40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log, Page 336 of 339  Not logged in ELOG logo
ID Date Author Type Category Subjectup
  7605   Wed Oct 24 09:15:12 2012 SteveUpdateVACvacuum rack 24V ps was current limited

Quote:

Quote:

Quote:

Apparently all of the ION pump valves (VIPEE, VIPEV, VIPSV, VIPSE) opened, which vented the main volume up to 62 mTorr.  All of the annulus valves (VAVSE, VAVSV, VAVBS, VAVEV, VAVEE) also appeared to be open.  One of the roughing pumps was also turned on.  Other stuff we didn't notice?  Bad. 

 Several of the suspensions were kicked pretty hard (600+ mV on some sensors) as a result of this quick vent wind.  All of the suspensions are damped now, so it doesn't look like we suffered any damage to suspensions.

CLOSE CALL on the vacuum system:

Jamie and I disabled V1, VM2 and VM3 gate valves by disconnecting their 120V solenoid actuator before the swap of the VME crate.

The vacuum controller unexpectedly lost control over the swap as Jamie described it. We were lucky not to do any damage! The ion pumps were cold and clean. We have not used them for years so their outgassing possibly  accumulated to reach ~10-50 Torr

I disconnected_ immobilized and labelled the following 6 valves:  the 4 large ion pump gate valves and VC1,  VC2  of the cryo pump. Note: the valves on the cryo pump stayed closed. It is crucial that a warm cry pump is kept closed!

This will not allow the same thing to happen again and protect the IFO from warm cryo contamination.

The down side of this that the computer can not identify vacuum states any longer.

This vacuum system badly needs an upgrade. I will make a list.

 While I was doing the oil change of the roughing pumps I accidentally touched the 24 V adjustment knob on the power supply.

All valve closed to default condition. I realized that the current indicator was red at 0.2A  and the voltage fluctuated from 3-13V

Increased current limiter to 0.4A and set voltage to 24V     I think this was the reason for the caos of valve switching during the VME swap.

 

  5590   Fri Sep 30 18:35:42 2011 steve, kiwamuUpdateVACvacuum set for poweroutage

We did the following:

1, closed V1, VM1,  annuloses: VASE, VASV, VABS, VAEV,  VAEE and VA6

2, stop rotation of Maglev-TP1, waited to decellerate and turned off power to it

3, closed V4,  stoped rotation of TP2, waited to decellerate and turned power off

4, opened VM3 to RGA that is still running

 

I will come in tomorrow 9-10am to restart pumping.

  13245   Wed Aug 23 10:11:46 2017 SteveUpdateVACvacuum valve specifications

The V1 gate valve specs installed at 40m wiki page. VAT model number 10846-UE44-0007 Our main volume pumping goes through this 8" id gate valve V1 to Maglev turbo  or Cryo pump to  VC1

The ion pumps have 6" id gate valves:VAT 10844-UE44-AAY1,  Pneumatic actuator with position indicator and double acting solenoid valve 115V 60Hz  Purchased 1999 Dec 22

UHV gate valves 2.5" id. VAT  10836-UE44    Pneumatic actuator with position indicator and double acting solenoid valve 115V 60 hz, IFO to RGA  VM1 &  RGA to Maglev  VM2

mini UHV gate valve 1.5" id.   VAT  01032-UE01      2016 cataloge page 14,   manual - no position indicator, VM4  next to manual adjustable fine leak valve to RGA

UHV angle valve 1.5" id, model VAT 28432-GE41, Viton plate seal, pneumatic actuator with position indicator & solenoid valve 115V & single acting closing spring  MEDM screen: VM3,VC2, V3,V4,V5,V6,VA6,V7 & annuloses Each chamber annulos has 2 valves.

UHV angle valve 1.5" id, model VAT 57132-GE05   go page 208,   Metal tip seal, manual actuating only with position indicator,   MEDM screen: roughing RV1 and venting VV1 hand wheel needed to close to torque spec

UHV angle valve  1.5" id. model VAT 28432-GE01           Viton plate seal, manual operation only at IT gauges Hornet & Super Bee and  ion pumps roughing  ports. These are not labeled.

                                                      

The Cryo pump interlock wiring was added too

Note: all moving valve plate seals are single.

  4059   Wed Dec 15 16:04:49 2010 steveConfigurationVACvacuum valves found in default condition

This condition is created when we run out of nitrogen that holds the valves in set positions. The Maglev and other turbos are still running in this configuration so one has to pay attention that the foreline valves are open.

Reset  error message on vacuum screen and opened V4 & V5 at 3pm today.

  3009   Fri May 28 13:32:01 2010 alberto, kiwamuUpdateVACvacuum work

We started a vacuum work in this morning. And still it's going on.

 

Although the last night the green team replaced a steering mirror by an 80% reflector on the PLS table, the beam axis to the MC looks fine.

The MC refl beam successfully goes into the MCrefl PD, and we can see the MC flashing as usual.

We started measuring the distance of the optics inside the vacuum chamber, found the distance from MC3 to MMT1(curved mirror) is ~13cm shorter than the design.

