40m
QIL
Cryo_Lab
CTN
SUS_Lab
TCS_Lab
OMC_Lab
CRIME_Lab
FEA
ENG_Labs
OptContFac
Mariner
WBEEShop
|
40m Log |
Not logged in |
 |
|
Sun Aug 5 13:28:43 2018, gautam, Update, CDS, c1lsc flaky
|
Mon Aug 6 00:26:21 2018, gautam, Update, CDS, More CDS woes
|
Mon Aug 6 14:38:38 2018, gautam, Update, CDS, More CDS woes 
|
Mon Aug 6 19:49:09 2018, gautam, Update, CDS, More CDS woes
|
Tue Aug 7 11:30:46 2018, gautam, Update, CDS, More CDS woes
|
Tue Aug 7 22:28:23 2018, gautam, Update, CDS, More CDS woes
|
Wed Aug 8 23:03:42 2018, gautam, Update, CDS, c1lsc model started
|
Thu Aug 9 12:31:13 2018, gautam, Update, CDS, CDS status update
|
Wed Aug 15 21:27:47 2018, gautam, Update, CDS, CDS status update
|
Tue Sep 4 10:14:11 2018, gautam, Update, CDS, CDS status update
|
Wed Sep 5 10:59:23 2018, wgautam, Update, CDS, CDS status update
|
Thu Sep 6 14:21:26 2018, gautam, Update, CDS, ADC replacement in c1lsc expansion chassis
|
Fri Sep 7 12:35:14 2018, gautam, Update, CDS, ADC replacement in c1lsc expansion chassis
|
Mon Sep 10 12:44:48 2018, Jon, Update, CDS, ADC replacement in c1lsc expansion chassis
|
Thu Sep 20 11:29:04 2018, gautam, Update, CDS, New PCIe fiber housed 
|
Thu Sep 20 16:19:04 2018, gautam, Update, CDS, New PCIe fiber install postponed to tomorrow
|
Fri Sep 21 16:46:38 2018, gautam, Update, CDS, New PCIe fiber installed and routed 
|
|
Message ID: 14194
Entry time: Thu Sep 6 14:21:26 2018
In reply to: 14193
Reply to this: 14195
14202
|
Author: |
gautam |
Type: |
Update |
Category: |
CDS |
Subject: |
ADC replacement in c1lsc expansion chassis |
|
|
Todd E. came by this morning and gave us (i) 1x new ADC card and (ii) 1x roll of 100m (2017 vintage) PCIe fiber. This afternoon, I replaced the old ADC card in the c1lsc expansion chassis, and have returned the old card to Todd. The PCIe fiber replacement is a more involved project (Steve is acquiring some protective tubing to route it from the FE in 1X6 to the expansion chassis in 1Y3), but hopefully the problem was the ADC card with red indicator light, and replacing it has solved the issue. CDS is back to what is now the nominal state (Attachment #1) and Yarm is locked for Jon to work on his IFOcoupling study. We will monitor the stability in the coming days.
Quote: |
(i) to replace the old generation ADC card in the expansion chassis which has a red indicator light always on and (ii) to replace the PCIe fiber (2010 make) running from the c1lsc front-end machine in 1X6 to the expansion chassis in 1Y3, as the manufacturer has suggested that pre-2012 versions of the fiber are prone to failure. We will do these opportunistically and see if there is any improvement in the situation.
|
|
|
|