Tega | Update | Computer Scripts / Programs | Moved modbus service from chiara to c1susaux | [Tega, Anchal, Paco]
After talking to Anchal, it was made clear that chiara is not the place to host the modbus service for the temperature sensors. The obvious machine is c1pem, but the startup cmd script loads c object files and it is not clear how easy it would integrate the modbus functionality since we can only login via telnet, so we decided to instead host the service on c1susaux. We also modified the /etc/motd file on c1susaucx which displays the welcome message during login to inform the user that this machine hosts the modbus service for the temperature sensor. Anchal plans to also document this information on the temperature sensor wiki at some point in the future when the page is updated to include what has been learnt so far.
We might also consider updating the database file to a more modern way of reading the temperature sensor data using FLOAT32_LE which is available on EPICs version 3.14 and above, instead of the current method which works but leaves the reader bemused by the bitwise operations that convert the two 16 bits words (A and B) to IEEE-754 32-bit float, via
field(CALC, "(A&D?(A&C?-1:1):0)*((G|A&E)*J+B)*2^((A&D)/G-F)")
where
field(INPA, "$HiWord")
field(INPB, "$LoWord")
field(INPC, "0x8000") # Hi word, sign bit
field(INPD, "0x7F80") # Hi word, exponent mask
field(INPE, "0x00FF") # Hi word, mantissa mask (incl hidden bit)
field(INPF, "150") # Exponent offset plus 23-bit mantissa shift
field(INPG, "0x0080") # Mantissa hidden bit
field(INPJ, "65536") # Hi/Lo mantissa ratio
field(CALC, "(A&D?(A&C?-1:1):0)*((G|A&E)*J+B)*2^((A&D)/G-F)")
field(PREC, "4")
as opposed to the more modern form
field(INP,"@asyn($(PORT) $(OFFSET))FLOAT32_LE") |
16323
|
Mon Sep 13 17:05:04 2021 |
Tega | Summary | PEM | Infrasensing temperature sensor modbus configuration | Anchal mentioned it would be good to put more details about how I arrived at the values needed to configure the modbus drive for the temperature sensor, since this information is not in the manual and is hard to find on the internet, so here is a breakdown.
So the generic format is:
drvAsynIPPortConfigure("<TCP_PORT_NAME>","<UNIT_IP_ADDRESS>:502",0,0,1)
modbusInterposeConfig("<TCP_PORT_NAME>",0,5000,0)
drvModbusAsynConfigure("<PORT_NAME>","<TCP_PORT_NAME>",<slaveAddress>,<modbusFunction>,<modbusStartAddress>,<modbusLength>,<dataType>,<pollMsec>,<plcType>)
which in our case become:
drvAsynIPPortConfigure("c1pemxendtemp","192.168.113.240:502",0,0,1)
modbusInterposeConfig("c1pemxendtemp",0,5000,0)
drvModbusAsynConfigure("C1PEMXENDTEMP","c1pemxendtemp",0,4,199,2,0,1000,"ServerCheck")
As can be seen, the parameters of the first two functions "drvAsynIPPortConfigure" and "modbusInterposeConfig" are straight forward, so we restrict our discussion to the case of third function "drvModbusAsynConfigure". Well, after hours of trolling the internet, I was able to piece together a coherent picture of what needs doing and I have summarised them in the table below.
drvModbusAsynConfigure
Once the asyn IP or serial port driver has been created, and the modbusInterpose driver has been configured, a modbus port driver is created with the following command:
drvModbusAsynConfigure(portName, # used by channel definitions in .db file to reference this unit)
tcpPortName, # reference to portName created with drvAsynIPPortConfigure command
slaveAddress, #
modbusFunction, #
modbusStartAddress, #
modbusLength, # length in dataType units
dataType, #
pollMsec, # how frequently to request a value in [ms]
plcType); #
drvModbusAsynConfigure command |
Parameter |
Data type |
Description |
portName |
string |
Name of the modbus port to be created.
|
tcpPortName |
string |
Name of the asyn IP or serial port previously created.
tcpPortName = { 192.168.113.240:502, 192.168.113.241:502, 192.168.113.242:502 }
|
slaveAddress |
int |
The address of the Modbus slave. This must match the configuration of the Modbus slave (PLC) for RTU and ASCII. For TCP the slave address is used for the "unit identifier", the last field in the MBAP header. The "unit identifier" is ignored by most PLCs, but may be required by some.
ServersCheck API ignores this value, as confirmed with pymodbus query, so set to default value:
slaveAddress = 0
|
modbusFunction |
int |
modbus supports the following 8 Modbus function codes:
Modbus Function Codes |
Access |
Function description |
Function code |
Bit access |
Read Coils |
1 |
Bit access |
Read Discrete Inputs |
2 |
Bit access |
Write Single Coil |
5 |
Bit access |
Write Multiple Coils |
15 |
16-bit word access |
Read Input Registers |
4 |
16-bit word access |
Read Holding Registers |
3 |
16-bit word access |
Write Single Register |
6 |
16-bit word access |
Write Multiple Registers |
16 |
|
modbusStartAddress |
int |
Start address for the Modbus data segment to be accessed.
(0-65535 decimal, 0-0177777 octal).
Modbus addresses are specified by a 16-bit integer address. The location of inputs and outputs within the 16-bit address space is not defined by the Modbus protocol, it is vendor-specific. Note that 16-bit Modbus addresses are commonly specified with an offset of 400001 (or 300001). This offset is not used by the modbus driver, it uses only the 16-bit address, not the offset.
For ServersCheck, the offset is "30001", so that
modbusStartAddress = 30200 - 30001 = 199
|
modbusLength |
int |
The length of the Modbus data segment to be accessed.
This is specified in bits for Modbus functions 1, 2, 5 and 15.
It is specified in 16-bit words for Modbus functions 3, 4, 6 and 16.
Length limit is 2000 for functions 1 and 2, 1968 for functions 5 and 15,
125 for functions 3 and 4, and 123 for functions 6 and 16.
ServersCheck uses two's complement 32-bits word (with big-endian byte order & little-endian word order) format to store floating-point data, as confirmed with pymodbus query, so that:
modbusLength = 2
|
modbusDataType |
int |
The modbusDataType is used to tell the driver the format of the Modbus data. The driver uses this information to convert the number between EPICS and Modbus. Data is transferred to and from EPICS as epicsUInt32, epicsInt32, and epicsFloat64 numbers.
Modbus data type:
0 = binary, twos-complement format
1 = binary, sign and magnitude format
2 = BCD, unsigned
3 = BCD, signed
Some Modbus devices (including ServersCheck) use floating point numbers, typically by storing a 32-bit float in two consecutive 16-bit registers. This is not supported by the Modbus specification, which only supports 16-bit registers and single-bit data. The modbus driver does not directly support reading such values, because the word order and floating point format is not specified.
Note that if it is desired to transmit BCD numbers untranslated to EPICS over the asynInt32 interface, then data type 0 should be used, because no translation is done in this case.
For ServersCheck, we wish to transmit the untranslated data, so:
modbusDataType = 0
|
pollMsec |
int |
Polling delay time in msec for the polling thread for read functions.
For write functions, a non-zero value means that the Modbus data should
be read once when the port driver is first created.
ServersCheck recommends setting sensor polling interval between 1-5 seconds, so we can try:
pollMsec = 1000
|
plcType |
string |
Type of PLC (e.g. Koyo, Modicon, etc.).
This parameter is currently used only to print information in asynReport.
In the future it could be used to modify the driver behavior for a specific PLC.
plcType = "ServersCheck"
|
Useful links
https://nodus.ligo.caltech.edu:8081/40m/16214
https://nodus.ligo.caltech.edu:8081/40m/16269
https://nodus.ligo.caltech.edu:8081/40m/16270
https://nodus.ligo.caltech.edu:8081/40m/16274
http://manuals.serverscheck.com/InfraSensing_Sensors_Platform.pdf
http://manuals.serverscheck.com/InfraSensing_Modbus_manualv5.pdf
https://community.serverscheck.com/discussion/comment/7419#Comment_7419
https://wiki-40m.ligo.caltech.edu/CDS/SlowControls
https://www.slac.stanford.edu/grp/ssrl/spear/epics/site/modbus/modbusDoc.html#Creating_a_modbus_port_driver
https://github.com/riptideio/pymodbus
https://en.wikipedia.org/wiki/Modbus
https://deltamotion.com/support/webhelp/rmctools/Communications/Ethernet/Supported_Protocols/Ethernet_Modbus_TCP.htm |
16322
|
Mon Sep 13 15:14:36 2021 |
Anchal | Update | LSC | Xend Green laser injection mirrors M1 and M2 not responsive | I was showing some green laser locking to Tega, I noticed that changing the PZT sliders of M1/M2 angular position on Xend had no effect on locked TEM01 or TEM00 mode. This is odd as changing these sliders should increase or decrease the mode-matching of these modes. I suspect that the controls are not working correctly and the PZTs are either not powered up or not connected. We'll investigate this in near future as per priority. |
16321
|
Mon Sep 13 14:32:25 2021 |
Yehonathan | Update | CDS | c1auxey assembly | So we agreed that the RTNs points on the c1auxex Acromag chassis should just be grounded to the local Acromag ground as it just needs a stable reference. Normally, the RTNs are not connected to any ground so there is should be no danger of forming ground loops by doing that. It is probably best to use the common wire from the 15V power supplies since it also powers the VME crate. I took the spectra of the ETMX OSEMs (attachment) for reference and proceeding with the grounding work.
|
Attachment 1: ETMX_OSEMS_Noise.png
|
|
16320
|
Mon Sep 13 09:15:15 2021 |
Paco | Update | LSC | MC unlocked? | Came in at ~ 9 PT this morning to find the IFO "down". The IMC had lost its lock ~ 6 hours before, so at about 03:00 AM. Nothing seemed like the obvious cause; there was no record of increased seismic activity, all suspensions were damped and no watchdog had tripped, and the pressure trends similar to those in recent pressure incidents show nominal behavior (Attachment #1). What happened?
