40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Fri Nov 4 18:31:05 2016, Lydia, Update, CDS, c1auxex channels/pins for Acromag 
    Reply  Sat Nov 5 15:45:44 2016, rana, Update, CDS, c1auxex channels/pins for Acromag 
       Reply  Mon Nov 7 19:49:44 2016, Johannes, Update, CDS, acromag chassis hooked up to PSL acromag_chassis_location.jpgacromag_chassis_top_view.jpg
          Reply  Tue Nov 8 17:51:09 2016, Lydia, Update, CDS, acromag chassis hooked up to PSL 
             Reply  Mon Nov 21 19:54:13 2016, Johannes, Update, CDS, acromag chassis hooked up to PSL acromag_chassis.jpg
                Reply  Wed Nov 30 11:56:56 2016, Lydia, Update, CDS, Wiring for Acromag auxex replacement auxex_acromag.pdf
                   Reply  Wed Nov 30 14:54:01 2016, Johannes, Update, CDS, Slow machine replacement 
                      Reply  Wed Dec 14 19:16:57 2016, Lydia, Update, CDS, Acromag Binary I/O testing 
                         Reply  Tue Jan 31 22:15:02 2017, Johannes, Update, CDS, vme crate backplane adapter boards vme_backplane_conn_sketch.jpg
                            Reply  Tue Feb 7 19:14:59 2017, Johannes, Update, CDS, vme crate backplane adapter board layout vme_backplane.pdf
                               Reply  Wed Feb 15 00:26:44 2017, Johannes, Update, DAQ, panels and pcbs acromag_chassis_panel.pdfvme_backplane_panel.pdfrfAmp.pdf
                                  Reply  Wed Feb 15 09:06:13 2017, ericq, Update, DAQ, panels and pcbs 
                                     Reply  Wed Feb 15 22:21:12 2017, Lydia, Update, DAQ, panels and pcbs 
Message ID: 12649     Entry time: Wed Nov 30 11:56:56 2016     In reply to: 12632     Reply to this: 12651
Author: Lydia 
Type: Update 
Category: CDS 
Subject: Wiring for Acromag auxex replacement 

I've attached a schematic for how we will connect the Acromag mosules to the slow channel I/O curently going to c1auxex. The following changes are made:

  • We are getting rid of the slow readbacks from the Anti-Image and Oplev boards, as Rana says they are unnnecessary.
  • The whitening switching for the QPD is currently done by a Contec "fast" binary I/O module, but can be managed by acromag instead. This alllows CAB_1Y9_34 to  be fed directly into the Acromag box since all of its connections can now be managed slow. 
  • There's no need to change the PD whitening scheme around (since the signals never get huge), so we can set those to always be on and then lose those Contec channels. This means all of the necessary pins on CAB_1Y9_10 can go to Acromag. 
  • All the other backplane cables go the the fast machines only. 

 

Attachment 1: auxex_acromag.pdf  86 kB  | Hide | Hide all