Author: Steve 
Type: Update 
Category: PEM 
Subject: air cond maitenance is today 

 Outside air quality at 8:30am  1.1 million of 0.5 micron particles cf / min with MET counter #2

AC unit output measured  directly at the outlet of east end  6,000  and south end 3,000 of 0.5 micron particles cf / min with counter #2

Lab measurement at the top of IOOC 20K of 0.5 micron particles cf / min with MET #1

HEPA filters: 2 mobile units  at the middle of the east arm at speed 100%, PSL enclosure 20% and south end flow bench are running.

The PSL, south flow bench and mobile unit (Envirco  sn69406003 ) measured zero counts of 0.5 & 0.3 micron particles

Envirco HEPA filter unit sn 69406001 measured 50 particles of 0.5micron and 320 of 0.3 micron particles cf / min with counter #2

This filter will be replaced.

                   

NOTE: inside air quality peaks we can not control. It depends on the weather and our house keeping.

When your work is particle sensitive keep your eyes on the particle counter.

 

 

 

 