Anyways I simply tried reopening the PSL shutter, and the IMC caught its lock almost immediately. I then locked the arms and everything seems fine for now . |
Attachment 1: VAC_2021-09-13_09-32-45.png
|
|
16319
|
Mon Sep 13 04:12:01 2021 |
Tega | Update | General | Added temperature sensors at Yend and Vertex too | I finally got the modbus part working on chiara, so we can now view the temperature data on any machine on the martian network, see Attachment 1.
I also updated the entries on /opt/rtcds/caltech/c1/chans/daq/C0EDCU.ini, as suggested by Koji, to include the SensorGatway temperature channels, but I still don't see their EPICs channels on https://ldvw.ligo.caltech.edu/ldvw/view. This means the channels are not available via nds so I think the temperature data is not being to be written to frame files on framebuilder but I am not sure what this entails, since I assumed C0EDCU.ini is the framebuilder daq channel list.
When the EPICs channels are available via nds, we should be able to display the temperature data on the summary pages.
Quote: |
I've added the other two temperature sensor modules on Y end (on 1Y4, IP: 192.168.113.241) and in the vertex on (1X2, IP: 192.168.113.242). I've updated the martian host table accordingly. From inside martian network, one can go to the browser and go to the IP address to see the temperature sensor status . These sensors can be set to trigger alarm and send emails/sms etc if temperature goes out of a defined range.
I feel something is off though. The vertex sensor shows temperature of ~28 degrees C, Xend says 20 degrees C and Yend says 26 degrees C. I believe these sensors might need calibration.
Remaining tasks are following:
- Modbus TCP solution:
- If we get it right, this will be easiest solution.
- We just need to add these sensors as streaming devices in some slow EPICS machine in there .cmd file and add the temperature sensing channels in a corresponding database file.
- Python workaround:
- Might be faster but dirty.
- We run a python script on megatron which requests temperature values every second or so from the IP addresses and write them on a soft EPICs channel.
- We still would need to create a soft EPICs channel fro this and add it to framebuilder data acquisition list.
- Even shorted workaround for near future could be to just write temperature every 30 min to a log file in some location.
[anchal, paco]
We made a script under scripts/PEM/temp_logger.py and ran it on megatron. The script uses the requests package to query the latest sensor data from the three sensors every 10 minutes as a json file and outputs accordingly. This is not a permanent solution.
|
|
Attachment 1: Screen_Shot_2021-09-13_at_4.16.22_AM.png
|
|
16318
|
Thu Sep 9 09:54:41 2021 |
Stephen | Summary | BHD | BHD OMC invacuum wiring - cable lengths | [Koji, Stephen - updated 30 September]
Cable lengths task - in vacuum cabling for the green section (new, custom for 40m) and yellow section (per aLIGO, except likely with cheaper FEP ribbon cable material) from 40m/16198. These arethe myriad of cables extending from the in vacuum flange to the aLIGO-style on-table Cable Stand (think, for example, D1001347), then from the cable stand to the OMCs.
a) select a position for the cable stand.
- Koji and I discussed and elected to place in the (-X, -Y) corner of the table (Northwest in the typical diagram) and near the table edge. This is adjacent to the intended exit flange for the last cable.
b) measure distances and cable routing approximations for cable bracket junctions
- Near OMC bracket to the cable stand, point to point = 17.2, routing estimate = 24.4.
- Far OMC bracket to the cable stand, point to point = 20.5, routing estimate = 32.2.
- Recommendation = 48" for all green section cables (using one length for each OMC, with extra slack to account for routing variation).
c) (outdated - see item (b) and attachment 3) measure distances (point to point) and cable routing approximations for all items.
+X OMC (long edge aligned with +Y beam axis) (overview image in Attachment 1)
- QPDs to the cable stand, point to point = 12, routing estimate = 20.
- DCPDs to the cable stand, point to point = 25, routing estimate = 32.
- PZTs to the cable stand, point to point = 21, routing estimate = 32.
+Y OMC (long edge aligned with +Y beam axis) (overview image in Attachment 1)
- QPDs to the cable stand, point to point = 16, routing estimate = 23.
- DCPDs to the cable stand, point to point = 26, routing estimate = 38.
- PZTs to the cable stand, point to point = 24, routing estimate = 33.
Cable stand to flange (Attachment 2) (specific image in Attachment 2)
- point to point = 35, routing estimate = 42
- Recommendation = 120" for all yellow section cables, per Koji's preferences for zigzag cable routing on stack and coiling of slack. |
Attachment 1: bhd_cable_length_check_cable_bracket_to_components.png
|
|
Attachment 2: bhd_cable_length_check_flange_to_cable_bracket.png
|
|
Attachment 3: bhd_cable_length_check_cable_bracket_to_omc_bracket.png
|
|
16317
|
Wed Sep 8 19:06:14 2021 |
Koji | Update | General | Backup situation | Tega mentioned in the meeting that it could be safer to separate some of nodus's functions from the martian file system.
That's an interesting thought. The summary pages and other web services are linked to the user dir. This has high traffic and can cause the issure of the internal network once we crash the disk.
Or if the internal system is crashed, we still want to use elogs as the source of the recovery info. Also currently we have no backup of the elog. This is dangerous.
We can save some of the risks by adding two identical 2TB disks to nodus to accomodate svn/elog/web and their daily backup.
host |
file system or contents |
condition |
note |
nodus |
root |
none or unknown |
|
nodus |
home (svn, elog) |
none |
|
nodus |
web (incl summary pages) |
backed up |
linked to /cvs/cds |
chiara |
root |
maybe |
need to check with Jon/Anchal |
chiara |
/home/cds |
local copy |
The backup disk is smaller than the main disk. |
chiara |
/home/cds |
remote copy - stalled |
we used to have, but stalled since 2017/11/17 |
fb1 |
root |
maybe |
need to check with Jon/Anchal |
fb1 |
frame |
rsync |
pulled from LDAS according to Tega |
|
|
|
|
|
16316
|
Wed Sep 8 18:00:01 2021 |
Koji | Update | VAC | cronjobs & N2 pressure alert | In the weekly meeting, Jordan pointed out that we didn't receive the alert for the low N2 pressure.
To check the situation, I went around the machines and summarized the cronjob situation.
[40m wiki: cronjob summary]
Note that this list does not include the vacuum watchdog and mailer as it is not on cronjob.
Now, I found that there are two N2 scripts running:
1. /opt/rtcds/caltech/c1/scripts/Admin/n2Check.sh on megatron and is running every minute (!)
2. /opt/rtcds/caltech/c1/scripts/Admin/N2check/pyN2check.sh on c1vac and is running every 3 hours.
Then, the N2 log file was checked: /opt/rtcds/caltech/c1/scripts/Admin/n2Check.log
Wed Sep 1 12:38:01 PDT 2021 : N2 Pressure: 76.3621
Wed Sep 1 12:38:01 PDT 2021 : T1 Pressure: 112.4
Wed Sep 1 12:38:01 PDT 2021 : T2 Pressure: 349.2
Wed Sep 1 12:39:02 PDT 2021 : N2 Pressure: 76.0241
Wed Sep 1 12:39:02 PDT 2021 : N2 pressure has fallen to 76.0241 PSI !
Tank pressures are 94.6 and 98.6 PSI!
This email was sent from Nodus. The script is at /opt/rtcds/caltech/c1/scripts/Admin/n2Check.sh
Wed Sep 1 12:40:02 PDT 2021 : N2 Pressure: 75.5322
Wed Sep 1 12:40:02 PDT 2021 : N2 pressure has fallen to 75.5322 PSI !
Tank pressures are 93.6 and 97.6 PSI!
This email was sent from Nodus. The script is at /opt/rtcds/caltech/c1/scripts/Admin/n2Check.sh
...
The error started at 11:39 and lasted until 13:01 every minute. So this was coming from the script on megatron. We were supposed to have ~20 alerting emails (but did none).
So what's happened to the mails? I tested the script with my mail address and the test mail came to me. Then I sent the test mail to 40m mailing list. It did not reach.
-> Decided to put the mail address (specified in /etc/mailname , I believe) to the whitelist so that the mailing list can accept it.
I did run the test again and it was successful. So I suppose the system can now send us the alert again.
And alerting every minute is excessive. I changed the check frequency to every ten minutes.
What's happened to the python version running on c1vac?
1) The script is running, spitting out some error in the cron report (email on c1vac). But it seems working.
2) This script checks the pressures of the bottles rather than the N2 pressure downstream. So it's complementary.
3) During the incident on Sept 1, the checker did not trip as the pressure drop happened between the cronjob runs and the script didn't notice it.
4) On top of them, the alert was set to send the mails only to an our former grad student. I changed it to deliver to the 40m mailing list. As the "From" address is set to be some ligox...@gmail.com, which is a member of the mailing list (why?), we are supposed to receive the alert. (And we do for other vacuum alert from this address).
|
16315
|
Tue Sep 7 18:00:54 2021 |
Tega | Summary | Calibration | System Identification via line injection | [paco]
This morning, I spent some time restoring the jupyter notebook server running in allegra. This server was first set up by Anchal to be able to use the latest nds python API tools which is handy for the calibration stuff. The process to restore the environment was to run "source ~/bashrc.d/*" to restore some of the aliases, variables, paths, etc... that made the nds server work. I then ran ssh -N -f -L localhost:8888:localhost:8888 controls@allegra from pianosa and carry on with the experiment.
[paco, hang, tega]
We started a notebook under /users/paco/20210906_XARM_Cal/XARM_Cal.ipynb on which the first part was doing the following;
- Set up list of excitations for C1:LSC-XARM_EXC (for example three sine waveforms) using awg.py
- Make sure the arm is locked
- Read a reference time trace of the C1:LSC-XARM_IN2 channel for some duration
- Start excitations (one by one at the moment, ramptime ~ 3 seconds, same duration as above)
- Get data for C1:LSC-XARM_IN2 for an equal duration (raw data in Attachment #1)
- Generate the excitation sine and cosine waveforms using numpy and demodulate the raw timeseries using a 4th order lowpass filter with fc ~ 10 Hz
- Estimate the correct demod phase by computing arctan(Q / I) and rerunning the demodulation to dump the information into the I quadrature (Attachment #2).
