2568
|
Wed Feb 3 11:13:15 2010 |
steve | Configuration | General | planed power outage for Sat. Feb 20 |
The electrical shop has to connect the new power transformer at CES. This means we will have no AC power for ~8 hrs on Saturday, February 20
Is this date good for us to power down ALL equipment in the lab?
Rana: Yes |
2585
|
Wed Feb 10 16:27:47 2010 |
steve | Configuration | General | IFO beam heights |
IN VACUUM beam heights are ALL 5.5" This is measured from the top of the optical table to the center of all TMs, mirrors and other optical components. This beam is ~36" above the floor.
PSL (inside of enclosure) main-output beam: PMC, MZ, RC and ISS are at 3" heights. IOO Angle & Position, MC-Trans and RFAM qpds are at 4"
ALL OTHER beam heights at atmosphere and different ISCT (interferrometer sensing, control optical table)s are at 4"
|
2612
|
Thu Feb 18 10:10:43 2010 |
steve | Configuration | General | 480 V AC power turned off |
Only the 40m cranes are running on 480VAC The electricians are rewiring this transformer on the mezzanine so it was shut down.
I tested all three cranes before the 480V power was turned off. The last thing to do with the cranes to wipe them down before use.
It will happen on next Tuesday morning. |
2617
|
Fri Feb 19 13:28:44 2010 |
Koji | Update | General | Prep for Power Supply Stop |
- ETMX/ETMY oplev paths renewed. The nominal gain for ETMY YAW was reversed as a steering mirror has been put.
- Oplevs/QPDs cenrtered except for the MCT QPD.
- SUS snapshots updated
- QPD/Aligment screenshots taken
40m Wiki: Preparation for power supply stop
|
Attachment 1: screen_shot.png
|
|
2620
|
Sun Feb 21 17:44:35 2010 |
rana | Update | General | Prep for Power Supply Stop |
- Turned on the RAID attached to linux1 (its our /cvs/cds disk)
- Turned on linux1 (it needed a keyboard and monitor in order to be happy - no fsck required)
- Turned on nodus (and started ELOG) + all the control room machines
- Turned on B/W monitors
- Untaped fridge
- Found several things OFF which were not listed in the Wiki...
- Turned ON the 2 big isolation transformers (next to Steve's desk and under the printer). These supply all of the CDS racks inside.
- ~75% of the power strips were OFF in the CDS racks ?? I turned on as many as I could find (except the OMC).
- Switched on and keyed on all of the FE and SLOW crates in no particular order. Some of the fans sound bad, but otherwise OK.
- Turned on all of the Sorensens that are labeled.
- Turned ON the linear supplies close to the LSC rack.
- ON the Marconis - set them according to the labels on them (probably out-dated).
- After restoring power to the PSL enclosure (via the Isolation Transformer under the printer) turned the Variac ON and HEPA on full speed.
- Plugged in the PSs for the video quads. Restored the Video MUX settings - looks like we forgot to save the correct settings for this guy...
PSL
1) Turned on the chiller, then the MOPA, then the RC's Heater power supply.
2) Shutter is open, laser is lasing, PMC is locked.
3) RC temperature is slowly rising. Will probably be thermalized by tomorrow.
Sun Feb 21 20:04:17 2010
Framebuilder is not mounting its RAID frames - in fact, it doesn't mount anything because the mountall command is failing on the RAID with the frames. The Jetstor RAID is also not responding to ping. Looks like the JetStor RAID which has all of our frames is still on the old 131 network, Joe. |
2621
|
Mon Feb 22 07:25:58 2010 |
rana | Update | General | Prep for Power Supply Stop |
Autoburts have not been working since the network changeover last Thursday.
Last snapshot was around noon on Feb 11... 
It turns out this happened when the IP address got switched from 131.... to 192.... Here's the horrible little piece of perl code which was failing:
$command = "/usr/sbin/ifconfig -a > $temp";
system($command);
open(TEMP,$temp) || die "Cannot open file $temp\n";
$site = "undefined";
#
# this is a horrible way to determine site location
while ($line = <TEMP>) {
if ($line =~ /10\.1\./) {
$site = "lho";
} elsif ($line =~ /10\.100\./) {
$site = "llo";
} elsif ($line =~ /192\.168\./) {
$site = "40m";
}
}
if ($site eq "undefined") {
die "Cannot Determine Which LIGO Observatory this is\n";
I've now put in the correct numbers for the 40m...and its now working as before. I also re-remembered how the autoburt works:
1) op340m has a line in its crontab to run /cvs/cds/caltech/burt/autoburt/burt.cron (I've changed this to now run at 7 minutes after the hour instead of at the start of the hour).
2) burt.cron runs /cvs/cds/scripts/autoburt.pl (it was using a perl from 1999 to run this - I've now changed it to use the perl 5.8 from 2002 which was already in the path).
3) autoburt.pl looks through every directory in 'target' and tries to do a burt of its .req file.
Oh, and it looks like Joe has fixed the bug where only op440m could ssh into op340m by editing the host.allow or host.deny file (+1 point for Joe).
But he forgot to elog it (-1 point for Joe).®
|
2622
|
Mon Feb 22 09:45:34 2010 |
josephb | Update | General | Prep for Power Supply Stop |
Quote: |
Autoburts have not been working since the network changeover last Thursday.
Last snapshot was around noon on Feb 11... 