We moved the positions of the flat mirror after the Faraday and the MMT1, but could not track the beam very well because we did not completely lock the MC.

Now we are trying to get the lock of the MC by steering the MC mirrors.

 

P.S.

Kevin suceeded in locking it !!

  3010   Fri May 28 13:51:51 2010 JenneUpdateVACvacuum work

Quote:

We started a vacuum work in this morning. And still it's going on.

 

Although the last night the green team replaced a steering mirror by an 80% reflector on the PLS table, the beam axis to the MC looks fine.

The MC refl beam successfully goes into the MCrefl PD, and we can see the MC flashing as usual.

We started measuring the distance of the optics inside the vacuum chamber, found the distance from MC3 to MMT1(curved mirror) is ~13cm shorter than the design.

We moved the positions of the flat mirror after the Faraday and the MMT1, but could not track the beam very well because we did not completely lock the MC.

Now we are trying to get the lock of the MC by steering the MC mirrors.

 

 

 Hey guys,

I just finished redoing the calc based on the measurements that happened last week.  Using the average of the Vert and Horz measurements in Kevin's elog 2986, I find that we need to make the MMT telescope ~8cm longer.  So, can you please place the flat mirror after the Faraday in the same place as the drawing, but move the MMT1 79mm farther away from that flat mirror?  Looking at the table layouts that Koji has on the wiki, this should still (barely) fit.

New distances:

d2a = 884.0mm (no change) ------  MC3 to Flat after Faraday

d2b = 1123.2mm (move MMT1 farther toward center of BS table)  -------- Flat after Faraday (SM1) to MMT1

d3 = 1955.0mm (result of moving MMT1)  ---------  MMT1 to MMT2

d4a = 1007.9mm (no chnage)        ----------- MMT2 to SM2

d4b = 495.6mm (no change) ------------ SM2 to PRM

  3011   Fri May 28 14:24:30 2010 JenneUpdateVACvacuum work

I just got off the phone with Alberto and Kiwamu, and I'm going to try to recalculate things based on their measurements of the distances between MC3 and SM1.  It sounds like the CAD drawings we have aren't totally correct.    I know that when we opened doors just before Christmas we measured the distances between the BS table and the ITM tables, but I don't think we measured the distance between the IOO table and the BS table.  Hopefully we can fit everything in our chambers.....

  2613   Thu Feb 18 15:39:16 2010 Koji and SteveConfigurationVACvalve condition: ALL OFF

As preparation for the upcoming planned power outage we turned turbos, RGA off and closed valves.

IFO chamber is not pumped now. Small leaks and out gassing will push the pressure up slowly. At 3 mTorr of P1 the PSL output shutter

will be closed by the interlock.

It is OK to use light in the IFO up to this point.

  5104   Wed Aug 3 09:40:13 2011 steveUpdateVACvent

The vacuum system is coming up to atm. The vent was started with slow N2 flow. The PSL output is blocked 2 places on the table.

  44   Thu Nov 1 09:17:27 2007 steveRoutineVACvent 64
Yesterday before vent I could not lock MC, therfore I could not measure the
transmitted power at MC2
The vent went well. We had lots of help.

We could not find the Nikon D40
PLEASE BORROW THINGS when taking them away
and bring them back promtly.

The laser was turned off for better visibility.

I see clean room frorks laying around here and there.
Please put them away so we do not carry excess particles into the chamber.
  10559   Thu Oct 2 09:23:23 2014 SteveUpdateVACvent 77

Quote:

 

 Pump down reached "vacuum normal" state. IFO _P1 pressure 1e-4 torr

PSL shutter is opened.

 IFO_P1 pressure 1.6e-5 torr after 6 days at atm

 

PS: PSL sliding door 11 was left open overnight. The PSL particle count will reach room counts in 20 seconds at low speed of HEPA

  12237   Fri Jul 1 09:20:44 2016 SteveUpdateVACvent 78

  VENT OBJECTIVES:

1, Fix ETMX sus "jump issue"

2, First Contact clean the arms

3, Install new spare cold cathode and convectron gauges: InstruTech-Hornet

4, Install 50 mm apeture beam baffles

5, Check and clean optical quality viewport from inside

 

The following bullets were executed:

  • Closed shutter of PSL-IR and green shutters at the ends 
  • Checked jam nuts are protecting bellows 
  • Check crane functionality & cleanliness last week

  • Particle count must be under 10,000 counts / cf min for 0.5 micron 
  • Checked all metal window covers are on. 
  • Check 5 cylinders (24 cft size) of instrument grade air, called Alfa Gas 1 in stock.
  • Took pictures of medm screens: sus-sum, aligned oplevs pos, alignment values and vac configuration
  • Turned Oplev servos off
  • Closed V1 and VM1, opened VM2
  • Opened VV1 manual valve to Nitrogen cylinder and let the P1 to rise to 25 Torr
  • Switched over to Instrument Grade Air Cylinder and continoed the vent with 8-10 PSI reading at the pressure regulator

We are venting the 40m IFO

     

Quote:

Steve has ordered some teflon parts to take the place of the metal parts in his acetone-soaking jig. They should arrive tomorrow. 