- Plot the estimated ASD of all the quadratures (Attachment #3)
[paco, hang, tega]
Estimation of open loop gain:
- Grab data from the C1:LSC-XARM_IN1 and C1:LSC-XARM_IN2 test points
- Infer excitation from their differnce, i.e. C1:LSC-XARM_EXC = C1:LSC-XARM_IN2 - C1:LSC-XARM_IN1
- Compute the open loop gain as follows : G(f) = csd(EXC,IN1)/csd(EXC,IN2), where csd computes the cross spectra density of the input arguments
- For the uncertainty in G, dG, we repeat steps (1) to (3) with & without signal injection in the C1:LSC-XARM_EXC channel. In the absence of signal injection, the signal in C1:LSC-XARM_IN2 is of the form: Y_ref = Noise/(1-G), whereas with nonzero signal injection, the signal in C1:LSC-XARM_IN2 has the form: Y_cal = EXC/(1-G) + Noise/(1-G), so their ratio, Y_cal/Y_ref = EXC/Noise, gives the SNR, which we can then invert to give the uncertainty in our estimation of G, i.e dG = Y_ref/Y_cal.
- For the excitation at 53 Hz, our measurtement for the open loop gain comes out to about 5 dB whiich is consistent with previous measurement.
- We seem to have an SNR in excess of 100 at measurement time of 35 seconds and 1 count of amplitude which gives a relative uncertainty of G of 0.1%
- The analysis details are ongoing. Feedback is welcome.
|
Attachment 1: raw_timeseries.pdf
|
|
Attachment 2: demod_signals.pdf
|
|
Attachment 3: cal_noise_asd.pdf
|
|
16314
|
Fri Sep 3 02:03:15 2021 |
Tega | Summary | Computers | Strip down large error files | Also deleted the ~50GB error files from ldas to prevent rsync from copying them to nodus again. With the new update to GWsumm, there are new error messages that initially didn't seem to affect the summary pages functionality, but in the extreme case can populated the error files the repeated warnings on the form "Loading: FrSerData", "Loading: FrSerData::n4294967295", "Loading: FrSummary","Loading: FrSerDataLoading: FrSerData" and many more combinations until we get file sizes of the order of ~50GB. So I have updated the checkstatus script to parse the error files and strip out the majority of these error messages. Work is ongoing to get them all.
In light of these large files generation, I decided to look in the summary pages folder to see if there are other large files that we need to keep track of and it turns there are indeed a collection of files in the archive folder that bloats the summary pages on ldas to ~1TB. Luckily these are not synced to nodus so no problem here. However, since the beginning of the year, the archive folders that hold data used for each day's computation have not been cleared. We have a script for doing this but it has not been run for a while now and it only delete archive files for a specific month which is hardcoded to two months from the date the file is run. I have modified the code to allow archive deletion for a range of months so we can clear data from Jan to July.
Quote: |
[tega, paco]
We found the files that took excess space in the chiara filesystem (see Attachment 1). They were error files from the summary pages that were ~ 50 GB in size or so located under /home/cds/caltech/users/public_html/detcharsummary/logs/. We manually removed them and then copied the rest of the summary page contents into the main file system drive (this is to preserve the information backup before it gets deleted by the cron job at the end of today) and checked carefully to identify the actual issue for why these files were as large in the first place.
We then copied the /detcharsummary directory from /media/40mBackup into /home/cds to match the two disks.
|
|
16313
|
Thu Sep 2 21:49:03 2021 |
Paco | Summary | Computers | chiara down, vac interlock tripped | [tega, paco]
We found the files that took excess space in the chiara filesystem (see Attachment 1). They were error files from the summary pages that were ~ 50 GB in size or so located under /home/cds/caltech/users/public_html/detcharsummary/logs/. We manually removed them and then copied the rest of the summary page contents into the main file system drive (this is to preserve the information backup before it gets deleted by the cron job at the end of today) and checked carefully to identify the actual issue for why these files were as large in the first place.
We then copied the /detcharsummary directory from /media/40mBackup into /home/cds to match the two disks. |
Attachment 1: 2021-09-02_21-51-15.png
|
|
16312
|
Thu Sep 2 21:21:14 2021 |
Koji | Summary | Computers | Vacuum recovery 2 | Attachment 1:
We are pumping the main volume with TP2. Once P1a reached the pressure ~2.2mtorr, we could open the PSL shutter. The TP2 voltage went up once but came down to ~20V. It's close to nominal now.
We wondered if we should use TP3 or not. I checked the vacuum pressure trends and found that the annulus pressures were going up. So we decided to open the annulus valves.
Attachment 2:
The current vacuum status is as shown in the MEDM screenshot.
There is no trend data of the valve status (sad) |
Attachment 1: Screenshot_2021-09-02_21-20-24.png
|
|
Attachment 2: Screenshot_2021-09-02_21-20-48.png
|
|
16311
|
Thu Sep 2 20:47:19 2021 |
Koji | Update | CDS | Chiara DHCP restarted | [Paco, Tega, Koji]
Once chiara's DHCP is back, things got much more straight forward.
c1iscex and c1iscey were rebooted and the IOPs were launched without any hesitation.
Paco ran rebootC1LSC.sh and for the first time in this year we had the launch of the processes without any issue. |
16310
|
Thu Sep 2 20:44:18 2021 |
Koji | Update | CDS | Chiara DHCP restarted | We had the issue of the RT machines rebooting. Once we hooked up the display on c1iscex, it turned out that the IP was not given at it's booting-up.
I went to chiara and confirmed that the DHCP service was not running
~>sudo service isc-dhcp-server status
[sudo] password for controls:
isc-dhcp-server stop/waiting
So the DHCP service was manually restarted
~>sudo service isc-dhcp-server start
isc-dhcp-server start/running, process 24502
~>sudo service isc-dhcp-server status
isc-dhcp-server start/running, process 24502
|
16309
|
Thu Sep 2 19:47:38 2021 |
Koji | Update | CDS | This week's FB1 GPS Timing Issue Solved | After the reboot daqd_dc was not working, but manual starting of open-mx / mx services solved the issue.
sudo systemctl start open-mx.service
sudo systemctl start mx.service
sudo systemctl start daqd_*
|
16308
|
Thu Sep 2 19:28:02 2021 |
Koji | Update | | This week's FB1 GPS Timing Issue Solved | After the disk system trouble, we could not make the RTS running at the nominal state. A part of the troubleshoot FB1 was rebooted. But the we found that the GPS time was a year off from the current time
controls@fb1:/diskless/root/etc 0$ cat /proc/gps
1283046156.91
controls@fb1:/diskless/root/etc 0$ date
Thu Sep 2 18:43:02 PDT 2021
controls@fb1:/diskless/root/etc 0$ timedatectl
Local time: Thu 2021-09-02 18:43:08 PDT
Universal time: Fri 2021-09-03 01:43:08 UTC
RTC time: Fri 2021-09-03 01:43:08
Time zone: America/Los_Angeles (PDT, -0700)
NTP enabled: no
NTP synchronized: yes
RTC in local TZ: no
DST active: yes
Last DST change: DST began at
Sun 2021-03-14 01:59:59 PST
Sun 2021-03-14 03:00:00 PDT
Next DST change: DST ends (the clock jumps one hour backwards) at
Sun 2021-11-07 01:59:59 PDT
Sun 2021-11-07 01:00:00 PST
Paco went through the process described in Jamie's elog [40m ELOG 16299] (except for the installation part) and it actually made the GPS time even strange
controls@fb1:~ 0$ cat /proc/gps
967861610.89
I decided to remove the gpstime module and then load it again. This made the gps time back to normal again.
controls@fb1:~ 0$ sudo modprobe -r gpstime
controls@fb1:~ 0$ cat /proc/gps
cat: /proc/gps: No such file or directory
controls@fb1:~ 1$ sudo modprobe gpstime
controls@fb1:~ 0$ cat /proc/gps
1314671254.11
|
16307
|
Thu Sep 2 17:53:15 2021 |
Paco | Summary | Computers | chiara down, vac interlock tripped | [paco, koji, tega, ian]
Today in the morning the name server / network file system running in chiara failed. This resulted in donatella/pianosa/rossa shell prompts to hang forever. It also made sitemap crash and even dropping into a bash shell and just listing files from some directory in the file system froze the computer. Remote ssh sessions on nodus also had the same symptoms.
A little after 1 pm, we started debugging this issue with help from Koji. He suggested we hook a monitor, keyboard, and mouse onto chiara as it should still work locally even if something with the NFS (network file system) failed. We did this and then we tried for a while to unmount the /dev/sdc1/ from /home/cds/ (main file system) and mount /dev/sdb1/ from /media/40mBackup (backup copy) such that they swap places. We had no trouble unmounting the backup drive, but only succeeded in unmounting the main drive with the "lazy" unmount, or running "umount -l". Running "df" we could see that the disk space was 100% used, with only ~ 1 GB of free space which may have been the cause for the issue. After swapping these disks by editing the /etc/fstab file to implement the aforementioned swapping, we rebooted chiara and we recovered the shell prompts in all workstations, sitemap, etc... due to the backup drive mounting. We then started investigating what caused the main drive to fill up that quickly, and noted that weirdly now the capacity was at 85% or about 500GB less than before (after reboot and remount), so some large file was probably dumped into chiara that froze the NFS causing the issue.
At this point we tried opening the PSL shutter to recover the IMC. The shutter would not open and we suspected the vacuum interlock was still tripped... and indeed there was an uncleared error in the VAC screen. So with Koji's guidance we walked to the c1vac near the HV station and did the following at ~ 5:13 PM -->
- Open V4; apart from a brief pressure spike in PTP2, everything looked ok so we proceeded to
- Open V1; P2 spiked briefly and then started to drop. Then, Koji suggested that we could
- Close V4; but we saw P2 increasing by a factor of~ 10 in a few seconds, so we
- Reopened V4;
We made sure that P1a (main vacuum pressure) was dropping and before continuing we decided to look back to see what the nominal vacuum state was that we should try to restore.
