|
|
Attachment 2: IMG_1800.JPG
|
|
Attachment 3: IMG_1801.JPG
|
|
7697
|
Mon Nov 12 16:52:03 2012 |
Steve | Update | VAC | pumpdown has completed |
The pressure is CC1 3e-4 Torr at 8 hours of pumping. Status: vacuum normal
The IFO is ready for light
|
Attachment 1: pd74.png
|
|
Attachment 2: pd74at8h.png
|
|
7703
|
Tue Nov 13 08:34:11 2012 |
Steve | Summary | VAC | pumpdown after 24days at atmosphere |
|
Attachment 1: pd74d1.png
|
|
Attachment 2: 24datm.png
|
|
Attachment 3: pdd1.png
|
|
7753
|
Tue Nov 27 09:44:09 2012 |
Steve | Update | VAC | pumpdown at 15 days |
It took 15 days to reach 1e-5 Torr
The RGA was turned on yesterday. The rga scan plotting was not working. Den wrote a Python script to log and plot because the Mathlab had trouble receiving data from our old c0raga.
It turned out that the Joe's log&plot system was working today. Thanks Den and Joe.
Here is the first rga scan.
|
Attachment 1: pd74m15d.png
|
|
Attachment 2: pd74m15d_rga1d.png
|
|
7849
|
Tue Dec 18 10:43:20 2012 |
Steve | Update | VAC | vent has completed |
The 40m vacuum envelope is at atm It took 4.5 hours at ~3 Torr/min speed. Atm1
What I did:
Turned PZT voltages off: 84.1V at OMC-rack location
- 99V at 1Y3 location as PZT_pitch,
56.6V KEPCO at 1Y3 location as PZT_yaw
Took screen shuts of SUS_SUMMARY, yesterday, Atm3
Turned off OPLEV _SERVOs, today , Atm2
Closed PSL_SHUTTER and green shutters at the ends
Set vacuum valves for vent position and opened VM2 for the RGA
|
Attachment 1: vent74.png
|
|
Attachment 2: bvent.png
|
|
Attachment 3: befVent.png
|
|
7853
|
Tue Dec 18 16:37:40 2012 |
Steve | Update | VAC | last RGA scan before vent |
|
Attachment 1: pd74m36d.png
|
|
Attachment 2: 36d_vacuum_normal.png
|
|
7856
|
Wed Dec 19 11:53:23 2012 |
Steve | Update | VAC | AC removed |
Koji, Manasa, Jenne, Jamie, Bob and Steve
Access connector removed this morning and work has began in the IOO chamber. BE WARE OF ANTS !
|
Attachment 1: workingatatm.png
|
|
7914
|
Thu Jan 17 17:04:49 2013 |
Steve | Update | VAC | vac monitor screen changed |
The COVAC_MONITOR.adl was changed. Ion pump labeled as disconnected means: ion pump controller power turned off and ion pump gate valve control connection disconnected.
RP2 roughing pump labeled disconnected means: hardware disconnected.
The actual operational, valve control screen has not been changed yet. |
Attachment 1: screenmod.png
|
|
7936
|
Thu Jan 24 08:28:35 2013 |
Steve | Update | VAC | when to pumpdown ? |
Reminder: I will be on vacation next week. We would have to put the access connector in tonight if I'm pumping down Friday, tomorrow. |
7939
|
Thu Jan 24 14:40:09 2013 |
Steve | Update | VAC | RGA backgroung |
RGA background with VM2 open to Maglev at day 37
Note: The PAN gauge of the annulos is at atm. Please do not vent this 200 ft long annulos line when you venting the annulos of a chamber. The chamber annulos should be closed off to this long 2" OD. pipe before you vent the annulos of a chamber.
|
Attachment 1: Screenshot.png
|
|
8057
|
Mon Feb 11 16:16:27 2013 |
Steve | Update | VAC | 55 days at atmoshere |
CP Stat 100 sheet-covers were replaced by clean ones on open chambers BS, ITMX, ITMY and ETMY this morning.
Try to fold the sheets such way that the clean side is facing each other, so they do not accumulate dust.
|
Attachment 1: atm55d.png
|
|
8106
|
Tue Feb 19 08:42:31 2013 |
Koji | Update | VAC | ETMX door open |
[Steve, Yuta, Koji]
The ETMX heavy door was removed. |
8129
|
Thu Feb 21 15:21:07 2013 |
yuta | Update | VAC | all heavy doors on, started pumping down annulus |
[Steve, Manasa, Jenne, Sendhil, Evan, Yuta]
We put heavy doors on ITMX/ITMY/BS chamber and started pumping down from annulus.
