Entry  Thu Aug 20 00:21:51 2020, gautam, Update, Electronics, First look at HV coil driver IMG_8724.JPGtimeDomain.pdfHVampNoise.pdf
    Reply  Sun Aug 23 23:36:58 2020, gautam, Update, Electronics, First look at HV coil driver IMG_5379.JPGstabilityCriterion.pdf
       Reply  Wed Aug 26 16:12:25 2020, gautam, Update, Electronics, Test mass coil current requirements coilCurrents.png
       Reply  Tue Sep 1 15:39:04 2020, gautam, Update, Electronics, HV coil driver oscillations fixed testSetup.pdfHVampNoise_driven.pdf
          Reply  Thu Oct 22 11:14:47 2020, gautam, Update, Electronics, HV coil driver packaged into 2U chassis HVampNoise_driven_chassis.pdfHVampNoise_dispUnits.pdfD1900163_measurementSetup.zip
             Reply  Thu Oct 22 13:04:42 2020, rana, Update, Electronics, HV coil driver packaged into 2U chassis 
                Reply  Thu Oct 22 22:01:53 2020, gautam, Update, Electronics, HV coil driver packaged into 2U chassis DACnoiseFilterGain.pdfDACnoiseFilterNoises.pdf
                   Reply  Fri Oct 23 09:03:43 2020, anchal, Update, Electronics, HV coil driver packaged into 2U chassis 
             Reply  Thu Nov 12 14:55:35 2020, gautam, Update, Electronics, More systematic noise characterization powerSupplyNoise.pdfcoherence.pdf
                Reply  Thu Nov 12 15:40:42 2020, Koji, Update, Electronics, More systematic noise characterization 
                   Reply  Mon Nov 16 00:02:34 2020, rana, Update, Electronics, More systematic noise characterization 
                      Reply  Wed Jan 20 10:13:06 2021, gautam, Update, Electronics, HV Power supply bypassing bypassCaps.pdfIMG_9079.jpgIMG_9078.jpgHVampNoise_driven_chassis.pdfprintCoilCurrents.pdf
                         Reply  Mon Feb 1 12:30:21 2021, gautam, Update, Electronics, More careful characterization HVPS.pdfHV_testckt.pdftotalNoise.pdf
                         Reply  Wed Feb 10 21:14:03 2021, gautam, Update, Electronics, Production version of the HV coil driver tested inputDiffRecTF.pdfLVnoises.pdftotalNoise.pdftimeDomainTests.pdf
                            Reply  Fri Feb 26 16:31:02 2021, gautam, Update, Electronics, Production version of the HV coil driver tested with KEPCO HV supplies totalNoise_KEPCO.pdf
                               Reply  Fri Feb 26 20:20:43 2021, Koji, Update, Electronics, Production version of the HV coil driver tested with KEPCO HV supplies 
                                  Reply  Sat Feb 27 17:25:42 2021, gautam, Update, Electronics, Production version of the HV coil driver tested with KEPCO HV supplies 
                                     Reply  Thu May 20 16:56:21 2021, Koji, Update, Electronics, Production version of the HV coil driver tested with KEPCO HV supplies P_20210520_154523_copy.jpg
Message ID: 15846     Entry time: Fri Feb 26 16:31:02 2021     In reply to: 15802     Reply to this: 15847
Author: gautam 
Type: Update 
Category: Electronics 
Subject: Production version of the HV coil driver tested with KEPCO HV supplies 

Koji asked me to test the production version of the coil driver with the KEPCO HV supplies. See Attachment #1 for the results. For comparison, I've added a single trace from the measurements made with the HP supplies. I continue to see excess noise with the KEPCO supplies. Note that in the production version of the board that was tested, there are a pair of 10uF bypass capacitors on the board for the HV supply lines. It is possible that one or both KEPCO supplies are damaged - one was from the ASY setup and one I found in the little rack next to 1X2. The test conditions were identical to that with the HP supplies (as best as I could make it so).

Attachment 1: totalNoise_KEPCO.pdf  467 kB  | Hide | Hide all
totalNoise_KEPCO.pdf
ELOG V3.1.3-