40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Sat Sep 19 23:59:22 2020, anchal, Summary, ALS, ALS noise budget update ALS_nb_ExtraPoles.pdfALS_controls.yamlALS_nb_Kiwamus_Values.pdfALS_controls_Kiwamus_Values.yamlALS_simulink_model.svg
    Reply  Sun Sep 20 23:12:13 2020, rana, Summary, ALS, ALS noise budget update 
       Reply  Tue Sep 22 00:14:43 2020, anchal, Summary, ALS, ALS noise budget update ALS_NoiseBudgetUpdate.pdfALS_controls.yaml
          Reply  Tue Sep 22 12:14:42 2020, rana, Summary, ALS, ALS noise budget update 
             Reply  Wed Sep 23 11:13:49 2020, anchal, Summary, ALS, ALS noise budget update ALS_NoiseBudgetUpdate.pdfALS_controls.yaml
                Reply  Wed Oct 7 16:56:23 2020, anchal, Summary, ALS, ALS noise budget update - Updated AUX PDH Loop values Extract_X_AUX_PDH_Model.zipALS_NoiseBudgetUpdate.pdf
                   Reply  Thu Oct 8 11:59:52 2020, rana, Summary, ALS, ALS noise budget update - Updated AUX PDH Loop values 
                      Reply  Fri Oct 9 18:32:14 2020, anchal, Summary, ALS, ALS noise budget update - Updated AUX PDH Loop values 
                         Reply  Wed Oct 14 17:03:55 2020, anchal, Summary, ALS, ALS noise budget update - Added whitening filter for ADC ALS_NoiseBudgetUpdate.pdf
Message ID: 15626     Entry time: Wed Oct 14 17:03:55 2020     In reply to: 15622
Author: anchal 
Type: Summary 
Category: ALS 
Subject: ALS noise budget update - Added whitening filter for ADC 

Koji recommended that I can add whitening filters to suppress ADC noise easily. I added a filter before ADC in ALS loop with 4 zeros at 1.5 Hz and 4 poles at 100 Hz and added a reversed filter in the digital filter of ALS. This did not change the performance of the loop but significantly reduced the contribution of ADC noise above 1 Hz. One can see ALS_controls.yaml for the filter description. Please let me know if this does not make sense or there is something that I have overlooked.

Now, the dominant noise source is DFD noise below 100 Hz and green laser frequency noise above that. For DFD noise, I used data dating back to Kiwamu's paper. The noise contribution from DFD in the model is lower than the latest measured ALS noise budget post on elog. I'll look further into design details and noise of DFD.


Code, data, and schematics

Attachment 1: ALS_NoiseBudgetUpdate.pdf  158 kB  Uploaded Wed Oct 14 18:14:50 2020  | Show | Show all
ELOG V3.1.3-