It turns out this happened when the IP address got switched from 131.... to 192.... Here's the horrible little piece of perl code which was failing:
$command = "/usr/sbin/ifconfig -a > $temp";
system($command);
open(TEMP,$temp) || die "Cannot open file $temp\n";
$site = "undefined";
#
# this is a horrible way to determine site location
while ($line = <TEMP>) {
if ($line =~ /10\.1\./) {
$site = "lho";
} elsif ($line =~ /10\.100\./) {
$site = "llo";
} elsif ($line =~ /192\.168\./) {
$site = "40m";
}
}
if ($site eq "undefined") {
die "Cannot Determine Which LIGO Observatory this is\n";
I've now put in the correct numbers for the 40m...and its now working as before. I also re-remembered how the autoburt works:
1) op340m has a line in its crontab to run /cvs/cds/caltech/burt/autoburt/burt.cron (I've changed this to now run at 7 minutes after the hour instead of at the start of the hour).
2) burt.cron runs /cvs/cds/scripts/autoburt.pl (it was using a perl from 1999 to run this - I've now changed it to use the perl 5.8 from 2002 which was already in the path).
3) autoburt.pl looks through every directory in 'target' and tries to do a burt of its .req file.
Oh, and it looks like Joe has fixed the bug where only op440m could ssh into op340m by editing the host.allow or host.deny file (+1 point for Joe).
But he forgot to elog it (-1 point for Joe).®
|
I knew there was going to be a script somewhere with a hard coded IP address. My fault for missing it. However, in regards to the removal of op340m's host.deny file, I did elog it here. Item number 5. |
2625
|
Mon Feb 22 11:42:48 2010 |
Koji | Update | General | Prep for Power Supply Stop |
Turned on the power supply for the oplev lasers.
Turned on the power of the aux NPRO.
Turned on some of the Sorensen at 1X1.
Fixed the thermal output to round -4.0.
Locked PMC / MZ.
Waiting for the computers recovering. |
2630
|
Tue Feb 23 06:47:57 2010 |
Koji | Update | General | IFO situations / low power MC lock |
Work on 22nd Monday:
[MC recovery]
- Tried to lock MC after the computer recovery by Joe.
- A lot of higher modes. I can touch the input periscope or the MC mirrors.
- First tried to align the MC mirrors. MC1 was aligned against the MC REFL PD. MC2/3 was aligned to maximize the transmitted power.
- After the alignment, I got the MC Trans Sum ~8V. Also I saw the flashing of the arm cavities. I decided to take this alignment although the beam looks little bit clipped by the faraday.
[IFO alignment recovery]
- Aligned the arms for TEM00 manually.
- Arm alignment script seems not working now. This could come from the move of the end QPDs
- PRMI/DRMI were aligned. All alignment values saved.
[Low power MC]
[Optical config]
- I fixed the MCT CCD camera. It is quite useful to align the MC.
- Inserted HWP+Cube PBS+HWP combo in the MC incident path.
- First HWP and PBS adjust the light power. The second HWP is fixed at 342deg such that it restores the poralization to S.
- The incident power was measured by the SCIENTECH power meter. Offset of 3mW was subtracted in the table below.
HWP1 angle |
P_MC_incident |
comment |
126deg |
1.03W |
Max |
100 |
0.39 |
|
90 |
0.098 |
Low power max |
85 |
0.021 |
Low power nominal |
- HWP1 85deg is the nominal.
- I needed to touch the steering mirror (indicated by the picture) to obtain TEM00.
The alignment of the HWPs and the cube PBS didn't change the mode. Thermal lense of the cube?
- I could not lock the MC with the incident power below 100mW. So the BS in the MC REFL path was replaced by a total reflector (Y1-45S).
- This increased the power on the MC REFL PD x10 of the previous. NOW WE ARE CONSTRAINED BETWEEN 81deg~90deg. DON'T ROTATE FURTHER!
- The original BS was stored on the AP table as shown in the picture.
- This total reflector disabled the MC WFS QPDs. We can't use them.
[Lock of the MC with 20mW incident]
- Disable the MC autolocker.
- Disable the MC WFS.
- Run
/cvs/cds/caltech/scripts/MC/mcloopson
- Turn on the MCL servo.
- Set the MCL gain to 1.5 (it was nominally 0.3 for the high power)
- Just wait until lock.
[Gain boost after the lock] ...If you like to have more gain
- There was almost no room to increase the MCL gain.
- MC_REFL_GAIN can be increased from +6dB to +20dB
ezcawrite "C1:IOO-MC_REFL_GAIN" 20
- MC_VCO_GAIN can be increased from -3dB to +2dB
ezcawrite "C1:IOO-MC_VCO_GAIN" 2
- Crank the FSS gains
ezcawrite C1:PSL-FSS_MGAIN `ezcaread -n C1:PSL-STAT_FSS_NOM_C_GAIN`
ezcawrite C1:PSL-FSS_FASTGAIN `ezcaread -n C1:PSL-STAT_FSS_NOM_F_GAIN`
[If lock is lost]
- Run
/cvs/cds/caltech/scripts/MC/mcdown |
Attachment 1: MC_incident.png
|
|
Attachment 2: MC_REFL.png
|
|
2632
|
Tue Feb 23 14:56:24 2010 |
steve | Update | General | ETMX optical table mass |
Our janitor dropped one 48" long fluorescent tube on the top cover of ETMX-isct. This accident made glasses fly all over the place.
He cleaned up nicely, but please beware of small glass pieces around ETMX chamber.
We did not clean up on the table in order to reserve oplev and green ITMX pointing alignment.
