40m
QIL
Cryo_Lab
CTN
SUS_Lab
TCS_Lab
OMC_Lab
CRIME_Lab
FEA
ENG_Labs
OptContFac
Mariner
WBEEShop
|
40m Log |
Not logged in |
 |
|
Fri Dec 8 23:31:31 2017, johannes, Frogs, ASS, c1ass slow channel offloading scripts with small
|
Wed Dec 13 09:49:23 2017, johannes, Update, ASS, wiring diagram
|
Thu Dec 14 00:32:56 2017, johannes, Update, ASS, Acromag new crate; c1auxex2 configured as gateway server for acromag 
|
Thu Dec 14 23:27:46 2017, johannes, Update, DAQ, aux chassis design   
|
Tue Jan 9 00:07:03 2018, johannes, Update, DAQ, etmx slow daq chassis
|
Wed Jan 10 22:24:28 2018, johannes, Update, DAQ, etmx slow daq chassis
|
Thu Jan 11 09:57:17 2018, Steve, Update, DAQ, acromag at ETMX
|
Thu Jan 11 20:59:41 2018, gautam, Update, DAQ, etmx slow daq chassis
|
Wed Jan 17 14:32:51 2018, gautam, Update, DAQ, Acromag checks
|
Wed Jan 17 22:44:14 2018, johannes, Update, DAQ, Acromag checks
|
Sun Jan 21 13:11:25 2018, johannes, Update, DAQ, Acromag checks
|
Fri Jan 12 10:02:05 2018, johannes, Update, DAQ, etmx slow daq chassis
|
Fri Jan 12 19:15:34 2018, johannes, Update, DAQ, etmx slow daq chassis
|
Wed Jan 24 18:12:31 2018, johannes, Update, DAQ, ETMX auxiliary DAQ work   
|
Wed Jan 24 19:17:06 2018, johannes, Update, DAQ, c1auxex2 startup behavior
|
Wed Jan 24 23:13:30 2018, johannes, Update, DAQ, c1auxex2 startup behavior
|
Thu Dec 14 19:33:20 2017, gautam, Frogs, ASS, c1ass slow channel offloading scripts with small
|
|
Message ID: 13537
Entry time: Fri Jan 12 10:02:05 2018
In reply to: 13529
Reply to this: 13543
|
Author: |
johannes |
Type: |
Update |
Category: |
DAQ |
Subject: |
etmx slow daq chassis |
|
|
Quote: |
There is some problem with the routing of the fast BIO channels through the new chassis - so the ANALOG de-whitening filter seems to be always engaged, despite our toggling the software BIO bits . Something must be wrongly wired, as we confirmed by returning only the FAST BIO wiring to the pre-acromag state (but everything else is now controlled by acromag) and didn't have the problem anymore. Or some electrical connection is not made (I had to use gender changers on these connectors due to lack of proper cabling)
The switches for the QPD gain stages did not work. I suspect a wiring problem, since the switching of the coil enables did work.
|
Both issues were fixed. In both cases it was two separate causes that prevented them from working.
The QPD gain stage switch software channels were assigned to wrong physical pins of the Acromag, and additionally their DSub cable was swapped with a different one.
The BIO switching had its signal and ground wires swapped on ALL connections, and part of it was also suffering from the cable-mixup.
Both issues were fixed. All backplane signals are now routed through the Acromag chassis.
Gautam and I did notice that occasionally ETMX alignment will start drifting as evident from the OpLev. I want to set up a diagnostic channel to see if the DAC voltages coming from the Acromag are responsible for this. |