Mon Jun 1 13:56:52 2009, Alberto, Update, PSL, Laser Power after fixing the laser chiller
|
Mon Jun 1 15:01:31 2009, rana, Update, PSL, Laser Power after fixing the laser chiller: more traces
|
Mon Jun 1 19:19:26 2009, rana, Update, PSL, 1000 days of hour-trend
|
|
Message ID: 1639
Entry time: Mon Jun 1 15:01:31 2009
In reply to: 1636
Reply to this: 1640
|
Author: |
rana |
Type: |
Update |
Category: |
PSL |
Subject: |
Laser Power after fixing the laser chiller: more traces |
|
|
If you look at the correlation between RMTEMP and HTEMP, you see what we knew: namely that there
was a 1:1 correlation before. After the chiller fix, I can see no correlation between the room and
amplifier temperature at the resolution of 10:1. So the chiller loop has a gain > 10 at 24 hour time
scales.
I don't understand why the PMC looks more stable. |
|
|