Plot below shows that the alignment was not effected.
|
Attachment 1: etmxmass.jpg
|
|
2639
|
Thu Feb 25 11:21:06 2010 |
Koji | Update | General | Tanks opened |
[Steve, Bob, Joe, Zach, Alberto, Kiwamu, Koji]
We opened the OMC-IMC access connector, ITMX North door, and ITMY West door.
We worked from 9:30-11:00.
The work was quite smooth thanks to the nice preparation of Steve as usual.
Thank the team for the great work!
|
2643
|
Fri Feb 26 11:48:36 2010 |
Koji | Update | General | MC incident beam shift |
Last night I worked on the MC incident beam such that we can hit the center of the MC mirrors.
Steve and I checked the incident beam on MC1. We found the beam is ~5mm south.
This was not too critical but it is better to be realigned. I moved the steering mirror on the OMC
table (in vac). We kept the MC resonated. After the maximization of the resonance, I realigned the
MC1 and MC3 such that the resonance in dominated by TEM00.
Jenne, Kiwamu, and I then closed the light door on to the OMC/IMC.
I will make more detailed entry with photos in order to explain what and how I did. |
2645
|
Sun Feb 28 16:45:05 2010 |
rana | Summary | General | Power ON Recovery |
- Turned ON the RAID above linux1.
- Hooked up a monitor and keyboard and then turned ON linux1.
- After linux1 booted, turned ON nodus - then restarted apache and elog on it using the wiki instructions.
- Turned on all of the control room workstatiions, tuned Pandora to Johnny Cash, started the auto package updater on Rosalba (517 packages).
- Started the startStrip script on op540m.
- turned on RAID for frames - wait for it to say 'SATA', then turn on daqctrl and then fb40m and then daqawg and then dcuepics
- turned on all the crates for FEs, Sorensens, Kepcos for LSC, op340m, mafalda was already on
- fb40m again doesn't mount the RAID again!
- I turned on fb40m2 and that fixes the problem. The fb40m /etc/vfstab points to 198.168.1.2, not the JetStor IP address.
- I plugged in the Video Switch - its power cord was disconnected.
- FEs still timing out saying 'no response from EPICS', but Alberto is now here.
Sun Feb 28 18:23:09 2010
Hi. This is Alberto. Its Sun Feb 28 19:23:09 2010
- Turned on c1dcuepics, c0daqctrl and c0daqawg. c0daqawg had a "bad"status on the daqdetail medm screen. The FEs still don't come up.
- Rebooted c1dcuepics and power cycled c0daqctrl and c0daqawg. The problem is still there.
- Turned on c1omc. Problem solved.
- Rebooted c1dcuepics and power cycled c0daqctrl and c0daqawg. c0daqawg now good. The FE are coming up.
- Plugged in the laser for ETMY's oplev
- Turned on the laser of ETMX's oplev from its key.
Monday, March 1, 9:00 2010 Steve turns on PSL-REF cavity ion pump HV at 1Y1 |
2664
|
Tue Mar 9 09:32:31 2010 |
Koji | Summary | General | Wideband measurement of Fast PZT response |
I have measured a wideband response of the fast PZT in the LWE NPRO 700mW in the Alberto's setup.
This is a basic measurement to determine how much phase modulation we can obtain by actuating the fast PZT,
primarily for the green locking experiment.
RESULT
- Above 200kHz, there are many resonances that screws up the phase.
- Modulation of 0.1rad can be easily obtained even at 10MHz if the modulation frequency is scanned.
- Change of the laser frequency in DC was observed depending on the modulation frequency.
i.e. At the resonance the laser frequency escaped from the RF spectrum analyzer.
This may induced by the heat dissipation in the PZT causing the temperature change of the crystal.
- Some concerns: Is there any undesired AM by the PZT modulation?
---
METHOD
1. Locked the PLL of for the PSL-NPRO beating at 20MHz.
2. Added the modulation signal to the NPRO PZT input.
I used the output of the network analyzer sweeping from 100kHz to 1MHz.
3. Measured the transfer function from the modulation input to the PLL error signal.
The PLL error is sensitive to the phase fluctuation of the laser. Found that the first resonance is at 200kHz.
The TF is not valid below 3kHz where the PLL suppresses the modulation.
4. Single frequency modulation: Disconnected the PLL setup.
Plug Marconi into the fast PZT input and modulate it at various frequencies.
Observing with the RF spectrum analyzer, I could see strong modulation below 1MHz.
It turned out later that the TF measurement missed the narrow peaks of the resonances due to the poor freq resolution.
Also the modulation depth varies frequency by frequency because of the resonances.
Scanned the frequency to have local maximum of the modulation depth. Adjusted the
modulation amplitude such that the carrier is suppressed (J0(m)=0 i.e. m~2.4). As I could not obtain
the carrier suppression at above 1MHz, the height of the carrier and the sidebands were measured.
The modulation frequency was swept from 100kHz to 10MHz.
5. Calibration. The TF measured has been calibrated using the modulation depth obtained at 100Hz,
where the resonance does not affect the response yet.
The responce of the PZT was ~10MHz/V below 30kHz. Looks not so strange although this valure is
little bit high from the spec (2MHz/V), and still higher than my previous experience at TAMA (5MHz/V).
Note that this calibration does not effect to the modulation depth of the single freq measurement as they are independent. |
Attachment 1: PZT_response.png
|
|
2709
|
Wed Mar 24 12:40:25 2010 |
daisuke | Configuration | General | Periscope for green laser delivery from the BSC to PSL table |
The periscope design for beam elevation of the green beams is posted. The design for the 90 deg steering version is also coming.
