40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Mon Mar 24 19:42:12 2014, Charles, Frogs, VAC, Power Failure 
    Reply  Mon Mar 24 21:36:28 2014, Koji, Update, General, Power Failure 
       Reply  Mon Mar 24 22:13:37 2014, steve, Update, General, Power Failure poweroutage.png
          Reply  Tue Mar 25 14:52:57 2014, steve, Update, VAC, vacuum is recovered 17hrsNoPumping.png
             Reply  Fri Mar 28 16:26:20 2014, steve, Update, VAC, RGA scan after power failure afterPowerFailure.png
          Reply  Tue Mar 25 16:11:24 2014, Koji, Update, General, Power Failure 
             Reply  Wed Mar 26 11:30:07 2014, Koji, Update, General, Power Failure 
                Reply  Wed Mar 26 22:22:43 2014, Manasa, Update, General, Recovery 
                   Reply  Thu Mar 27 10:34:39 2014, ericq, Update, General, Recovery 
Message ID: 9748     Entry time: Mon Mar 24 22:13:37 2014     In reply to: 9747     Reply to this: 9749   9750
Author: steve 
Type: Update 
Category: General 
Subject: Power Failure 

Quote:

I'm checking the status from home.

P1 is 8e-4 torr

nodus did not feel the power outage (is it APS supported?)

linux1 booted automatically

c1ioo booted automatically.

c1sus, c1lsc, c1iscex, c1iscey need manual power button push.

 9:11pm closed PSL shutter, turned Innolight 2W laser on,

         turned 3 IFO air cond on,

        CC1 5.1e-5 torr, V1 is closed, Maglev has failed, valve configuration is " Vacuum Normal "  with V1 & VM1 closed, RGA not running,   c1vac1 and c1vac2   were saved by UPS,

        (Maglev is not connected to the UPS because it is running on 220V)

        reset & started Maglev.........I can not open V1 without the 40mars running...........

        Rossa is the only computer running in the control room,

        Nodus and Linux1 was saved by UPS,

        turned on IR lasers at the ends, green shutters are closed

It is safe to leave the lab as is.

     

Attachment 1: poweroutage.png  607 kB  | Hide | Hide all
poweroutage.png
ELOG V3.1.3-