I had a chat with Alex this morning and discovered that the dcu_ids 13,14,15,16 are reserved currently, and should not be used. I was told 9-12 and 17-26 were fine to use. I pointed out that we will eventually have more modules than that. His response was he is currently working on the framebuilder code and "modernizing" it, and that those restrictions will hopefully be lifted in the future although he isn't certain at this time what the real maximum gds_id number is (he was only willing to vouch for up to 26 - although the OMC seems to be currently working and set to 30).
Alex also suggested running an iop module to provide timing (since we are using adcSlave=1 option in the models). Apparently these are x00.mdl, x01.mdl, x11.mdl files in the /home/control/cds/advLigoRTS/src/epics/simLink/ directory. I saved x00.mdl as io1.mdl (I didn't want to use io0 as its a pain to differentiate between a zero and 'O'. This new IOP is using gds_node=1, dcu_id=9. I modified the approriate files to include it.
I modified /etc/rc.d/rc.local and added io1 to shmem line. I modified /cvs/cds/caltech/target/fb/daqdrc to use dcu_id 9 as the controller (this is the new iop model dcu_id number). In that same directory I modifed the file master by adding /cvs/cds/caltech/chans/daq/C1IO1.ini as well as uncommenting tpchn_C1 line. I modified testpoint.par in /cvs/cds/caltech/target/gds/param to include C-node0, and modified the prognum for lsc and lsp to 0x31001003 and 0x31001005.
So I started the 3 processes with startio1, startlsc, startlsp, then went to the fb directory and started the framebuilder. However, the model lsc.mdl is still having issues, although lsp and io1 seem to be working. At this point I just need to track down what fundamentally is different between lsc and lsp and correct it in the lsc model. I'm hoping its not related to the fact that we actually had a previous lsc front end and there's some legacy stuff getting in the way. One thing I can test is changing the name and see if that runs.
|