(2010-03-29: update drawings by daisuke)
90deg version: http://nodus.ligo.caltech.edu:8080/40m/2725

|
Attachment 2: 40m_periscope_A_100329.pdf
|
|
Attachment 3: 40m_periscope_A_dwg_100329.zip
|
2725
|
Mon Mar 29 01:45:26 2010 |
daisuke | Configuration | General | Periscope version B for green laser ... |
Here the design of the periscope for the 90 deg steering version is posted.
straight version http://nodus.ligo.caltech.edu:8080/40m/2709 |
Attachment 1: 40m_periscope_B.png
|
|
Attachment 2: 40m_periscope_B_100329.pdf
|
|
Attachment 3: 40m_periscope_B_dwg_100329.zip
|
2746
|
Thu Apr 1 00:43:33 2010 |
Mott | Update | General | PZT response for the innolight |
Kiwamu and I measure the PZT response of the Innolight this evening from 24 kHz to 2MHz.
We locked the PLL at ~50 MHz offset using the Lightwave NPRO and and swept the Innolight with the network analyzer (using the script I made; it has one peculiar property, but it does work correctly).
We will post the plot of the Lightwave PZT response tomorrow morning.
**EDIT**: As Koji pointed out, the calibration factor on this plot is WRONG. See my more recent update for the correctly calibrated plot. |
Attachment 1: Innolight_Bode.png
|
|
2747
|
Thu Apr 1 07:17:15 2010 |
Koji | Update | General | PZT response for the innolight |
The shape of the TF looks nice but the calibration must be wrong.
Suppose 1/f slope with 10^-4 rad/V at 100kHz. i.e. m_pm = 10/f rad/V
This means m_fm = 10 Hz/V. This is 10^6 times smaller than that of LWE NPRO.
(Edit: Corrected some numbers but it is not significant)
Quote: |
Kiwamu and I measure the PZT response of the Innolight this evening from 24 kHz to 2MHz.
We locked the PLL at ~50 MHz offset using the Lightwave NPRO and and swept the Innolight with the network analyzer (using the script I made; it has one peculiar property, but it does work correctly).
We will post the plot of the Lightwave PZT response tomorrow morning.
|
|
2748
|
Thu Apr 1 10:21:58 2010 |
Mott | Update | General | PZT response for the innolight |
Quote: |
The shape of the TF looks nice but the calibration must be wrong.
Suppose 1/f slope with 10^-4 rad/V at 10kHz. i.e. m_pm = 1/f rad/V
This means m_fm = 1 Hz/V. This is 10^7 times smaller than that of LWE NPRO.
Quote: |
Kiwamu and I measure the PZT response of the Innolight this evening from 24 kHz to 2MHz.
We locked the PLL at ~50 MHz offset using the Lightwave NPRO and and swept the Innolight with the network analyzer (using the script I made; it has one peculiar property, but it does work correctly).
We will post the plot of the Lightwave PZT response tomorrow morning.
|
|
Koji is absolutely right. I just double checked my matlab code, and saw that I divided when I should have multiplied. The correctly calibrated plots are attached here for the Innolight and the lightwave. Kiwamu and I will measure the amplitude and the jitter today. |
Attachment 1: Innolight_Response.png
|
|
Attachment 2: Lightwave_response.png
|
|
2749
|
Thu Apr 1 10:47:48 2010 |
Koji | Update | General | PZT response for the innolight |
Innolight: 100rad/V @ 100kHz => 1e7/f rad/V => 10MHz/V
LWE: 500rad/V @ 100kHz => 5e7/f rad/V => 50MHz/V
They sound little bit too big, aren't they? |
2750
|
Thu Apr 1 12:07:22 2010 |
rana | Update | General | PZT response for the innolight |
The Lightwave NPRO should be around 5 MHz/V.
The Innolight PZT coefficient is ~1.1 MHz/V.
(both are from some Rick Savage LHO elog entries) |
2754
|
Thu Apr 1 18:05:29 2010 |
Mott | Update | General | PZT response for the innolight |
We realized that we had measured the wrong calibration value; we were using the free-running error signal with the marconi far from the beat frequency, which was very small. When we put the Marconi right at the beat, the signal increased by a factor of ~12 (turning our original calibration of 10 mV/rad into 120 mV/rad). The re-calibrated plots are attached. |
Attachment 1: Innolight_Response_calFix.png
|
|
Attachment 2: Lightwave_response_calFix.png
|
|
2755
|
Thu Apr 1 18:44:40 2010 |
Koji | Update | General | PZT response for the innolight |
Innolight 10 rad/V @ 100kHz => 1e6/f rad/V => 1MHz/V
LWE 30 rad/V @ 100kHz => 3e6/f rad/V => 3MHz/V
---------
BTW, don't let me calculate the actuator response everytime.
The elog (=report) should be somewhat composed by the following sections
Motivation - Method - Result (raw results) - Discussion (of the results)
Quote: |
We realized that we had measured the wrong calibration value; we were using the free-running error signal with the marconi far from the beat frequency, which was very small. When we put the Marconi right at the beat, the signal increased by a factor of ~12 (turning our original calibration of 10 mV/rad into 120 mV/rad). The re-calibrated plots are attached.
|
|
2756
|
Thu Apr 1 19:59:32 2010 |
Mott | Update | General | PZT response for the innolight |
We measured the Amplitude Modulation response of the PZTs, to find regions with large phase modulation but small amplitude modulation.