What we did:
1. Replaced POP55 with AS55 back, because it was not broken.
2. Centered on AS55, REFL55, REFL11, POPDC PD.
3. Tried to lock PRMI, but I couldn't lock even MI stably for more than 1 min. I believe this is because it was noisy this morning. But I checked again that REFL/POP/AS beams are coming out without clipping and we have some error signals.
4. Noticed AS beam has less range in left (on AS camera), so we tweaked OM4 a little to make more room.
6. Took pictures inside ITMX and BS chambers
7. Put heavy doors on ITMX/ITMY/BS chambers.
8. Started pumping down annulus.
9. Recentered IPANG/IPPOS and oplevs on their QPDs.
POP, REFL, AS:
|
8131
|
Thu Feb 21 18:01:27 2013 |
Steve | Update | VAC | pumpdown at 230 Torr |
We are pumping down with RP1 & RP3 oily roughing pumps at 3 Torr/min speed. The butterfly valve was just removed.
The PSL shutter is open to vacuum at ~100 mW 1064 nm. The inter lock should close it at ~5 mTorr.
Rana will shut down pumping tonight.
He will close V3 from screen, close RV1 valve with torque wheel, turn off roughing pumps and disconnect hose between RV1 and roughing pumps.
I will restart pumping early morning tomorrow.
|
8134
|
Thu Feb 21 21:12:42 2013 |
Koji | Update | VAC | pumpdown at 230 Torr |
[Rana, Yuta, Koji]
21:05 at the pressure of 10torr
V3 closed. RV1 manually closed. RPs were turned off. And the bellows between RV1 and the rughing pumps are disconnected. |
8135
|
Fri Feb 22 08:01:25 2013 |
Steve | Update | VAC | pumpdown continuous |
Pump down is restarted after 10.5 hrs stop overnight. |
Attachment 1: 16hrs_pd75.png
|
|
8136
|
Fri Feb 22 11:12:16 2013 |
Steve | Update | VAC | pumpdown completed |
IFO P1 pressure is 1 mTorr. It is ready for high power light.
The Maglev took over the pumping at 500 mTorr
|
Attachment 1: mag60min.png
|
|
Attachment 2: pd75at20h.png
|
|
8155
|
Mon Feb 25 08:22:03 2013 |
Steve | Update | VAC | pumpdown at day 4 |
All normal, IFO pressure 1.5e-5 Torr
RGA is pumped by TP-3 in back ground mode.
|
Attachment 1: 4d.png
|
|
Attachment 2: 66d@atm.png
|
|
8206
|
Fri Mar 1 14:50:36 2013 |
Steve | Update | VAC | pumpdown day 8 |
Atm1, RGA background scan with TP3 pumping at day 7
Atm2, IFO CC1 = 1.1e-5 Torr at day 8
Vacuum valve VM3 closed and VM2 opened, it switched the RGA to IFO scanning mode. CC4 = 3.5e-6 Torr
TP3 is pumping on the annuloses, their pressures are 1-3 mTorr
Vacuum condition reached the state of Vacuum Normal. The MEDM screen "Current State" channel does not work because we disconnected some valves after the VME swap CAOS
Note: TP1 Maglev performance on Atm2 CC4 = 4e-9 Torr when VM2 valve was open
|
Attachment 1: bgTP3d7.png
|
|
Attachment 2: RGAonIFO.png
|
|
8231
|
Tue Mar 5 14:59:32 2013 |
Steve | HowTo | VAC | dry-forepump replaced |
TP3 turbo pump's dry-foreline pump was replaced.
How to do it:
The pump should be replaced when it's performance <1.0 - 1.3 Torr
Set up valve configuration as shown at Atm1: close in this order VAEE, VASV, VABS, VASV, VASE, VA6 and V5,
Turn TP3 off at it's controller in the rack. Wait till is stops, so you can read 760 Torr at TP3 foreline gauge
Disconnect intake, exhaust vacuum seals and replace pump. Reconnect vacuum fitting and start it up.