We are currently searching the two systems for diffrences to see if we can narrow down the culprit of the failure.
|
16306
|
Wed Sep 1 21:55:14 2021 |
Koji | Summary | General | Towards the end upgrade | - Sat amp mod and test: on going (Tega)
- Coil driver mod and test: on going (Tega)
- Acromag: almost ready (Yehonathan)
- IDC10-DB9 cable / D2100641 / IDC10F for ribbon in hand / Dsub9M ribbon brought from Downs / QTY 2 for two ends -> Made 2 (stored in the DSUB connector plastic box)
- IDC40-DB9 cable / D2100640 / IDC40F for ribbon in hand / DB9F solder brought from Downs / QTY 4 for two ends -> Made 4 0.5m cables (stored in the DSUB connector plastic box)
- DB15-DB9 reducer cable / ETMX2+ETMY2+VERTEX16+NewSOS14 = 34 / to be ordered
- End DAC signal adapter with Dewhitening (with DIFF/SE converter) / to be designed & built
- End ADC adapter (with SE/DIFF converter) / to be designed & built
MISC Ordering
- 3.5 x Sat Amp Adapter made (order more DSUB25 conns)
- -> Gave 2 to Tega, 1.5 in the DSUB box
- 5747842-4 A32100-ND -> 5747842-3 A32099-ND Qty40
- 5747846-3 A32125-ND -> 747846-3 A23311-ND Qty40
- Tega's sat amp components
- 499Ω P499BCCT-ND 78 -> Backorder -> RG32P499BCT-ND Qty 100
- 4.99KΩ TNPW12064K99BEEA 56 -> Qty 100
- 75Ω YAG5096CT-ND 180 -> Qty 200
- 1.82KΩ P18391CT-ND 103 -> Qty 120
- 68 nF P10965-ND 209
- Order more DB9s for Tega's sat amp adapter 4 units (look at the AA IO BOM)
- 4x 8x 5747840-4 DB9M PCB A32092-ND -> 6-747840-9 A123182-ND Qty 35
- 4x 5x 5747844-4 A32117-ND -> Qty 25
- 4x 5x DB9M ribbon MMR09K-ND -> 8209-8000 8209-8000-ND Qty 25
- 4x 5x 5746861-4 DB9F ribbon 5746861-4-ND -> 400F0-09-1-00 LFR09H-ND Qty 35
- Order 18bit DAC AI -> 16bit DAC AI components 4 units
- 4x 4x 5747150-8 DSUB9F PCB A34072-ND -> D09S24A4PX00LF609-6357-ND Qty 20
- 4x 1x 787082-7 CONN D-TYPE RCPT 68POS R/A SLDR (SCSI Female) A3321-ND -> 5787082-7 A31814-ND Qty 5
- 4x 1x 22-23-2021 Connector Header Through Hole 2 position 0.100" (2.54mm) WM4200-ND -> Qty5
|
16305
|
Wed Sep 1 14:16:21 2021 |
Jordan | Update | VAC | Empty N2 Tanks | The right N2 tank had a bad/loose valve and did not fully open. This morning the left tank was just about empty and the right tank showed 2000+ psi on the gauge. Once the changeover happened the copper line emptied but the valve to the N2 tank was not fully opened. I noticed the gauges were both reading zero at ~1pm just before the meeting. I swapped the left tank, but not in time. The vacuum interlocks tripped at 1:04 pm today when the N2 pressure to the vacuum valves fell below 65psi. After the meeting, Chub tightened the valve, fully opened it and refilled the lines. I will monitor the tank pressures today and make sure all is ok.
There used to be a mailer that was sent out when the sum pressure of the two tanks fell <600 psi, telling you to swap tanks. Does this no longer exist? |
16304
|
Tue Aug 31 14:55:24 2021 |
rana | Summary | LSC | XARM POX OLTF | this model doesn't seem to include the analog AA, analog AI, digital AA, digital AI, or data transfer delays in the system. I think if you include those you will get more accuracy at high frequencies. Probably Anchal has those included in his DARM loop model?
|
16303
|
Mon Aug 30 17:49:43 2021 |
Paco | Summary | LSC | XARM POX OLTF | Used diaggui to get OLTF in preparation for optimal system identification / calibration. The excitation was injected at the control point of the XARM loop C1:LSC-XARM_EXC. Attachment 1 shows the TF (red scatter) taken from 35 Hz to 2.3 kHz with 201 points. The swept sine excitation had an envelope amplitude of 50 counts at 35 Hz, 0.2 counts at 100 Hz, and 0.2 at 200 Hz. In purple continous line, the model for the OLTF using all the digital control filters as well as a simple 1 degree of freedom plant (single pole at 0.99 Hz) is overlaid. Note the disagreement of the OLTF "model" at higher frequencies which we may be able to improve upon using vector fitting.
Attachment 2 shows the coherence (part of this initial measurement was to identify an appropriately large frequency range where the coherence is good before we script it). |
Attachment 1: XARM_POX_OLTF.pdf
|
|
Attachment 2: XARM_POX_Coh.pdf
|
|
16302
|
Thu Aug 26 10:30:14 2021 |
Jamie | Configuration | CDS | front end time synchronization fixed? | I've been looking at why the front end NTP time synchronization did not seem to be working. I think it might not have been working because the NTP server the front ends were point to, fb1, was not actually responding to synchronization requests.
I cleaned up some things on fb1 and the front ends, which I think unstuck things.
On fb1:
- stopped/disabled the default client (systemd-timesyncd), and properly installed the full NTP server (ntp)
- the ntp server package for debian jessie is old-style sysVinit, not systemd. In order to make it more integrated I copied the auto-generated service file to /etc/systemd/system/ntp.service, and added and "[install]" section that specifies that it should be available during the default "multi-user.target".
- "enabled" the new service to auto-start at boot ("sudo systemctl enable ntp.service")
- made sure ntp was configured to serve the front end network ('broadcast 192.168.123.255') and then restarted the server ("sudo systemctl restart ntp.service")
For the front ends:
- on fb1 I chroot'd into the front-end diskless root (/diskless/root) and manually specifed that systemd-timesyncd should start on boot by creating a symlink to the timesyncd service in the multi-user.target directory:
$ sudo chroot /diskless/root
$ cd /etc/systemd/system/multi-user.target.wants
$ ln -s /lib/systemd/system/systemd-timesyncd.service
- on the front end itself (c1iscex as a test) I did a "systemctl daemon-reload" to force it to reload the systemd config, and then restarted the client ("systemctl restart systemd-timesyncd")
- checked the NTP synchronization with timedatectl:
controls@c1iscex:~ 0$ timedatectl
Local time: Thu 2021-08-26 11:35:10 PDT
Universal time: Thu 2021-08-26 18:35:10 UTC
RTC time: Thu 2021-08-26 18:35:10
Time zone: America/Los_Angeles (PDT, -0700)
NTP enabled: yes
NTP synchronized: yes
RTC in local TZ: no
DST active: yes
Last DST change: DST began at
Sun 2021-03-14 01:59:59 PST
Sun 2021-03-14 03:00:00 PDT
Next DST change: DST ends (the clock jumps one hour backwards) at
Sun 2021-11-07 01:59:59 PDT
Sun 2021-11-07 01:00:00 PST
controls@c1iscex:~ 0$
Note that it is now reporting "NTP enabled: yes" (the service is enabled to start at boot) and "NTP synchronized: yes" (synchronization is happening), neither of which it was reporting previously. I also note that the systemd-timesyncd client service is now loaded and enabled, is no longer reporting that it is in an "Idle" state and is in fact reporting that it synchronized to the proper server, and it is logging updates:
controls@c1iscex:~ 0$ sudo systemctl status systemd-timesyncd
â— systemd-timesyncd.service - Network Time Synchronization
Loaded: loaded (/lib/systemd/system/systemd-timesyncd.service; enabled)
Active: active (running) since Thu 2021-08-26 10:20:11 PDT; 1h 22min ago
Docs: man:systemd-timesyncd.service(8)
Main PID: 2918 (systemd-timesyn)
Status: "Using Time Server 192.168.113.201:123 (ntpserver)."
CGroup: /system.slice/systemd-timesyncd.service
└─2918 /lib/systemd/systemd-timesyncd
Aug 26 10:20:11 c1iscex systemd[1]: Started Network Time Synchronization.
Aug 26 10:20:11 c1iscex systemd-timesyncd[2918]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 26 10:20:11 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 64s/+0.000s/0.000s/0.000s/+26ppm
Aug 26 10:21:15 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 128s/-0.000s/0.000s/0.000s/+25ppm
Aug 26 10:23:23 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 256s/+0.001s/0.000s/0.000s/+26ppm
Aug 26 10:27:40 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 512s/+0.003s/0.000s/0.001s/+29ppm
Aug 26 10:36:12 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 1024s/+0.008s/0.000s/0.003s/+33ppm
Aug 26 10:53:16 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 2048s/-0.026s/0.000s/0.010s/+27ppm
Aug 26 11:27:24 c1iscex systemd-timesyncd[2918]: interval/delta/delay/jitter/drift 2048s/+0.009s/0.000s/0.011s/+29ppm
controls@c1iscex:~ 0$
So I think this means everything is working.
I then went ahead and reloaded and restarted the timesyncd services on the rest of the front ends.
We still need to confirm that everything comes up properly the next time we have an opportunity to reboot fb1 and the front ends (or the opportunity is forced upon us).
There was speculation that the NTP clients on the front ends (systemd-timesyncd) would not work on a read-only filesystem, but this doesn't seem to be true. You can't trust everything you read on the internet. |
16300
|
Thu Aug 26 10:10:44 2021 |
Paco | Update | CDS | FB is writing the frames with a year old date | [paco, ]
We went over the X end to check what was going on with the TRX signal. We spotted the ground terminal coming from the QPD is loosely touching the handle of one of the computers on the rack. When we detached it completely from the rack the noise was gone (attachment 1).
We taped this terminal so it doesn't touch anything accidently. We don't know if this is the best solution since it is probably needs a stable voltage reference. In the Y end those ground terminals are connected to the same point on the rack. The other ground terminals in the X end are just cut.
We also took the PSD of these channels (attachment 2). The noise seem to be gone but TRX is still a bit noisier than TRY. Maybe we should setup a proper ground for the X arm QPD?