We did this by blocking 1 arm of the PLL, feeding the source output of the Network Analyzer into the PZT input of the laser in question, and reading the output of the PD on the NA. We calibrated by dividing by the DC voltage of the PD (scaled by the ratio of the AC gain to DC gain of the New Focus PD).
The AM response of the Innolight looks fairly smooth up to ~1MHz, and it is significantly below the PM response for most of its range. The region between 20 and 30 kHz shows very good separation of about 10^3 rad/RIN (and up to 10^5 rad/RIN at ~21.88 kHz, where there is the negative spike in the AM response). The region between 1.5 MHz and 2MHz also looks viable if it is desirable to actuate at higher frequencies.
The Lightwave offers very good AM/PM separation up to about 500 kHz, but becomes quite noisy about 1MHz. |
Attachment 1: Innolight_AM_Response.png
|
|
Attachment 2: Innolight_AM_PM.png
|
|
Attachment 3: InnoVsLW_PM.png
|
|
Attachment 4: Innolight_AM_Response.png
|
|
Attachment 5: Lightwave_AM_PM.png
|
|
2763
|
Sun Apr 4 17:32:07 2010 |
Alberto | Metaphysics | General | new y-arm? |
Quote: |
There's several more of the this vintage in one of the last cabinets down the new Y-arm.
|
Hold on, did the arms get re-baptized? |
2845
|
Mon Apr 26 12:24:58 2010 |
josephb | Update | General | Daily Downs update |
Talked with Jay briefly this morning.
We are due another 1-U 4 core (8 CPU) machine, which is one of the ones currently in the test stand. I'm hoping sometime this week I can convince Alex to help me remove it from said test stand.
The megatron machine we have is definitely going to be used in the 40m upgrade (to answer a question of Rana's from last Wednesday's meeting). Thats apparently the only machine of that class we get, so moving it to the vertex for use as the LSC or SUS vertex machine may make sense. Overall we'll have the ASS, OMC, Megatron (SUS?), along with the new 4 1-U machines, for LSC, IO, End Y and End X. We are getting 4 more IO chassis, for a total 5. ASS and OMC machine will be going without full new chassis.
Speaking of IO chassis, they are still being worked on. Still need a few cards put in and some wiring work done. I also didn't see any other adapter boards finished either. |
3063
|
Thu Jun 10 10:58:02 2010 |
Koji | Update | General | LaTeXlabs |
I could not dare to share my google doc with this site...
Quote: |
Quote: |
BTW, latex launched this new thing for writing pdfs. doesnot require any installations. check http://docs.latexlab.org
|
so cool!
|
|
3064
|
Thu Jun 10 11:10:21 2010 |
Alberto | Update | General | LaTeXlabs |
Quote: |
I could not dare to share my google doc with this site...
Quote: |
Quote: |
BTW, latex launched this new thing for writing pdfs. doesnot require any installations. check http://docs.latexlab.org
|
so cool!
|
|
Just in case, granted access to Google docs can be revoked any time from here:
https://www.google.com/accounts/IssuedAuthSubTokens |
3082
|
Wed Jun 16 18:14:13 2010 |
Aidan | Update | General | Glass cover from overhead light smashed on PSL table |
I was giving a tour of the 40m yesterday. We were looking at the PSL table. About 30 seconds after I turned the lights on a glass cover from one of the lights (NW corner) popped out of its holder and smashed on the table.
I've cleaned up all the broken glass I could see but there may be some small shards there. Please use caution in that area. |
Attachment 1: DSC_1769.JPG
|
|
Attachment 2: DSC_1768.JPG
|
|
3085
|
Fri Jun 18 13:42:52 2010 |
Koji | HowTo | General | Update your work |
All SURFs (and all others as always) are supposed to post the update of your status on the elog.
In fact, I already heard that Sharmila had been working on the serial connection to TC-200 and made some results. All of us like to hear the story. |
3103
|
Wed Jun 23 12:31:36 2010 |
Gopal | Update | General | 6.16.10-6.23.10 Weekly Update |
Summary of This Week's Activities:
6/16: LIGO Orientation; First Weekly Meeting; 40m tour with Jenne; Removed WFS Box Upper Panel, Inserted Cable, Reinstalled panel
6/17: Read Chapter 1 of Control Systems Book; LIGO Safety Meeting; Koji's Talk about PDH Techniques, Fabry-Perot Cavities, and Sensing/Control; Meeting w/ Nancy and Koji
6/18: LIGO Talk Part II; Glossed over "LASERS" book; Read Control Systems Book Chapter 2; Literary Discussion Circle
6/21: Modecleaner Matrix Discussion with Nancy; Suggested Strategy: construct row-by-row with perturbations to each d.f. --> Leads to some questions on how to experimentally do this.
6/22: Learned Simulink; Learned some Terminal from Joe and Jenne; LIGO Meeting; Rana's Talk; Christian's Talk; Simulink Intro Tutorial
6/23 (morning): Simulink Controls Tutorial; Successfully got a preliminary feedback loop working (hooray for small accomplishments!)
Outlook for the Upcoming Week:
Tutorials (in order of priority): Finish Simulink Tutorials, Work through COMSOL Tutorials
Reading (in order of priority): Jenne's SURF Paper, Controls Book, COMSOL documentation, Lasers by Siegman.