Confirm operational details on the front of the controller: 50 K_RPM, 0.2A and <100 mTorr
Reset valves in reverse order
PS: the average life of the tip seal on the Varian SSH-110 dry-pump is about 1 year
This pump " ser LP1007L556 " seal made new record of 668 days: thanks to Bob Taylor who is replacing these seals
|
Attachment 1: changingforepump.png
|
|
Attachment 2: TP3wFp600.jpg
|
|
8238
|
Wed Mar 6 08:40:03 2013 |
Steve | Update | VAC | first scan of this pumpdown |
Pumpdown 75 - Maglev - day 12
Precondition: 66 days at atm, installed TIP-TILTs with coils that replaced PZT-Jena input steering
|
Attachment 1: pd75m12d.png
|
|
Attachment 2: pd75mRGA12d.png
|
|
8311
|
Tue Mar 19 17:00:14 2013 |
Steve | Update | VAC | large window quote of Cascade |
Optical quality 6.5" OD window specs and quotes for vacuum view ports and optical table enclosure are on the 40m wiki_ Aux Optics page.
We have just received a very good quote #2 from Cascade Optical. |
8664
|
Mon Jun 3 09:46:40 2013 |
Steve | Update | VAC | RGA scan at day 100 |
Vacuum normal condition at pumdown day 100
|
Attachment 1: d100Mpd75.png
|
|
Attachment 2: d100Mpd75p.png
|
|
Attachment 3: badguys.png
|
|
8847
|
Mon Jul 15 14:12:15 2013 |
Steve | Update | VAC | RGA scan at day 144 |
Pumpdown 75, vacuum normal condition at day 144
|
Attachment 1: pd75mRGA144d.png
|
|
Attachment 2: pd75m144d.png
|
|
8904
|
Tue Jul 23 08:21:31 2013 |
Steve | Update | VAC | Vent has started |
Thanks for the good preparation. IFO pressure P1=20 Torr |
Attachment 1: beforVent.png
|
|
Attachment 2: startVent.png
|
|
8907
|
Tue Jul 23 14:00:03 2013 |
Steve | Update | VAC | the vent is completed |
The 40m IFO has reached atmospher in 5 hours. It is ready to open chamber condition. The RGA is pumped with the maglev.
P1 pirani gauge is contact dependent as you see it on the linear plot It will be replaced during this vent.
The venting speed was 2-4 Torr / min
Atm2 shows how the BS is sensing the venting air cylinder changes.
The 4th cylinder of instrument grade air bump is overlapping with our janitor working at the BS chamber.
|
Attachment 1: Atm.png
|
|
Attachment 2: 5cyl.png
|
|
Attachment 3: ventSum1d.png
|
|
8914
|
Tue Jul 23 22:55:13 2013 |
Jenne | Update | VAC | BS, ITMY doors to be opened in the morning |
We will open the BS and ITMY doors first thing tomorrow morning. I plan to try to be in around 9 am. The first order of business will be to flip the folding mirrors that are not currently flipped (SR2, SR3, PR3). |
8915
|
Wed Jul 24 10:35:41 2013 |
Steve | Update | VAC | BS, ITMY doors are removed |
Quote: |
We will open the BS and ITMY doors first thing tomorrow morning. I plan to try to be in around 9 am. The first order of business will be to flip the folding mirrors that are not currently flipped (SR2, SR3, PR3).
|
Jenne, Annalisa & Steve |
Attachment 1: beforeDoorsOff.png
|
|
Attachment 2: particlecount10d.png
|
|
8933
|
Mon Jul 29 16:04:40 2013 |
Steve | Update | VAC | AC removed |
Manasa, Eric, Evan, Koji and Steve,
Access connector removed in order to complete alignment. Light aluminum with acetate windows AC installed.
|
Attachment 1: acout.png
|
|
Attachment 2: AlAcACa.jpg
|
|
Attachment 3: AlAcACb.jpg
|
|
8934
|
Mon Jul 29 16:15:13 2013 |
Koji | Update | VAC | AC removed |
Prior to the access connector removal, Manasa and I aligned the IFO mirrors.
The arms were locked and aligned by ASS. |
8946
|
Wed Jul 31 10:27:00 2013 |
Steve | Update | VAC | instrument grade air is discontinoued |
We have been using Air Liquide Instrument Grade Air for venting the 40m vacuum envelope. It is no longer available.
The replacement is Alphagas 1, total hydrocarbon <0.1% ppm
LINK TO Alphagaz

Air Liquide > ALPHAGAZ™ Specifications

ALPHAGAZ™ Specifications
ALPHAGAZ™ range of Pure Gases for Analysis: two purity levels tailored to cover all your analytical needs.
Because each analytical application is sensitive to critical impurities that can affect your results, tests in our research center and analyzer manufacturers' studies confirm that the main impurities are moisture, oxygen and hydrocarbons.
Based on these critical impurities, Air Liquide has developed ALPHAGAZ™ brand with a Maximum Impurity Level (H2O, O2, CnHm).
