Message ID: 1083     Entry time: Fri Oct 24 11:21:26 2008
Author: pete 
Type: Configuration 
Category: PSL 
Subject: FSS LO input calibrated in dBm 
Based on the measurements described in my previous elog, I created a new calc record in the file /cvs/cds/caltech/target/c1psl/psl.db
grecord(calc, "C1:PSL-FSS_LOCALC")
{
        field(INPA,"C1:PSL-FSS_LODET")
        field(SCAN,".1 second")
        field(PREC,"4")
        field(CALC,"6.29*LOGE(A)+5.36")
}

After restarting scipe3 to load this change, I told C1PSL_FSS.adl to look at this record instead of *LODET. That MEDM screen now shows LO input calibrated in dBm.

For reference, the operators available for use in the CALC field are listed in the EPICS Record ref manual, Chapter 9. The manual can be found here:
http://www.aps.anl.gov/epics/EpicsDocumentation/AppDevManuals/RecordRef/Recordref-3.html

Yoichi said he was fixing an SVN problem, so I have not yet committed the two files I changed: /cvs/cds/caltech/target/c1psl/psl.db and /cvs/cds/caltech/medm/c1/psl/C1PSL_FSS.adl.