Work: Primarily COMSOL-related and pre-discussed with Rana |
3142
|
Wed Jun 30 11:35:06 2010 |
Gopal | Update | General | 6.23.10 - 6.30.10 Weekly Update |
Summary of this Week's Activities:
6/23: LIGO Safety Tour; Simulink Controls Tutorial
6/24: Simulink Diagram for Feedback Loop; Constructed Pendulum Transfer Function; Discussion with Dr. Weinstein
6/25: Prepare for pump-down of vacuum chamber; crane broken due to locking failure; worked through COMSOL tutorials
6/28: Ran through Python Tutorials; Began learning about Terminal
6/29: Wrote Progress Report 1 First Draft
6/30: Began editing Progress Report 1 |
3218
|
Wed Jul 14 12:31:11 2010 |
nancy | Update | General | Weekly Update |
Summary of this week's work
Wednesday - Aligned the mode cleaner with Koji, and then measured the beam characteristics at MC2 end. Koji then taught me how to read the WFS signals
Thursday - wrote a script to measure the signals and calculated the coefficients relating mirror movement and DC signals of WFS. To know the possibility of the control, found SVD of the coeff matrix, and condition number.
Friday - Set up the measurement of QPD linear response using a laser outside the cavity. Took data.
Monday - did the calculations and plotting for the above experiment. Then played around with the MEDM screens , and also tried to see what happens to the Power Spectrum of WFS signals by changing the coefficients in teh matrix. (failed)
Tuesday - played around with WFS, tried seeing what it does when switched on at different points, and also what it does when I disturb the system while WFS has kept it locked.
Today - had switched off the WFS sensors yesterday night after locking the MC as wanted to know that how does MC behave when no WFS gain is applied. I checked in the morning, the MC was locked all night.
I am now proceding with my calculations for the sensing matrix |
3251
|
Tue Jul 20 15:06:48 2010 |
josephb, bob | Omnistructure | General | New speakers in ceiling in control room |
After the crane training, Bob attached speakers to the ceiling right next to the projector, for use with presentations. |
3284
|
Sat Jul 24 13:13:41 2010 |
rana, steve, alberto | Update | General | Initial Crane Inspection reveals flaws: wiring and oil |
The guy from KroneCrane (sp?) came today and started the crane inspection on the X End Crane. There were issues with our crane so he's going to resume on Monday. We turned off the MOPA fur the duration of the inspection.
- None of our cranes have oil in the gearbox and it seems that they never did since they have never been maintained. Sloppy installation job. The crane oiling guy is going to come in on Monday.
- They tried to test the X-End crane with 2500 lbs. (its a 1 ton crane). This tripped the thermal overload on the crane as intended with this test. Unfortunately, the thermal overload switch disabled the 'goes down' circuit instead of the 'goes up' circuit as it should. We double checked the wiring diagram to confirm our hypothesis. Seems the X-End crane was wired up incorrectly in the first place 16 years ago. We'll have to get this fixed.
The plan is that they will bring enough weight to test it at slightly over the rating (1 Ton + 10 %) and we'll retry the certification after the oiling on Monday. |
3290
|
Mon Jul 26 10:04:24 2010 |
steve | Update | General | Initial Crane Inspection reveals flaws: wiring, oil and imbalance |
Quote: |
The guy from KroneCrane (sp?) came today and started the crane inspection on the X End Crane. There were issues with our crane so he's going to resume on Monday. We turned off the MOPA fur the duration of the inspection.
- None of our cranes have oil in the gearbox and it seems that they never did since they have never been maintained. Sloppy installation job. The crane oiling guy is going to come in on Monday.
- They tried to test the X-End crane with 2500 lbs. (its a 1 ton crane). This tripped the thermal overload on the crane as intended with this test. Unfortunately, the thermal overload switch disabled the 'goes down' circuit instead of the 'goes up' circuit as it should. We double checked the wiring diagram to confirm our hypothesis. Seems the X-End crane was wired up incorrectly in the first place 16 years ago. We'll have to get this fixed.
The plan is that they will bring enough weight to test it at slightly over the rating (1 Ton + 10 %) and we'll retry the certification after the oiling on Monday.
|
The south end crane has one more flaw. The wall cantilever is imbalanced: meaning it wants to rotate south ward, because its axis is off.
This effects the rope winding on the drum as it is shown on Atm2
Atm1 is showing Jay Swar of KoneCrane and the two 1250 lbs load that was used for the test. Overloading the crane at 125% is general practice at load testing.
It was good to see that the load brakes were working well at 2500 lbs. Finally we found a good service company! and thanks for Rana and Alberto
for coming in on Saturday. |
Attachment 1: 2500.JPG
|
|
Attachment 2: sedrum.JPG
|
|
3300
|
Tue Jul 27 16:33:50 2010 |
Koji | Summary | General | High school students tour |
Jenne made the 40m tour for the annual visit of 30-40 students.
c.f.
Tour 2009 http://nodus.ligo.caltech.edu:8080/40m/1717
Tour 2008 http://nodus.ligo.caltech.edu:8080/40m/737
|
Attachment 1: IMG_2657.jpg
|
|
3312
|
Wed Jul 28 16:42:21 2010 |
steve | Update | General | Crane gear box cheched |
Quote: |
Quote: |
The guy from KroneCrane (sp?) came today and started the crane inspection on the X End Crane. There were issues with our crane so he's going to resume on Monday. We turned off the MOPA fur the duration of the inspection.
- None of our cranes have oil in the gearbox and it seems that they never did since they have never been maintained. Sloppy installation job. The crane oiling guy is going to come in on Monday.