- The Maximum Impurity Level is the same across the whole product range. This constitutes a guarantee of quality with regard to major critical impurities and contamination tracers. ALPHAGAZ™ 2 offers an even greater guarantee in terms of purity (CO, CO2, H2).
- The Minimum Total Purity is a prerequisite for product quality, but we do not stop there: Air Liquide selects and controls its gas sources by defining specifications regarding impurities that are critical for your analysis or application.
ALPHAGAZ™ 1 |
ALPHAGAZ™ 1 |
ALPHAGAZ™ 2 |
ALPHAGAZ™ 2 |
ALPHAGAZ™ AUTO IV |
ALPHAGAZ™ CO2 SFC |
He, N2, H2,
Ar, O2 |
Air |
He, N2, H2,
Ar, O2 |
Air |
Air*, N2, O2 |
CO2 |
Specifications (ppm vol): |
H2O < 3 ppm
O2 < 2 ppm
CnHm < 0.5 ppm |
H2O< 3 ppm
CnHm< 0.1 ppm
CO2 < 1 ppm
CO < 1 ppm |
H2O < 0.5 ppm
O2 < 0.1 ppm
CO2 < 0.1 ppm
CO < 0.1 ppm
CnHm < 0.1 ppm
H2 < 0.1 ppm |
H2O < 0,5 ppm
CnHm < 50 ppb
CO2 < 0,1 ppm
CO < 0,1 ppm
NOx < 10 ppb *
SO2 < 10 ppb* |
CnHm < 0.2 ppm
CO2 < 0.5 ppm
CO < 0.5 ppm
NO/NOx < 0.1 ppm |
H2O < 5 ppm
O2 < 2 ppm
CnHm < 2 ppm
NVOC* < 2 ppm
CO < 5 ppm
NO + NO2 < 2 ppm
S Total < 1 ppm
H2 < 0.5 ppm |
|
20 ± 1 % O2 (Europe)
21 ± 1% O2 (North America) |
|
20,9 ± 1 % O2
*: Detection limit |
*20 ± 1 % O2 |
*NVOC: Non Volatile Organic Compounds |
Minimum Total Purity |
|
8963
|
Mon Aug 5 10:50:48 2013 |
Steve | Update | VAC | RGA background |
RGA background at day 12 of this vent . The maglev is pumping on the rga through VM2
|
Attachment 1: v75bgMd12.png
|
|
8970
|
Tue Aug 6 10:06:29 2013 |
Steve | Update | VAC | Pumpdown is at 500Torr |
The pumpdown has started at 8:38am
Manasa was here to confirm good alignment of the IFO
Inner jam nuts of AC bellow were torqued to 45 ft/lbs and door nuts were check on opened chambers.
Annulos were roughed down to 500 mTorr
Oplev servos turned off, PSL and green shutters closed before pumpdown started
|
Attachment 1: befPd.png
|
|
8973
|
Tue Aug 6 16:45:31 2013 |
Steve | Update | VAC | Pumpdown is completed |
IFO P1=1mT PSL shutter is opened
|
Attachment 1: 8hrPd76.png
|
|
Attachment 2: 1mT.png
|
|
8976
|
Wed Aug 7 10:51:49 2013 |
Steve | Update | VAC | Pumpdown at 26hrs |
Cold cathode gauge CC1 -h (horizontal) just coming on 9.2e-5 Torr
P2 is the fore line pressure of the maglev. One can see the 4 Torr load during switching over to turbo pumping.
CC4 5e-9 Torr is the performance of the maglev pumping on the RGA only.
The annuloses are not pumped now. They are closed off to see how much outgassing plus leak they have.
Configuration: vacuum normal, annuloses not pumped
Condition: normal
Precondition: 14 days at atm, IOO chamber north door was taken off as a new entrance, the ETMX chamber was not opened.
What is new in the vacuum system: new P1 pirani gauge, gold plated clean allen wrench and ..........what else was dropped?
Note: the wireless laptop did not fail once all day yesterday. I want to give credit to the person who is responsible for this.
|
Attachment 1: 26hr.png
|
|
Attachment 2: 14datm.png
|
|
8978
|
Wed Aug 7 15:36:29 2013 |
Steve | Update | VAC | TP2 drypump replaced |
TP2's fore line - dry pump replaced at performance level 600 mTorr after 10,377 hrs of continuous operation.
Where are the foreline pressure gauges? These values are not on the vac.medm screen.
The new tip seal dry pump lowered the small turbo foreline pressure 10x
TP2fl after 2 day of pumping 65mTorr |
Attachment 1: forelinesPs.jpg
|
|