Message ID: 1258     Entry time: Thu Jan 29 16:50:53 2009
Author: josephb, alberto 
Type: Configuration 
Category: Computers 
Subject: Megatron fixed 
The warning light on megatron and the fans at full speed were fixed by not just power cycling, but completely unplugging megatron from power, waiting for a minute, and then reconnecting the power cables.

Apparently, the Sunfire X4600s at Hanford have also had intermittent problems, which required unplugging the machines completely. In their case, they were unable to access the machine normally, nor could they access the the Intergrated Lights Out Manager (ILOM).

Here, we could interact normally with megatron, but were unable to connect to the ILOM. We were able to get BIOS, but unable to change any of the setting for the ILOM connection. Since the ILOM is a seperate processor and effectively always on, even when the power light is off, a normal shutdown won't reset it. Hence the need to completely disconnect the power supply.