- They tried to test the X-End crane with 2500 lbs. (its a 1 ton crane). This tripped the thermal overload on the crane as intended with this test. Unfortunately, the thermal overload switch disabled the 'goes down' circuit instead of the 'goes up' circuit as it should. We double checked the wiring diagram to confirm our hypothesis. Seems the X-End crane was wired up incorrectly in the first place 16 years ago. We'll have to get this fixed.
The plan is that they will bring enough weight to test it at slightly over the rating (1 Ton + 10 %) and we'll retry the certification after the oiling on Monday.
|
The south end crane has one more flaw. The wall cantilever is imbalanced: meaning it wants to rotate south ward, because its axis is off.
This effects the rope winding on the drum as it is shown on Atm2
Atm1 is showing Jay Swar of KoneCrane and the two 1250 lbs load that was used for the test. Overloading the crane at 125% is general practice at load testing.
It was good to see that the load brakes were working well at 2500 lbs. Finally we found a good service company! and thanks for Rana and Alberto
for coming in on Saturday.
|
Jeff Stinson, technician of KoneCrane inspected the south end crane hoist gear box. This was the one that was really low on oil. The full condition require
~ 950cc of EPX-7 (50-70W) high viscosity gear oil. The remaining 120 cc oil was drained and the gear box cover was removed. See Atm 1
He found the gear box, load brake and gearing in good condition. The slow periodic sound of the drive was explained by the split bearings at Atm 3
The Vertex and the east end crane gear boxes needed only 60 cc oil to be added to each Atm 4 and their drives were tested.
Conclusion: all 3 gear boxes and drives are in good working condition.
Tomorrow's plan: load test at 1 ton and correct-check 3 phase wiring. |
Attachment 1: P1060503.JPG
|
|
Attachment 2: P1060511.JPG
|
|
Attachment 3: P1060515.JPG
|
|
Attachment 4: P1060517.JPG
|
|
3318
|
Thu Jul 29 12:31:09 2010 |
Koji | Summary | General | Lab Schedule |
July
29 Thu BS chamber work: Move cable towers / green steering mirrors / (2 TTs with TT charactrization) / Put the heavy door by 5PM.
30 Fri Pumping down
31 Sat WFS work by Nancy
Aug
1 Sun - 5 Thu WFS work by Nancy
5 Thu PSL Table prep
6 Fri PSL Table prep / Likely to shut down the PSL
9 Mon PSL Table prep / shutting down of the PSL (optional)
10 Tue PSL box Frame lifting
12 Thu PSL table tapping
16 Mon - 17 Tue concrete pouring preparation
19 Thu - 23 Fri Tripod placement
24 Tue - 26 Thu concrete pouring |
Attachment 1: PSL_work_schedule.pdf
|
|
3333
|
Fri Jul 30 14:53:09 2010 |
steve | Update | General | PSL table leg upgrade |
Quote: |
July
29 Thu BS chamber work: Move cable towers / green steering mirrors / (2 TTs with TT charactrization) / Put the heavy door by 5PM.
30 Fri Pumping down
31 Sat WFS work by Nancy
Aug
1 Sun - 5 Thu WFS work by Nancy
5 Thu PSL Table prep
6 Fri PSL Table prep / Likely to shut down the PSL
9 Mon PSL Table prep / shutting down of the PSL (optional)
10 Tue PSL box Frame lifting
12 Thu PSL table tapping
16 Mon - 17 Tue concrete pouring preparation
19 Thu - 23 Fri Tripod placement
24 Tue - 26 Thu concrete pouring
|
The PSL table height will be raised to the level of the AP table. This will be done using 6 TMC's Rigid Damped Tripod legs. Their planed positions shown below.
The legs will be grouted to the floor with concrete.
http://www.techmfg.com/products/floorplatforms/rigiddampedtripod.htm |
Attachment 1: psllegs.PDF
|
|
3335
|
Fri Jul 30 17:52:12 2010 |
Koji | Configuration | General | Jacket |
Jenne and I need our jackets. We removed them from the Rb clock.
Thanks for making them warm. Probably a Scotland sweater would fit. |
3337
|
Fri Jul 30 19:20:15 2010 |
Alastair | Configuration | General | Jacket |
Quote: |
Jenne and I need our jackets. We removed them from the Rb clock.
Thanks for making them warm. Probably a Scotland sweater would fit.
|
Thanks for the loan guys. I do have a lot of warm weather clothing at home that is not so necessary in the California climate. I will find some suitable attire for the Rb clocks there. |
3348
|
Mon Aug 2 17:12:28 2010 |
Koji | Update | General | Lab schedule for the week of Aug. 2 |
Aug
2 Mon - 5 Thu WFS work (Nancy)
2 Mon - 4 Wed
Jenne: Seismometer fix / Seismic measurements on the PSL table
TT characterization (with Koji)
Preparations ETM suspensions (optional: may be in later weeks)
Kiwamu: CDS test for SUS (may be involving Koji)
Alberto: RF system prep.
All: For 5th and 6th: PSL cabling works Koji
5 Thu PSL Table prep
6 Fri PSL Table prep / Likely to shut down the PSL
9 Mon PSL Table prep / shutting down of the PSL (optional)
10 Tue PSL box Frame lifting
12 Thu PSL table tapping
16 Mon - 17 Tue concrete pouring preparation
19 Thu - 23 Fri Tripod placement
24 Tue - 26 Thu concrete pouring |
Attachment 1: PSL_work_schedule.pdf
|
|
3368
|
Thu Aug 5 16:18:37 2010 |
Alastair | Update | General | clocks still not locked fully - hut removed |
The rubidium clocks are still not quite locked together, though it is clear that the beat frequency has dropped a lot since yesterday.
