Author: Anchal 
Type: Update 
Category: General 
Subject: c1vac issues, 1 pressure gauge died 

[Anchal, Paco, Tega]


Disk full issue:

c1vac was showing /var disk to be full. We moved all gunzipped backup logs to /home/controls/logBackUp. This emptied 36% of space on /var. Ideally, we need not log so much. Some solution needs to be found for reducing these log sizes or monitoring them for smart handling.


Pressure sensor malfunctioning:

We were unable to opel the PSL shuttter, due to the interlock with C1:Vac-P1a_pressure. We found that C1:Vac-P1a_pressure is not being written by serial_MKS937a service on c1vac. The issue was the the sensor itself has become bad and needs to be replaced. We believe that "L 0E-04" in the status (C1:Vac-P1a_status) message indicates a malfunctioning sensor.

Quick fix:

We removed writing of C1:Vac-P1a_pressure and C1:Vac-P1a_status from MKS937a and mvoed them to XGS600 which is using the sensor 1 from main volume. See this commit.

Now we are able to open PSL shutter. The sensor should be replaced ASAP and this commit can be reverted then.