We saw that the X end station ALS laser was off. We turned it on and also the crystal oven and reenabled the temperature controller. Green light immidiately appeared. We are now working to restore the ALS lock. After running XARM ASS we were unable to lock the green laser so we went to the XEND and moved the piezo X ALS alignment mirrors until we maximized the transmission in the right mode. We then locked the ALS beams on both arms successfully. It very well could be that the PZT offsets were reset by the power glitch. The XARM ALS still needs some tweaking, its level is ~ 25% of what it was before the power glitch. |
Attachment 1: Screenshot_from_2021-08-26_10-09-50.png
|
|
Attachment 2: TRXTRY_Spectra.pdf
|
|
16299
|
Wed Aug 25 18:20:21 2021 |
Jamie | Update | CDS | GPS time on fb1 fixed, dadq writing correct frames again | I have no idea what happened to the GPS timing on fb1, but it seems like the issue was coincident with the power glitch on Monday.
As was noted by Koji above, the GPS time kernel interface was off by a year, which was causing the frame builder to write out files with the wrong names. fb1 was using DAQD components from the advligorts 3.3 release, which used the old "symmetricom" kernel module for the GPS time. This old module was also known to have issues with time offsets. This issue is remniscent of previous timing issues with the DAQ on fb1.
I noted that a newer version of the advligorts, version 3.4, was available on debian jessie, the system running on fb1. advligorts 3.4 includes a newer version of the GPS time module, renamed gpstime. I checked with Jonathan Hanks that the interfaces did not change between 3.3 and 3.4, and 3.4 was mostly a bug fix and packaging release, so I decided to upgrade the DAQ to get the new components. I therefore did the following
-
updated the archive info in /etc/apt/sources.list.d/cdssoft.list, and added the "jessie-restricted" archive which includes the mx packages: https://git.ligo.org/cds-packaging/docs/-/wikis/home
-
removed the symmetricom module from the kernel
sudo rmmod symmetricom
-
upgraded the advligorts-daqd components (NOTE I did not upgrade the rest of the system, although there are outstanding security upgrades needed):
sudo apt install advligorts-daqd advligorts-daqd-dc-mx
-
loaded the new gpstime module and checked that the GPS time was correct:
sudo modprobe gpstime
-
restarted all the daqd processes
sudo systemctl restart daqd_*
Everything came up fine at that point, and I checked that the correct frames were being written out. |
16298
|
Wed Aug 25 17:31:30 2021 |
Paco | Update | CDS | FB is writing the frames with a year old date | [paco, tega, koji]
After invaluable assistance from Jamie in fixing this yearly offset in the gps time reported by cat /proc/gps, we managed to restart the real time system correctly (while still manually synchronizing the front end machine times). After this, we recovered the mode cleaner and were able to lock the arms with not much fuss.
Nevertheless, tega and I noticed some weird noise in the C1:LSC-TRX_OUT which was not present in the YARM transmission, and that is present even in the absence of light (we unlocked the arms and just saw it on the ndscope as shown in Attachment #1). It seems to affect the XARM and in general the lock acquisition...
We took some quick spectrum with diaggui (Attachment #2) but it doesn't look normal; there seems to be broadband excess noise with a remarkable 1 kHz component. We will probably look into it in more detail. |
Attachment 1: TRX_noise_2021-08-25_17-40-55.png
|
|
Attachment 2: TRX_TRY_power_spectra.pdf
|
|
16297
|
Wed Aug 25 11:48:48 2021 |
Yehonathan | Update | CDS | c1auxey assembly | After confirming that, indeed, leaving the RTN connection floating can cause reliability issues we decided to make these connections in the c1auxex analog input units.
According to Johannes' wiring scheme (excluding the anti-image and OPLEV since they are decommissioned), Acromag unit 1221b accepts analog inputs from two modules. All of these channels are single-ended according to their schematics.
One option is to use the Acromag ground and connect it to the RTNs of both 1221b and 1221c. Another is to connect the minus wire of one module, which is tied to the module's ground, to the RTN. We shouldn't tie the grounds of the different modules together by connecting them to the same RTN point.
We should take some OSEM spectra of the X end arm before and after this work to confirm we didn't produce more noise by doing so. Right now, it is impossible due to issues caused by the recent power surge.
Quote: |
{Yehonathan, Jon}
We poked (looked in situ with a flashlight, not disturbing any connections) around c1auxex chassis to understand better what is the wiring scheme.
To our surprise, we found that nothing was connected to the RTNs of the analog input Acromag modules. From previous experience and the Acromag manual, there can't be any meaningful voltage measurement without it.
|
|
16296
|
Wed Aug 25 08:53:33 2021 |
Jordan | Update | SUS | 2" Adapter Ring for SOS Arrived 8/24/21 | 8 of the 2"->3" adapter rings (D2100377) arrived from RDL yesterday. I have not tested the threads but dimensional inspection on SN008 cleared. Parts look very good. The rest of the parts should be shipping out in the next week. |
Attachment 1: 20210824_152259.jpg
|
|
Attachment 2: 20210824_152259.jpg
|
|
Attachment 3: 20210824_152308.jpg
|
|
16295
|
Tue Aug 24 22:37:40 2021 |
Anchal | Update | General | Time synchronization not really working | I attempted to install chrony and run it on one of the FE machines. It didn't work and in doing so, I lost the working NTP client service on the FE computers as well. Following are some details:
- I added the following two mirrors in the apt source list of root.jessie at /etc/apt/sources.list
deb http://ftp.us.debian.org/debian/ jessie main contrib non-free
deb-src http://ftp.us.debian.org/debian/ jessie main contrib non-free
- Then I installed chrony in the root.jessie using
sudo apt-get install chrony
- I was getting an error E: Can not write log (Is /dev/pts mounted?) - posix_openpt (2: No such file or directory) . To fix this, I had to run:
sudo mount -t devpts none "$rootpath/dev/pts" -o ptmxmode=0666,newinstance
sudo ln -fs "pts/ptmx" "$rootpath/dev/ptmx"
- Then, I had another error to resolve.
Failed to read /proc/cmdline. Ignoring: No such file or directory
start-stop-daemon: nothing in /proc - not mounted?
To fix this, I had to exit to fb1 and run:
sudo mount --bind /proc /diskless/root.jessie/proc
- With these steps, chrony was finally installed, but I immediately saw an error message saying:
Starting /usr/sbin/chronyd...
Could not open NTP sockets
- I figured this must be due to ntp running in the FE machines. I logged into c1iscex and stopped and disabled the ntp service:
sudo systemctl stop ntp
sudo systemctl disable ntp
- I saw some error messages from the above coomand as FEs are read only file systems:
Synchronizing state for ntp.service with sysvinit using update-rc.d...
Executing /usr/sbin/update-rc.d ntp defaults
insserv: fopen(.depend.stop): Read-only file system
Executing /usr/sbin/update-rc.d ntp disable
update-rc.d: error: Read-only file system
- So I went back to chroot in fb1 and ran the two command sabove that failed:
/usr/sbin/update-rc.d ntp defaults
/usr/sbin/update-rc.d ntp disable
- The last line gave the output:
insserv: warning: current start runlevel(s) (empty) of script `ntp' overrides LSB defaults (2 3 4 5).
insserv: warning: current stop runlevel(s) (2 3 4 5) of script `ntp' overrides LSB defaults (empty).
- I igored this and moved forward.
- I copied the chronyd.service from nodus to the chroot in fb1 and configured it to use nodus as the server. The I started the chronyd.service
sudo systemctl status chronyd.service
but got the saem issue of NTP sockets.
â—Â chronyd.service - NTP client/server
Loaded: loaded (/usr/lib/systemd/system/chronyd.service; disabled)
Active: failed (Result: exit-code) since Tue 2021-08-24 21:52:30 PDT; 5s ago
Process: 790 ExecStart=/usr/sbin/chronyd $OPTIONS (code=exited, status=1/FAILURE)
Aug 24 21:52:29 c1iscex systemd[1]: Starting NTP client/server...
Aug 24 21:52:30 c1iscex chronyd[790]: Could not open NTP sockets
Aug 24 21:52:30 c1iscex systemd[1]: chronyd.service: control process exited, code=exited status=1
Aug 24 21:52:30 c1iscex systemd[1]: Failed to start NTP client/server.
Aug 24 21:52:30 c1iscex systemd[1]: Unit chronyd.service entered failed state.
-
I tried a few things to resolve this, but couldn't get it to work. So I gave up on using chrony and decided to go back to ntp service atleast.
-
I stopped, disabled and checked status of chrony:
sudo systemctl stop chronyd
sudo systemctl disable chronyd
sudo systemctl status chronyd
This gave the output:
â—Â chronyd.service - NTP client/server
Loaded: loaded (/usr/lib/systemd/system/chronyd.service; disabled)
Active: failed (Result: exit-code) since Tue 2021-08-24 22:09:07 PDT; 25s ago
Aug 24 22:09:07 c1iscex systemd[1]: Starting NTP client/server...
Aug 24 22:09:07 c1iscex chronyd[2490]: Could not open NTP sockets
Aug 24 22:09:07 c1iscex systemd[1]: chronyd.service: control process exited, code=exited status=1
Aug 24 22:09:07 c1iscex systemd[1]: Failed to start NTP client/server.
Aug 24 22:09:07 c1iscex systemd[1]: Unit chronyd.service entered failed state.
Aug 24 22:09:15 c1iscex systemd[1]: Stopped NTP client/server.
-
I went back to fb1 chroot and removed chrony package and deleted the configuration files and systemd service files:
sudo apt-get remove chrony
-
But when I started ntp daemon service back in c1iscex, it gave error:
sudo systemctl restart ntp
Job for ntp.service failed. See 'systemctl status ntp.service' and 'journalctl -xn' for details.
-
Status shows:
sudo systemctl status ntp
â—Â ntp.service - LSB: Start NTP daemon
Loaded: loaded (/etc/init.d/ntp)
Active: failed (Result: exit-code) since Tue 2021-08-24 22:09:56 PDT; 9s ago
Process: 2597 ExecStart=/etc/init.d/ntp start (code=exited, status=5)
Aug 24 22:09:55 c1iscex systemd[1]: Starting LSB: Start NTP daemon...
