40m
QIL
Cryo_Lab
CTN
SUS_Lab
TCS_Lab
OMC_Lab
CRIME_Lab
FEA
ENG_Labs
OptContFac
Mariner
WBEEShop
|
40m Log |
Not logged in |
 |
|
Fri May 9 01:36:28 2014, rana, Summary, SUS, Optical Lever QPD Sum trends: they're almost all too weak
|
Mon May 12 22:42:19 2014, rana, Summary, SUS, Optical Lever QPD Sum trends: they're almost all too weak 
|
Mon May 12 22:52:59 2014, Jenne, Summary, SUS, Optical Lever Filters are all different
|
Tue May 13 13:27:58 2014, Steve, Summary, SUS, Optical Lever Servos setting table
|
Tue May 13 17:03:05 2014, Steve, Summary, SUS, ETMX oplev laser replaced
|
Tue May 13 17:31:32 2014, Jenne, Summary, SUS, ETMX oplev laser replaced: New oplev gains set 
|
Tue May 13 22:55:57 2014, Jenne, Summary, SUS, ETMX oplev: cleanup
|
Wed May 14 10:04:06 2014, Steve, Summary, SUS, oplev laser and temperature
|
Tue May 20 09:12:25 2014, Steve, Summary, SUS, ETMX oplev qpd board  
|
Tue May 20 15:54:39 2014, rana, Summary, SUS, ETMX oplev qpd board
|
|
Message ID: 9946
Entry time: Tue May 13 13:27:58 2014
In reply to: 9942
Reply to this: 9947
|
Author: |
Steve |
Type: |
Summary |
Category: |
SUS |
Subject: |
Optical Lever Servos setting table |
|
|
Quote: |
For some reason or another, I decided that we should see if the optical lever servos were injecting too much noise into the test masses. The ITMs are much worse than the ETMs and I am afeared that they might be making the main noise for our arms in the 20-40 Hz region. Jenne is checking up on these feedback loops to see what's up.
To estimate the actuator gains of the mirrors, I turned on 1 count drives from LSC/CAL oscillators into the LSC drives of each test mass at the frequencies shown in the plot with the resulting peaks showing up in in POX/Y with the single arm locks in red. I will leave these going permanently, but with 0.1 count ampltiudes; we need to make it so in the scripts.
|
I'm in the process of filling this table
OPLEV
SERVO
|
300 ^
2:0
|
BR
16,24
Hz
|
ELP |
RLP |
BOOST |
RES |
GAIN
|
QPD
COUNTS
|
QPD
mW
|
QPD
beam
OD
|
HE/NE
output
mW
|
%
back
on QPD
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ETMY PIT |
FM1 |
FM5 |
|
55 |
|
|
-30 |
8,200 |
0.2 |
|
3.3 |
|
YAW |
FM1 |
FM5 |
|
55 |
|
|
-28 |
|
|
|
|
|
ETMX PIT |
FM1 |
FM5 |
35 |
|
|
|
4.4 |
900 |
0.2 |
|
1.7 |
|
YAW |
FM1 |
FM5 |
35 |
|
|
|
2.1 |
|
|
|
|
|
ITMY PIT |
FM1 |
FM5 |
|
|
|
3.3 |
52 |
14,400 |
0.4 |
|
9.5 |
|
YAW |
FM1 |
FM5 |
|
|
|
3.3 |
-46 |
|
|
|
|
|
ITMX PIT |
FM1 |
FM5 |
50 |
|
|
3.3 |
30 |
7,400 |
0.17 |
|
2.8 |
|
YAW |
FM1 |
FM5 |
50 |
|
|
3.3 |
-20 |
|
|
|
|
|
BS PIT |
FM1 |
FM5 |
35 |
|
|
3.3 |
9 |
2,800 |
0.05 |
|
2.8 |
|
YAW |
FM1 |
FM5 |
35 |
|
|
3.3 |
-9 |
|
|
|
|
|
PRM PIT |
FM1 |
FM5 |
55 |
|
FM7 |
3.3 |
7 |
3200 |
0.06 |
|
2.8 |
|
YAW |
FM1 |
FM5 |
55 |
|
FM7 |
3.3 |
-5 |
|
|
|
|
|
SRM PIT |
FM1 |
|
|
|
|
|
-20 |
|
|
|
9.5 |
|
YAW |
FM1 |
|
|
|
|
|
20 |
|
|
|
|
|
I should replace ETMX He/Ne laser |
|
|