I checked on the clocks and the 1pps sync light is on. The clocks are really hot again though despite the gap left at the bottom of the igloo. The side of the clocks were hot enough to not be touchable.
I made the executive decision that I would remove the hut just now. We can let the clocks lock together and then put the hut back on just before measuring. This way the hut will isolate from temperature fluctuations during the measurement but it won't be running at the hotter equilibrium temperature. I hope that the temperature won't change too much during the measurement if we put the hut back on.
RA: Attachment deleted because it was in Postscript format. Also not allowed here are the Stone Tablet and Cave Painting formats. |
3377
|
Fri Aug 6 16:20:08 2010 |
rana | Update | General | clocks still not locked fully - phase shifted |
I tried to get the clocks to be closer to 90 deg for the relative phase by adding some cable length to one of the lines, but they are still wandering too much. We need to use the serial interface and up the gain in their 1PPS locking loops. |
Attachment 1: Untitled.pdf
|
|
3378
|
Fri Aug 6 17:47:36 2010 |
steve | Summary | General | cranes load tested at 1998 lbs |
Quote: |
Quote: |
Quote: |
The guy from KroneCrane (sp?) came today and started the crane inspection on the X End Crane. There were issues with our crane so he's going to resume on Monday. We turned off the MOPA fur the duration of the inspection.
- None of our cranes have oil in the gearbox and it seems that they never did since they have never been maintained. Sloppy installation job. The crane oiling guy is going to come in on Monday.
- They tried to test the X-End crane with 2500 lbs. (its a 1 ton crane). This tripped the thermal overload on the crane as intended with this test. Unfortunately, the thermal overload switch disabled the 'goes down' circuit instead of the 'goes up' circuit as it should. We double checked the wiring diagram to confirm our hypothesis. Seems the X-End crane was wired up incorrectly in the first place 16 years ago. We'll have to get this fixed.
The plan is that they will bring enough weight to test it at slightly over the rating (1 Ton + 10 %) and we'll retry the certification after the oiling on Monday.
|
The south end crane has one more flaw. The wall cantilever is imbalanced: meaning it wants to rotate south ward, because its axis is off.
This effects the rope winding on the drum as it is shown on Atm2
Atm1 is showing Jay Swar of KoneCrane and the two 1250 lbs load that was used for the test. Overloading the crane at 125% is general practice at load testing.
It was good to see that the load brakes were working well at 2500 lbs. Finally we found a good service company! and thanks for Rana and Alberto
for coming in on Saturday.
|
Jeff Stinson, technician of KoneCrane inspected the south end crane hoist gear box. This was the one that was really low on oil. The full condition require
~ 950cc of EPX-7 (50-70W) high viscosity gear oil. The remaining 120 cc oil was drained and the gear box cover was removed. See Atm 1
He found the gear box, load brake and gearing in good condition. The slow periodic sound of the drive was explained by the split bearings at Atm 3
The Vertex and the east end crane gear boxes needed only 60 cc oil to be added to each Atm 4 and their drives were tested.
Conclusion: all 3 gear boxes and drives are in good working condition.
Tomorrow's plan: load test at 1 ton and correct-check 3 phase wiring.
|
Atm1, service report: load test were performed at max horizontal reach with 1998 lbs ( American Ton is 2000 lbs)
Vertical drives and brakes worked well. The 5 minutes sagging test showed less than 1 mm movement .
The wiring is correct. Earlier hypothesis regarding the wiring ignored the mechanical brake action.
Our cranes are certified now. Operator training and SOP is in the work.
Vertex Folding I -beam will get latch-lock and the south end I-beam will be leveled.
Atm2, south end
Atm3, east end
Atm4, folding crane at ITMX at 14 ft horizontal reach |
Attachment 1: 0.9ton.PDF
|
|
Attachment 2: P1060523.JPG
|
|
Attachment 3: P1060532.JPG
|
|
Attachment 4: P1060541.JPG
|
|
3394
|
Tue Aug 10 17:21:48 2010 |
steve | Update | General | PSL optical table is at 30" height |
Mike Gerfen, Koji and Steve,
Our old ( 6 x 10 x 1 ) ft Newport optical table will have the same height as the neighboring AP table when this job is finished.
Today's work was to elevate the optical table ~ 2400 lbs to 30" clearance to create a workable space below.
Atm1, enclosure frame was raised by 6"
Atm2, 2 pellet jacks and 4x4 technology in the work.
Atm3, ready for drill and tap with jig plate in place, note 4 Al legs 8" OD. 1/4" wall safely supporting the load
Atm4, showing clamps that holding 1/2" plywood with jigs
Atm5, We removed the 4 old legs: 6" OD steel, 1/4" wall and 10" high after they were unloaded. |
Attachment 1: P1060586.JPG
|
|
Attachment 2: P1060583.JPG
|
|
Attachment 3: P1060591.JPG
|
|
Attachment 4: P1060593.JPG
|
|
Attachment 5: P1060597.JPG
|
|
3452
|
Fri Aug 20 20:36:05 2010 |
Alastair | Update | General | Elog |
Elog was down, I restarted it. |
3461
|
Tue Aug 24 06:34:01 2010 |
Alastair | Update | General | Elog... |
...was down. Have restarted it. |
3475
|
Fri Aug 27 07:21:13 2010 |
Alastair | Update | General | elog... |
was down. I restarted the version in the 2.7.5 folder. It went down again almost immediately but stayed up after the second restart. |