Entry  Wed Sep 29 17:10:09 2021, Anchal, Summary, CDS, c1teststand problems summary c1teststand_issues_summary.pdf
    Reply  Thu Sep 30 14:09:37 2021, Anchal, Summary, CDS, New way to ssh into c1teststand 
       Reply  Thu Mar 3 15:37:40 2022, Anchal, Summary, CDS, c1teststand restructured 
    Reply  Mon Oct 4 11:05:44 2021, Anchal, Summary, CDS, c1teststand problems summary 
       Reply  Mon Oct 4 18:00:16 2021, Koji, Summary, CDS, c1teststand problems summary 
          Reply  Tue Oct 5 17:58:52 2021, Anchal, Summary, CDS, c1teststand problems summary 
       Reply  Tue Oct 5 18:00:53 2021, Anchal, Summary, CDS, c1teststand time synchronization working now 
          Reply  Mon Oct 11 17:31:25 2021, Anchal, Summary, CDS, Fixed mounting of mx devices in fb. daqd_dc is running now. 
             Reply  Mon Oct 11 18:29:35 2021, Anchal, Summary, CDS, Moving forward? 
                Reply  Tue Oct 12 17:20:12 2021, Anchal, Summary, CDS, Connected c1sus2 to martian network 
                   Reply  Tue Oct 12 23:42:56 2021, Koji, Summary, CDS, Connected c1sus2 to martian network 
                      Reply  Wed Oct 13 11:25:14 2021, Anchal, Summary, CDS, Ran c1sus2 models in martian CDS. All good! CDS_screens_running.png
                         Reply  Tue Oct 19 18:20:33 2021, Ian MacMillan, Summary, CDS, c1sus2 DAC to ADC test data3_Plots.pdfdata2_Plots.pdf
                            Reply  Tue Oct 19 23:43:09 2021, Koji, Summary, CDS, c1sus2 DAC to ADC test P_20211019_224433.jpgP_20211019_224122.jpgP_20211019_224400.jpgP_20211019_224411.jpg
                               Reply  Wed Oct 20 11:48:27 2021, Anchal, Summary, CDS, Power supple configured correctly. 
                               Reply  Tue Oct 26 18:24:00 2021, Ian MacMillan, Summary, CDS, c1sus2 DAC to ADC test data2_Plots.pdfdata3_Plots.pdf
                         Reply  Wed Dec 22 17:40:22 2021, Anchal, Summary, CDS, c1su2 model updated with SUS damping blocks for 7 SOSs 
                            Reply  Wed Dec 29 20:09:40 2021, rana, Summary, CDS, c1su2 model updated with SUS damping blocks for 7 SOSs 
                            Reply  Fri Mar 4 11:04:34 2022, Anchal, Summary, CDS, c1susaux2 system setup and running 40mBHD_C1SUSAUX2_Acromag_Chassis.pdf
                               Reply  Mon Mar 7 19:38:47 2022, Anchal, Summary, CDS, c1susaux2 slow controls issues 
                               Reply  Mon Mar 14 12:20:05 2022, Anchal, Summary, CDS, c1susaux2 slow controls acromag chassis installed BHD_WatchDogs.png40mBHD_C1SUSAUX2_Acromag_Chassis.pdf
                                  Reply  Thu Mar 17 19:12:44 2022, Anchal, Summary, CDS, c1auxey1 slow controls acromag chassis installed, not powered 
                                     Reply  Fri Mar 18 18:39:13 2022, Yehonathan, Summary, CDS, c1auxey1 slow controls acromag chassis installed, powered 
                                        Reply  Fri Mar 18 19:10:51 2022, Anchal, Summary, CDS, c1auxey1 slow controls issues 
                                           Reply  Mon Mar 21 18:42:06 2022, Anchal, Summary, CDS, c1auxey1 slow controls issues 
                                  Reply  Mon Apr 4 17:03:47 2022, Anchal, Summary, CDS, c1susaux2 slow controls acromag chassis fixed and installed Screenshot_2022-04-04_17-03-26.png
                            Reply  Tue Mar 15 11:52:34 2022, Anchal, Summary, CDS, c1su2 model updated for sending Run/Acquire Binary Output to Binary Interface card c1su2.pdf
                               Reply  Tue Mar 15 14:10:41 2022, Anchal, Summary, CDS, c1su2 model remade, reinstalled, restarted after the update 
             Reply  Tue Oct 12 17:10:56 2021, Anchal, Summary, CDS, Some more information 
Message ID: 16700     Entry time: Fri Mar 4 11:04:34 2022     In reply to: 16533     Reply to this: 16712   16724
Author: Anchal 
Type: Summary 
Category: CDS 
Subject: c1susaux2 system setup and running 

I took the c1teststand computer from teststand and converted it into c1susaux2. To do so, I installed a fresh copy of debian 10 on it and followed the steps on this wiki page. I did some parts slightly differently though. The directory /cvs/cds/caltecg/c1susaux2 is a repository and contains the service unit file modbusIOC.service as well. A symbolic link is created at /etc/systemd/system to use this service file for creating the modbusIOC service. All db files are generated by parsing the acromag chassis wiring file using this python script.

The service file is running without any errors now and all channels are available. The leftmost bench on EEshop at 40m is now ready to do LO1 slow controls and monitor testing. If someone gets time today, they can hookup an unused coil driver to the chassis and verify ENABLE switching and monitoring through the optical isolators. We can also drive some voltage on the PD monitors and verify the functioning of our ADCs. Once this test passes, it is straight forward to finish the remaining 6 SOS wiring and we would be good to install the chassis.

Attaching wiring diagram of c1susuaux2 acromag chassis. Any comments/modification suggestions should come soon as we'll go ahead and wire it soon.

Note: While accessing channels using caget on c1susuaux2, you might get a warning "Identical process variable names on multiple servers". You can safely ignore it. It just means that channel is accessible on that particular computer via two different network interfaces (martian network eno1 and acromag subnetwork eno2) and it will just pick one of them.

Attachment 1: 40mBHD_C1SUSAUX2_Acromag_Chassis.pdf  1008 kB  | Hide | Hide all
40mBHD_C1SUSAUX2_Acromag_Chassis.pdf
ELOG V3.1.3-