Fri Nov 4 18:31:05 2016, Lydia, Update, CDS, c1auxex channels/pins for Acromag
|
Sat Nov 5 15:45:44 2016, rana, Update, CDS, c1auxex channels/pins for Acromag
|
Mon Nov 7 19:49:44 2016, Johannes, Update, CDS, acromag chassis hooked up to PSL 
|
Tue Nov 8 17:51:09 2016, Lydia, Update, CDS, acromag chassis hooked up to PSL
|
Mon Nov 21 19:54:13 2016, Johannes, Update, CDS, acromag chassis hooked up to PSL
|
Wed Nov 30 11:56:56 2016, Lydia, Update, CDS, Wiring for Acromag auxex replacement
|
Wed Nov 30 14:54:01 2016, Johannes, Update, CDS, Slow machine replacement
|
Wed Dec 14 19:16:57 2016, Lydia, Update, CDS, Acromag Binary I/O testing
|
Tue Jan 31 22:15:02 2017, Johannes, Update, CDS, vme crate backplane adapter boards
|
Tue Feb 7 19:14:59 2017, Johannes, Update, CDS, vme crate backplane adapter board layout
|
Wed Feb 15 00:26:44 2017, Johannes, Update, DAQ, panels and pcbs  
|
Wed Feb 15 09:06:13 2017, ericq, Update, DAQ, panels and pcbs
|
Wed Feb 15 22:21:12 2017, Lydia, Update, DAQ, panels and pcbs
|
|
Message ID: 12632
Entry time: Mon Nov 21 19:54:13 2016
In reply to: 12607
Reply to this: 12649
|
Author: |
Johannes |
Type: |
Update |
Category: |
CDS |
Subject: |
acromag chassis hooked up to PSL |
|
|
[Lydia, Johannes]
We connected and powered up the Acromag chassis today. It lives in 1X4 and is powered by the Sorensen +20V power supply in 1X5 via the fuse rail on the side of 1X4. For this we had to branch off the 20V path to the dewhitening and anti-image filter crate of the c1:susaux driven SOS optics. After confirming that none of the daughter modules in the crate draw from the 20V line, we added a wire leading to a new fuse we added for this unit and ran a power cable from there.
The diagnostic connector of the PSL laser is now connected to the unit and a tmux session was created on megatron that interfaces with the chassis and broadcasts the EPICS channels. We need to watch out in the coming days for epics freezes/outages, as in the past these seemed to occur around the same times we were toying with the Acromags.
Quote: |
We set up the chassis in 1X7 today. Steve is ordering a longer 25 pin cable to reach. Until then the PSL diagnostic channels will not be usable.
|
|
|
|