Aug 24 22:09:56 c1iscex systemd[1]: ntp.service: control process exited, code=exited status=5
Aug 24 22:09:56 c1iscex systemd[1]: Failed to start LSB: Start NTP daemon.
Aug 24 22:09:56 c1iscex systemd[1]: Unit ntp.service entered failed state.
-
I tried to enable back the ntp service by sudo systemctl enable ntp. I got similar error messages of read only filesystem as earlier.
Synchronizing state for ntp.service with sysvinit using update-rc.d...
Executing /usr/sbin/update-rc.d ntp defaults
insserv: warning: current start runlevel(s) (empty) of script `ntp' overrides LSB defaults (2 3 4 5).
insserv: warning: current stop runlevel(s) (2 3 4 5) of script `ntp' overrides LSB defaults (empty).
insserv: fopen(.depend.stop): Read-only file system
Executing /usr/sbin/update-rc.d ntp enable
update-rc.d: error: Read-only file system
-
I came back to c1iscex and tried restarting the ntp service but got same error messages as above with exit code 5.
-
I checked c1sus, the ntp was running there. I tested the configuration by restarting the ntp service, and then it failed with same error message. So the remaining three FEs, c1lsc, c1ioo and c1iscey have running ntp service, but they won't be able to restart.
-
As a last try, I rebooted c1iscex to see if ntp comes back online nicely, but it doesn't.
Bottom line, I went to try chrony in the FEs, and I ended up breaking the ntp client services on the computers as well. We have no NTP synchronization in any of the FEs.
Even though Paco and I are learning about the ntp and cds stuff, I think it's time we get help from someone with real experience. The lab is not in a good state for far too long.
Quote: |
tl;dr: NTP servers and clients were never synchronized, are not synchronizing even with ntp... nodus is synchronized but uses chronyd; should we use chronyd everywhere?
|
|
16294
|
Tue Aug 24 18:44:03 2021 |
Koji | Update | CDS | FB is writing the frames with a year old date | Dan Kozak pointed out that the new frame files of the 40m has not been written in 2021 GPS time but 2020 GPS time.
Current GPS time is 1313890914 (or something like that), but the new files are written as C-R-1282268576-16.gwf
I don't know how this can happen but this may explain why we can't have the agreement between the FB gps time and the RTS gps time.
(dataviewer seems dependent on the FB GPS time and it indicates 2020 date. DTT/diaggui does not.)
This is the way to check the gpstime on fb1. It's apparently a year off.
controls@fb1:~ 0$ cat /proc/gps
1282269402.89 |
Attachment 1: Screen_Shot_2021-08-24_at_18.46.24.png
|
|
16293
|
Tue Aug 24 18:11:27 2021 |
Paco | Update | General | Time synchronization not really working | tl;dr: NTP servers and clients were never synchronized, are not synchronizing even with ntp... nodus is synchronized but uses chronyd; should we use chronyd everywhere?
Spent some time investigating the ntp synchronization. In the morning, after Anchal set up all the ntp servers / FE clients I tried restarting the rts IOPs with no success. Later, with Tega we tried the usual manual matching of the date between c1iscex and fb1 machines but we iterated over different n-second offsets from -10 to +10, also without success.
This afternoon, I tried debugging the FE and fb1 timing differences. For this I inspected the ntp configuration file under /etc/ntp.conf in both the fb1 and /diskless/root.jessie/etc/ntp.conf (for the FE machines) and tried different combinations with and without nodus, with and without restrict lines, all while looking at the output of sudo journalctl -f on c1iscey. Everytime I changed the ntp config file, I restarted the service using sudo systemctl restart ntp.service . Looking through some online forums, people suggested basic pinging to see if the ntp servers were up (and broadcasting their times over the local network) but this failed to run (read-only filesystem) so I went into fb1, and ran sudo chroot /diskless/root.jessie/ /bin/bash to allow me to change file permissions. The test was first done with /bin/ping which couldn't even open a socket (root access needed) by running chmod 4755 /bin/ping then ssh-ing into c1iscey and pinging the fb1 machine successfully. After this, I ran chmod 4755 /usr/sbin/ntpd so that the ntp daemon would have no problem in reaching the server in case this was blocking the synchronization. I exited the chroot shell and the ntp daemon in c1iscey; but the ntpstat still showed unsynchronised status. I also learned that when running an ntp query with ntpq -p if a client has succeeded in synchronizing its time to the server time, an asterisk should be appended at the end. This was not the case in any FE machine... and looking at fb1, this was also not true. Although the fb1 peers are correctly listed as nodus, the caltech ntp server, and a broadcast (.BCST.) server from local time (meant to serve the FE machines), none appears to have synchronized... Going one level further, in nodus I checked the time synchronization servers by running chronyc sources the output shows
controls@nodus|~> chronyc sources
210 Number of sources = 4
MS Name/IP address Stratum Poll Reach LastRx Last sample
===============================================================================
^* testntp1.superonline.net 1 10 377 280 +1511us[+1403us] +/- 92ms
^+ 38.229.59.9 2 10 377 206 +8219us[+8219us] +/- 117ms
^+ tms04.deltatelesystems.ru 2 10 377 23m -17ms[ -17ms] +/- 183ms
^+ ntp.gnc.am 3 10 377 914 -8294us[-8401us] +/- 168ms
I then ran chronyc clients to find if fb1 was listed (as I would have expected) but the output shows this --
Hostname Client Peer CmdAuth CmdNorm CmdBad LstN LstC
========================= ====== ====== ====== ====== ====== ==== ====
501 Not authorised
So clearly chronyd succeeded in synchronizing nodus' time to whatever server it was pointed at but downstream from there, neither the fb1 or any FE machines seem to be synchronizing properly. It may be as simple as figuring out the correct ntp configuration file, or switching to chronyd for all machines (for the sake of homogeneity?) |
16292
|
Tue Aug 24 09:22:48 2021 |
Anchal | Update | General | Time synchronization working now | Jamie told me to use chroot to log in into the chroot jail of debian os that are exported for the FEs and install ntp there. I took following steps at the end of which, all FEs have NTP synchronized now.
- I logged into fb1 through nodus.
- chroot /diskless/root.jessie /bin/bash took me to the bash terminal for debian os that is exported to all FEs.
- Here, I ran sudo apt-get install ntp which ran without any errors.
- I then edited the file in /etc/ntp.conf , i removed the default servers and added following lines for servers (fb1 and nodus ip addresses):
server 192.113.168.201
server 192.113.168.201
- I logged into each FE machine and ran following commands:
sudo systemctl stop systemd-timesyncd.service; sudo systemctl status systemd-timesyncd.service;
timedatectl; sleep 2;sudo systemctl daemon-reload; sudo systemctl start ntp; sleep 2; sudo systemctl status ntp; timedatectl
sudo hwclock -s
- The first line ensures that systemd-timesyncd.service is not running anymore. I did not uninstall timesyncd and left its configuration file as it is.
- The second line first shows the times of local and RTC clocks. Then reloads the daemon services to get ntp registered. Then starts ntp.service and shows it's status. Finally, the timedatectl command shows the synchronized clocks and that NTP synchronization has occured.
- The last line sets the local clock same as RTC clock. Even though this wasn't required as I saw that the clocks were already same to seconds, I just wanted a point where all the local clocks are synchronized to the ntp server.
- Hopefully, this would resolve our issue of restarting the models anytime some glitch happens or when we need ot update something in one of them.
Edit Tue Aug 24 10:19:11 2021:
I also disabled timesyncd on all FEs using sudo systemctl disable systemd-timesyncd.service
I've added this wiki page for summarizing the NTP synchronization knowledge. |
16291
|
Mon Aug 23 22:51:44 2021 |
Anchal | Update | General | Time synchronization efforts | Related elog thread: 16286
I didn't really achieve anything but I'm listing what I've tried.
- I know now that the timesyncd isn't working because systemd-timesyncd is known to have issues when running on a read-only file system. In particular, the service does not have privileges to change the clock or drift settings at /run/systemd/clock or /etc/adjtime.
- The workarounds to these problems are poorly rated/reviews in stack exchange and require me to change the /etc/systmd/timesyncd.conf file but I'm unable to edit this file.
- I know that Paco was able to change these files earlier as the files are now changed and configured to follow a debian ntp pool server which won't work as the FEs do not have internet access. So the conf file needs to be restored to using ntpserver as the ntp server.
- From system messages, the ntpserver is recognized by the service as shown in the second part of 16285. I really think the issue is in file permissions. the file /etc/adjtime has never been updated since 2017.
- I got help from Paco on how to edit files for FE machines. The FE machines directories are exported from fb1:/diskless/root.jessie/
- I restored the /etc/systmd/timesyncd.conf file to how it as before with just servers=ntpserver line. Restarted timesyncd service on all FEs,I tried a few su the synchronization did not happen.
- I tried a few suggestions from stackexchange but none of them worked. The only rated solution creates a tmpfs directory outside of read-only filesystem and uses that to run timesyncd. So, in my opinion, timesyncd would never work in our diskless read-only file system FE machines.
- One issue in an archlinux discussion ended by the questioner resorting to use opennptd from openBSD distribution. The user claimed that opennptd is simple enough that it can run ntp synchornization on a read-only file system.
- Somehwat painfully, I 'kind of' installed the openntpd tool in the fb1:/diskless/root.jessie directory following directions from here. I had to manually add user group and group for the FEs (which I might not have done correctly). I was not able to get the openntpd daemon to start properly after soe tries.
- I restored everything back to how it was and restarted timesyncd in c1sus even though it would not do anything really.
