[Koji / Gautam (Remote)]
Lab status
- Gray Panel: The lab AC was off. Turned on all three (N/S, CTRL RM, E/W)
- The control room AC was running.
Work stations
- Control Room: All the control machines were running. We knew that nodus/chiara/fb were running
- 1X6/7:
- JETSTOR was making beeping sound. “Power #1 failed””power #2 failed”
- Optimus & megatron were off -> turned on -> up and running now
- 1X1/2:
- Power cycled the netgear at the top of the IOO rack (maybe not necessary)
- Turned on c1ioo -> up and running now
- 1X4/5: Rebooted c1sus / c1lsc -> up and running now
- 1X9: Rebooted c1iscex -> up and running now
- 1Y4: Rebooted c1iscex -> up and running now
Vacuum status
- Looked like everything was running as if it did not see the power glitch
- TP1 normal: Set speed 33.6k rpm / Actual speed 33.6k rpm
- TP2 normal: 66k rpm / PTP2 16.0 mtorr
- TP3 normal: 31k rpm / PTP3 45.4mtorr
- P1 LOW / P2 1.7mtorr / CC2 1.1e-6 / P3 7.6e-2 / P4 LO
- Annuli: 2.7~3torr
- CC1 9.6e-6 / SUPER BEE 0.9mtorr
C1VAC recovery
- c1vac was alive, but was isolated from the martian network
- Checked the network I/F status with
/sbin/ifconfig -a
- eth0 had no IP
- eth1 had the vac subnet IP (192.168.114.9)
- Ran
sudo /sbin/ifdown eth0 then sudo /sbin/ifup eth0
- The I/F eth0 started running and c1vac became visible from martian
- Later checked the vacuum screen: The pressure values and valve statuses looked normal.
The interlock state was “running”. The system state was “unrecognized”.
End RTS recovery
- The end slow machines (auxex and auxey) were already running
- Restarting end RT models:
- c1iscey ->
rtcds start --all
- c1iscex ->
rtcds start --all
- Confirmed that the models can dump the SUSs
Vertex RTS recovery
- We wanted to use the reboot script. (
/opt/rtcds/caltech/c1/scripts/cds/rebootC1LSC.sh )
- c1susaux
- To be safe, we wanted to bring c1susaux first.
- c1susaux does not make the network I/Fs up automatically upon reboot.
-> Connect an LCD display / keyboard / mouse to c1susaux
-> Ran sudo /sbin/ifup eth0 and sudo /sbin/ifup eth1
- Now c1susaux is visible from martian.
- Login c1susaux and ran:
sudo systemctl start modbusIOC.service
-> c1susaux epics is up and running now
- ...Meanwhile c1susaux lost its eth1 somehow. This made the slow values of 8 vertex sus all zero
-> Ran sudo /sbin/ifdown eth1 and sudo /sbin/ifup eth1 again on c1susaux -> this resolved the issue
- c1psl
- Login c1psl and ran:
sudo systemctl start modbusIOC.service
-> c1psl epics is up and running now
- Prepared for the rebooting script
- Ran
/opt/rtcds/caltech/c1/scripts/cds/rebootC1LSC.sh
- Rebooting was done successfully. All the suspensions looked free and healthy.
- Burtrestored c1susaux (used Apr 12 21:19 snapshot)
Hardware
- PSL laser / Xend AUX laser / Yend AUX laser were off -> turned on
- The PMC was immediately automatically locked.
- The main marconi was off -> forgot to turn on
- The end temp controllers for the SHG crystals were on but not enabled -> now enabled
RTS recovery ~ part 2
- FB: FB status of all the RTS models were still red
- Timing: c1x01/2/3/5 were 1 sec behind of FB and c1x04 was 2 sec behind
- -> Remedy: https://nodus.ligo.caltech.edu:8081/40m/14349
- Software rebooting of FB
- Manually start the open-mx and mx services using
sudo systemctl start open-mx.service
sudo systemctl start mx.service
- Check that the system time returned by gpstime matches the gpstime reported by internet sources. e.g. http://leapsecond.com/java/gpsclock.htm
- Manually start the daqd processes using
sudo systemctl start daqd_*
- This made all the FB(FE) indicators green!
- Ran the reboot script again -> All green!
IMC recovery
- The IMC status was checked
- No autolocker, but it could be manually locked. i.e. MC1/2/3 were not so much misalignment
- Autolocker/Slow FSS recovery along with https://nodus.ligo.caltech.edu:8081/40m/15121
sudo systemctl start MCautolocker.service
sudo systemctl start FSSSlow.service
- Both of them failed to run
- Note by Gautam: The problem with the
systemctl commands failing was that the NFS mount points weren’t mounted. Which in turn was because of the familiar /etc/resolv.conf problem. I added chiara to the namespace in this file, and then manually mounted the NFS mount points. This fixed the problem.
Now the IMC is locked and the autolocker is left running.
Burt restore
- Used Apr 12 21:19 snapshot
- c1psl
- c1alsepics/c1assepics/c1asxepics/c1asyepics
- c1aux/c1auxex/c1auxey/
- c1iscaux/c1susaux
- This made REFL and AS beams back to the CCDs. As has small fringes.
- Y arm has small IR flashes as well as green flashes.
JETSTOR recovery
- JETSTOR was beeping.
- Shutdown megatron
- Followed the instruction https://nodus.ligo.caltech.edu:8081/40m/13107
- This stopped beeping. Waiting for JETSTOR to come up -> In a minute, JETSTOR display became normal and all disks showed green.
- Bring megatron back up again
N2 bottle
- The left N2 bottle was empty. The right one had 1500PSI.
- Replaced the left bottle with the spare one in the room.
- Now the left one 2680PSI and the right one 1400PSI.
Closing
- Closed PSL/AUX laser shutters
- Turned off the lights in the lab, CTRL room, and the office.
Remaining Issues
- [done] MCAutoLocker / FSSSlow scripts are not running
- The PRM alignment slider has no effect (although the PRM is aligned…) -> SLOW DAQ frozen???
JETSTOR is not mounted on megatron [gautam mounted Jetstor on megatron on 4/18 at 2pm]
|