Quote: |
This time no matter how we try to set the time, the IOPs do not run with "DC status" green. (We kept having 0x4000)
|
|
16290
|
Mon Aug 23 19:00:05 2021 |
Koji | Update | General | Campus Wide Power Glitch Reported: Monday, 8/23/21 at 9:30am | Restarting the RTS was unsuccessful because of the timing discrepancy error between the RT machines and the FB. This time no matter how we try to set the time, the IOPs do not run with "DC status" green. (We kept having 0x4000)
We then decided to work on the recovery without the data recorded. After some burtrestores, the IMC was locked and the spot appeared on the AS port. However, IPC seemed down and no WFS could run. |
16289
|
Mon Aug 23 15:25:59 2021 |
Ian MacMillan | Update | CDS | SUS simPlant model | I am adding a State-space block to the SimPlant cds model using the example Chris gave. I made a new folder in controls called SimPlantStateSpace. wI used the code below to make a state-space LTI model with a 1D pendulum then I converted it to a discrete system using c2d matlab function. Then I used these in the rtss.m file to create the state space code I need in the SimPlantStateSpace_1D_model.h file.
%sys_model.m
Q = 1000;
phi = 1/Q;
g = 9.806;
m = 0.24; % mass of pendulum
l = 0.248; %length of pendulum
w_0 = sqrt(g/l);
f=16000 %this is the frequency of the channel that will be used
A = [0 1; -w_0^2*(1+1/Q*1i) -w_0/Q]
B = [0; 1/m];
C = [1 0];
D = [0];
sys_dc = ss(A,B,C,D)
sys=c2d(sys_dc, 1/f)
This code outputs the discrete state space that is added to the header file attached. |
Attachment 1: SimPlantStateSpace.zip
|
16288
|
Mon Aug 23 11:51:26 2021 |
Koji | Update | General | Campus Wide Power Glitch Reported: Monday, 8/23/21 at 9:30am | Campus Wide Power Glitch Reported: Monday, 8/23/21 at 9:30am (more like 9:34am according to nodus log)
nodus: rebooted. ELOG/apache/svn is running. (looks like Anchal worked on it)
chiara: survived the glitch thanks to UPS
fb1: not responding -> @1pm open to login / seemed rebooted only at 9:34am (network path recovered???)
megatron: not responding
optimus: no route to host
c1aux: ping ok, ssh not responding -> needed to use telnet (vme / vxworks)
c1auxex: ssh ok
c1auxey: ping ok, ssh not respoding -> needed to use telnet (vme / vxworks)
c1psl: ping NG, power cycled the switch on 1X2 -> ssh OK now
c1iscaux: ping NG -> rebooted the machine -> ssh recovered
c1iscaux2: does not exist any more
c1susaux: ping NG -> responds after 1X2 switch reboot
c1pem1: telnet ok (vme / vxworks)
c1iool0: does not exist any more
c1vac1: ethernet service restarted locally -> responding
ottavia: doesnot exist?
c1teststand: ping ok, ssh not respoding
3:20PM we started restarting the RTS |
16287
|
Mon Aug 23 10:17:21 2021 |
Paco | Summary | Computers | system reboot glitch | [paco]
At 09:34 PST I noted a glitch in the controls room as the machines went down except for c1ioo. Briefly, the video feeds disappeared from the screens, though the screens themselves didn't lose power. At first I though this was some kind of power glitch, but upon checking with Jordan, it most likely was related to some system crash. Coming back to the controls room, I could see the MC reflection beam swinging, but unfortunately all the FE models came down. I noticed that the DAQ status channels were blank.
I ssh into c1ioo no problem and ran "rtcds stop c1ioo c1als c1omc", then "rtcds restart c1x03" to do a soft restart. This worked, but the DAQ status was still blank. I then tried to ssh into c1sus and c1lsc without success, similarly c1iscex and c1iscey were unreachable. I went and did a hard restart on c1iscex by switching it off, then its extension chassis, then unplugging the power cords, then inverting these steps, and could ssh into it from rossa. I ran "rtcds start c1x01" and saw the same blank DAQ status. I noticed the elog was also down... so nodus was also affected?
[paco, anchal]
Anchal got on zoom to offer some assistance. We discovered that the fb1 and nodus were subject to some kind of system reboot at precisely 09:34. The "systemctl --failed" command on fb1 displayed both the daqd_dc.service and rc-local.service as loaded but failed (inactive). Is it a good idea to try and reboot the fb1 machine? ... Anchal was able to bring elog back up from nodus (ergo, this post).
[paco]
Although it probably needs the DAQ service from the fb1 machine to be up and running, I tried running the scripts/cds/rebootC1LSC.sh script. This didn't work. I tried running sudo systemctl restart daqd_dc from the fb1 machine without success. Running systemctl reset-failed "worked" for daqd_dc and rc-local services on fb1 in the sense that they were no longer output from systemctl --failed, but they remained inactive (dead) when running systemctl status on them. Following from 15303 I succeeded in restarting the daqd services. Turned out I needed to manually start the open-mx and mx services in fb1. I rerun the restartC1LSC script without success. The script fails because some machines need to be rebooted by hand.
|
16286
|
Fri Aug 20 06:24:18 2021 |
Anchal | Update | CDS | Time synchornization not running | I read on some stack exchange that 'NTP synchornized' indicator turns 'yes' in the output of command timedatectl only when RTC clock has been adjusted at some point. I also read that timesyncd does not do the change if the time difference is too much, roughly more than 3 seconds.
So I logged into all FE machines and ran sudo hwclock -w to synchronize them all to the system clocks and then waited if the timesyncd does any correction on RTC. It did not. A few hours later, I found the RTC clocks drifitng again from the system clocks. So even if the timesynd service is running as it should, it si not performing time correction for whatever reason.
Maybe we should try to use some other service?
Quote: |
The NTP synchronized flag in output of timedatectl command did not change to yes and the RTC is still 3 seconds ahead of the local clock.
|
|
16285
|
Fri Aug 20 00:28:55 2021 |
Anchal | Update | CDS | Time synchornization not running | I added ntpserver as a known host name for address 192.168.113.201 (fb1's address where ntp server is running) in the martian host list in the following files in Chiara:
/var/lib/bind/martian.hosts
/var/lib/bind/rev.113.168.192.in-addr.arpa
Note: a host name called ntp was already defined at 192.168.113.11 but I don't know what computer this is.
Then, I restarted the DNS on chiara by doing:
sudo service bind9 restart
Then I logged into c1lsc and c1ioo and ran following:
controls@c1ioo:~ 0$ sudo systemctl restart systemd-timesyncd.service
controls@c1ioo:~ 0$ sudo systemctl status systemd-timesyncd.service -l
● systemd-timesyncd.service - Network Time Synchronization
Loaded: loaded (/lib/systemd/system/systemd-timesyncd.service; enabled)
Active: active (running) since Fri 2021-08-20 07:24:03 UTC; 53s ago
Docs: man:systemd-timesyncd.service(8)
Main PID: 23965 (systemd-timesyn)
Status: "Idle."
CGroup: /system.slice/systemd-timesyncd.service
└─23965 /lib/systemd/systemd-timesyncd
Aug 20 07:24:03 c1ioo systemd[1]: Starting Network Time Synchronization...
Aug 20 07:24:03 c1ioo systemd[1]: Started Network Time Synchronization.
Aug 20 07:24:03 c1ioo systemd-timesyncd[23965]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 07:24:35 c1ioo systemd-timesyncd[23965]: Using NTP server 192.168.113.201:123 (ntpserver).
controls@c1ioo:~ 0$ timedatectl
Local time: Fri 2021-08-20 07:25:28 UTC
Universal time: Fri 2021-08-20 07:25:28 UTC
RTC time: Fri 2021-08-20 07:25:31
Time zone: Etc/UTC (UTC, +0000)
NTP enabled: yes
NTP synchronized: no
RTC in local TZ: no
DST active: n/a
The same output is shown in c1lsc too. The NTP synchronized flag in output of timedatectl command did not change to yes and the RTC is still 3 seconds ahead of the local clock.
Then I went to c1sus to see what was the status output before rstarting the timesyncd service. I got folloing output:
controls@c1sus:~ 0$ sudo systemctl status systemd-timesyncd.service -l
● systemd-timesyncd.service - Network Time Synchronization
Loaded: loaded (/lib/systemd/system/systemd-timesyncd.service; enabled)
Active: active (running) since Tue 2021-08-17 04:38:03 UTC; 3 days ago
Docs: man:systemd-timesyncd.service(8)
Main PID: 243 (systemd-timesyn)
Status: "Idle."
CGroup: /system.slice/systemd-timesyncd.service
└─243 /lib/systemd/systemd-timesyncd
Aug 20 02:02:18 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 02:36:27 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 03:10:35 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 03:44:43 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 04:18:51 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 04:53:00 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 05:27:08 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 06:01:16 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 06:35:24 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
Aug 20 07:09:33 c1sus systemd-timesyncd[243]: Using NTP server 192.168.113.201:123 (ntpserver).
This actually shows that the service was able to find ntpserver correctly at 192.168.113.201 even before I changed the name server file in chiara. So I'm retracting the changes made to name server. They are probably not required.
The configuration files for timesynd.conf are read only even with sudo. I tried changing permissions but that did not work either. Maybe these files are not correctly configured. The man page of timesyncd says to use field 'NTP' to give the ntp servers. Our files are using field 'Servers'. But since we are not getting any error message, I don't think this is the issue here.
I'll look more into this problem. |
16284
|
Thu Aug 19 14:14:49 2021 |
Koji | Update | CDS | Time synchornization not running | 131.215.239.14 looks like Caltech's NTP server (ntp-02.caltech.edu)
https://webmagellan.com/explore/caltech.edu/28415b58-837f-4b46-a134-54f4b81bee53
I can't say it is correct or not as I did not make the survey at your level. I think you need a few tests of reconfiguring and restarting the NTP clients to see if time synchronization starts. Because the local time is not regulated right now anyway, this operation is safe I think.
|
16283
|
Thu Aug 19 03:23:00 2021 |
Anchal | Update | CDS | Time synchornization not running | I tried to read a bit and understand the NTP synchronization implementation in FE computers. I'm quite sure that NTP synchronization should be 'yes' if timesyncd are running correctly in the output of timedatectl in these computers. As Koji reported in 15791, this is not the case. I logged into c1lsc, c1sus and c1ioo and saw that RTC has drifted from the software clocks too which does not happen if NTP synchronization was active. This would mean that almost certainly, if the computers are rebooted, the synchronization will be lost and the models will fail to come online.
My current findings are the following (this should be documented in wiki once we setup everything):
- nodus is running a NTP server using chronyd. One can check the configuration of this NTP serer in /etc/chornyd.conf
- fb1 is running an NTP server using ntpd that follows nodus and an IP address 131.215.239.14. This can be seen in /etc/ntp.conf.
- There are no comments to describe what this other server (131.215.239.14) is. Does the GC network have an NTP server too?
- c1lsc, c1sus and c1ioo all have systemd-timesyncd.service running with configuration file in /etc/systemd/timesyncd.conf.
- The configuration file set Servers=ntpserver but echo $ntpserver produces nothing (blank) on these computers and I've been unable to find anyplace where ntpserver is defined.
- In chiara (our name server), the name server file /etc/hosts does not have any entry for ntpserver either.
- I think the problem might be that these computers are unable to find the ntpserver as it is not defined anywhere.
The solution to this issue could be as simple as just defining ntpserver in the name server list. But I'm not sure if my understanding of this issue is correct. Comments/suggestions are welcome for future steps.
|
16282
|
Wed Aug 18 20:30:12 2021 |
Anchal | Update | ASS | Fixed runASS scripts | Late elog: Original time of work Tue Aug 17 20:30 2021
I locked the arms yesterday remotely and tried running runASS.py scripts (generally ran by clicking Run ASS buttons on IFO OVERVIEW screen of ASC screen). We have known for few weeks that this script stopped working for some reason. It would start the dithering and would optimize the alignment but then would fail to freeze the state and save the alignment.
I found the caget('C1:LSC-TRX_OUT') or caget('C1:LSC-TRY_OUT') were not working in any of the workstations. This is weird since caget was able to acquire these fast channel values earlier and we have seen this script to work for about a month without any issue.
Anyways, to fix this, I just changed the channel name to 'C1:LSC-TRY_OUT16' when the script checks in the end if the arm has indeed been aligned. It was only this step that was failing. Now the script is working fine and I tested them on both arms. On the Y arm, I misaligned the arm by adding bias in yaw by changing C1:SUS-ITMY_YAW_OFFSET from -8 to 22. The script was able to align the arm back. |
16281
|
Tue Aug 17 04:30:35 2021 |
Koji | Update | SUS | New electronics | Received:
Aug 17, 2021 2x ISC Whitening
Delivered 2x Sat Amp board to Todd
|
Attachment 1: P_20210816_234136.jpg
|
|
Attachment 2: P_20210816_235106.jpg
|
|
Attachment 3: P_20210816_234220.jpg
|
|
16280
|
Mon Aug 16 23:30:34 2021 |
Paco | Update | CDS | AS WFS commissioning; restarting models | [koji, ian, tega, paco]
With the remote/local assistance of Tega/Ian last friday I made changes on the c1sus model by connecting the C1:ASC model outputs (found within a block in c1ioo) to the BS and PRM suspension inputs (pitch and yaw). Then, Koji reviewed these changes today and made me notice that no changes are actually needed since the blocks were already in place, connected in the right ports, but the model probably just wasn't rebuilt...
So, today we ran "rtcds make", "rtcds install" on the c1ioo and c1sus models (in that order) but the whole system crashed. We spent a great deal of time restarting the machines and their processes but we struggled quite a lot with setting up the right dates to match the GPS times. What seemed to work in the end was to follow the format of the date in the fb1 machine and try to match the timing to the sub-second level. This is especially tricky when performed by a human action so the whole task is tedious. We anyways completed the reboot for almost all the models except the c1oaf (which tends to make things crashy) since we won't need it right away for the tasks ahead. One potential annoying issue we found was in manually rebooting c1iscey because one of its network ports is loose (the ethernet cable won't click in place) and it appears to use this link to boot (!!) so for a while this machine just wasn't coming back up.
Finally, as we restored the suspension controls and reopened the shutters, we noticed a great deal of misalignment to the point no reflected beam was coming back to the RFPD table. So we spent some time verifying the PRM alignment and TT1 and TT2 (tip tilts) and it turned out to be mostly the latter pair that were responsible for it. We used the green beams to help optimize the XARM and YARM transmissions and were able to relock the arms. We ran ASS on them, and then aligned the PRM OpLevs which also seemed off. This was done by giving a pitch offset to the input PRM oplev beam path and then correcting for it downstream (before the qpd). We also adjusted the BS OpLev in the end.
Summary; the ASC BS and PRM outputs are now built into the SUS models. Let the AS WFS loops be closed soon!
Addenda by KA
- Upon the RTS restarting,
Date/Time adjustment
sudo date --set='xxxxxx'
- If the time on the CDS status medm screen for each IOP match with the FB local time, we ran
rtcds start c1x01
(or c1x02, etc)
- Every time we restart the IOPs, fb was restarted by
telnet fb1 8083
> shutdown
and restarted mx_stream from the CDS screen because these actions change the "DC" status.
- Today we once succeeded to restart the vertex machines. However, the RFM signal transmission did fail. So the end two machines were power cycled as well as c1rfm, but this made all the machines in RED again. Hell...
- We checked the PRM oplev. The spot was around the center but was clipped. This made us so confused. Our conclusion was that the oplev was like that before the RTS reboot. |
16279
|
Thu Aug 12 20:52:04 2021 |
Koji | Update | General | PSL shutter was closed this morning | I did a bit more investigation on this.
- I checked P1~P4, PTP2/3, N2, TP2, TP3. But found only P1a and P2 were affected.
- Looking at the min/mean/max of P1a and P2 (Attachment 1), the signal had a large fluctuation. It is impossible to have P1a from 0.004 to 0 instantaneously.
- Looking at the raw data of P1a and P2 (Attachment 2), the value was not steadily large. Instead it looks like fluctuating noise.
So my conclusion is that because of an unknown reason, an unknown noise coupled only into P1a and P2 and tripped the PSL shutter. I still don't know the status of the mail alert. |
Attachment 1: Screen_Shot_2021-08-12_at_20.51.19.png
|
|
Attachment 2: Screen_Shot_2021-08-12_at_20.51.34.png
|
|
16278
|
Thu Aug 12 14:59:25 2021 |
Koji | Update | General | PSL shutter was closed this morning | What I was afraid of was the vacuum interlock. And indeed there was a pressure surge this morning. Is this real? Why didn't we receive the alert? |
Attachment 1: Screen_Shot_2021-08-12_at_14.58.59.png
|
|
16277
|
Thu Aug 12 11:04:27 2021 |
Paco | Update | General | PSL shutter was closed this morning | Thu Aug 12 11:04:42 2021 Arrived to find the PSL shutter closed. Why? Who? When? How? No elog, no fun. I opened it, IMC is now locked, and the arms were restored and aligned. |
16276
|
Wed Aug 11 12:06:40 2021 |
Yehonathan | Update | CDS | Opto-isolator for c1auxey | I redid the differential input experiment using the DS360 function generator we recently got. I generated a low frequency (0.1Hz) sine wave signal with an amplitude 0.5V and connected the + and - output to a differential input on the new c1auxcey Acromag chassis. I recorded a time series of the corresponding EPICS channel with and without the common on the DS360 connected to the Ref connector on the Acromag unit. The common connector on the DS360 is not normally grounded (there is a few tens of kohms between the ground and common connectors). The attachment shows that, indeed, the analog input readout is extremely noisy with the Ref being disconnected. The point where the Ref was connected to common is marked in the picture.
Conclusion: Ref connector on the analog input Acromag units must be connected to some stable voltage source for normal operation. |
Attachment 1: SUS-ETMY_SparePDMon0_2.png
|
|
16275
|
Wed Aug 11 11:35:36 2021 |
Paco | Update | LSC | PRMI MICH orthogonality plan | [yehonathan, paco]
Yesterday we discussed a bit about working on the PRMI sensing matrix.
In particular we will start with the "issue" of non-orthogonality in the MICH actuated by BS + PRM. Yesterday afternoon we played a little with the oscillators and ran sensing lines in MICH and PRCL (gains of 50 and 5 respectively) in the times spanning [1312671582 -> 1312672300], [1312673242 -> 1312677350] for PRMI carrier and [1312673832 -> 1312674104] for PRMI sideband. Today we realize that we could have enabled the notchSensMat filter, which is a notch filter exactly at the oscillator's frequency, in FM10 and run a lower gain to get a similar SNR. We anyways want to investigate this in more depth, so here is our tentative plan of action which implies redoing these measurements:
Task: investigate orthogonality (or lack thereof) in the MICH when actuated by BS & PRM.
1) Run sensing MICH and PRCL oscillators with PRMI Carrier locked (remember to turn NotchSensMat filter on).
2) Analyze data and establish the reference sensing matrix.
3) Write a script that performs steps 2 and 3 in a robust and safe way.
4) Scan the C1:LSC-LOCKIN_OUTMTRX, MICH to BS and PRM elements around their nominal values.
5) Scan the MICH and PRCL RFPD rotation angles around their nominal values.
We also talked about the possibility that the sensing matrix is strongly frequnecy dependant such that measuring it at 311Hz doesn't give us accurate estimation of it. Is it worthwhile to try and measure it at lower frequencies using an appropriate notch filter?
Wed Aug 11 15:28:32 2021 Updated plan after group meeting
- The problem may be in the actuators since the orthogonality seems fine when actuating on the ITMX/ITMY, so we should instead focus on measuring the actuator transfer functions using OpLevs for example (same high freq. excitation so no OSEM will work > 10 Hz). |
16274
|
Tue Aug 10 17:24:26 2021 |
paco | Update | General | Five day trend | Attachment 1 shows a five and a half day minute-trend of the three temperature sensors. Logging started last Thursday ~ 2 pm when all sensors were finally deployed. While it appears that there is a 7 degree gradient along the XARM it seems like the "vertex" (more like ITMX) sensor was just placed on top of a network switch (which feels lukewarm to the touch) so this needs to be fixed. A similar situation is observed in the ETMY sensor. I shall do this later today.
Done. The temperature reading should now be more independent from nearby instruments.
Wed Aug 11 09:34:10 2021 I updated the plot with the full trend before and after rearranging the sensors. |
Attachment 1: six_day_minute_trend.png
|
|
|