So, we will be begin the venting process tomorrow. Doors to come off on Tuesday.

 

  12314   Wed Jul 20 11:39:07 2016 SteveUpdateVACvent 78 day 20

RGA background scan

Quote:

Vacuum Status: Chamber Open

All chamber annuloses are vented.  Vac Monitor screen is not communicating with gauges. The valve position indicator are working.

RGA is pumped by Maglev through VM2

 

 

  12383   Mon Aug 8 10:35:12 2016 SteveUpdatePEMvent 78 day 38

 

Quote:

RGA background scan

Quote:

Vacuum Status: Chamber Open

All chamber annuloses are vented.  Vac Monitor screen is not communicating with gauges. The valve position indicator are working.

RGA is pumped by Maglev through VM2

 

 

 

  12250   Wed Jul 6 10:58:07 2016 SteveUpdateVACvent 78 valve configuration

Vacuum Status: Chamber Open

All chamber annuloses are vented.  Vac Monitor screen is not communicating with gauges. The valve position indicator are working.

RGA is pumped by Maglev through VM2

 

  12238   Fri Jul 1 15:48:10 2016 SteveUpdateVACvent 78 at 710 Torr

I just disconnected the 6th instrument grade air cylinder from the vacuum envelope at 720 Torr. Now it will reach equilibrium through a filter as it sucks in lab air.

This is the sure way not to over pressurize the chamber.

 

  12559   Thu Oct 13 16:48:34 2016 SteveUpdateVACvent 79 is completed

IFO is at atmosphere. The MC can be locked in air now.

The doors will be coming off tomorrow 8am sharp.

Do we want to install the ITM baffles?

What about the found OSEM filters?

 

  12557   Thu Oct 13 09:30:38 2016 SteveUpdateGeneralvent 79 is happening
Quote:

I have completed the following non-Steve portions of the pre-vent checklist [wiki-40m.ligo.caltech.edu]

  • Center all oplevs, transom QPDs (and IPPOS + IPANG if they are set up)
  • Align the arm cavities for IR and align the green lasers to the arms.
  • Update the SUS Driftmon values
  • Reconcile all SDF differences
  • Reduce input power to no more than 100mW (measured at the PSL shutter) by adjusting wave plate+PBS setup on the PSL table BEFORE the PMC. (Using the WP + PBS that already exist after the laser.)
  • Replace 10% BS before MC REFL PD with Y1 mirror and lock MC at low power.
  • Close shutter of PSL-IR and green shutters at the ends

All shutters are closed. Ready for Steve to check nuts and begin venting!

- checked all jam nuts

- checked all viewports are covered

- turned oplev servos off

- took pictures of medm screens: sus summs, aligned oplev centering, IFO& MC alignment biases and vac configuration

- checked particle counts

- checked crane operational safety

- closed V1, VM1, annuloses

- opened VV1  and vented with Airgas brand, Industrial Grade Nitrogen [ 99.99% ] to 25 Torr

- switched over to Airgas brand compressed air, Alphagas " AI UZ300 "  with Total Hydro Carbon 0.1 PPM

  10536   Thu Sep 25 08:21:15 2014 SteveUpdateVACvent day 1

Quote:

[Steve, EricQ, Jenne]

ITMY and BS heavy doors are off, light doors are on.  Q is aligning the IFO.

 

  10542   Fri Sep 26 09:13:17 2014 SteveUpdateSUSvent day 2

 ITMY in vac table needs leveling.

  7594   Tue Oct 23 08:45:00 2012 SteveUpdateVACvent day 3

Quote:

Quote:

Quote:

Quote:

 

 PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now.  Jenne is taking over here.

 Valves closed, 500 torr.  Steve will finish off Monday morning, then we'll take off doors and get to work.

 We are almost at atm.  P1 750 Torr,  We are slowly reaching equilibrium.

 The access connector was removed, BS and ITMY chambers were opened yesterday.

New one piece aluminum shell access connector installed. Jenne lowered the PSL out put into MC to ~100mW

  10547   Mon Sep 29 09:11:25 2014 SteveUpdateVACvent day 5 RGA scan

 

 

  2635   Tue Feb 23 19:00:45 2010 kiwamuConfigurationVACvent finished

The vent has been finished.

Now the pressure inside the chamber is 760 torr, and it's getting equilibrium with the atmospheric pressure.

Therefore we are ready and can open the door of the chamber tomorrow.

  3259   Wed Jul 21 12:41:31 2010 kiwamuUpdateVACvent finished

The vent has been finished successfully in this morning.

The vent was finished successfully this morning.

  3266   Thu Jul 22 08:07:27 2010 steveUpdateVACvent finished

Quote:

The vent has been finished successfully in this morning.

The vent was finished successfully this morning.

 Thanks to Kiwamu, Alberto and Koji

  6889   Thu Jun 28 20:59:28 2012 yutaBureaucracyLockingvent for PRC check, TOMORROW!

Koji, Jamie and I talked together and I decided to VENT TOMORROW MORNING. Main purpose of this vent is to see if PRM is flipped or not.

Vent schedule:
June 28 (Thu)
  Prepare for the vent tonight

June 29 (Fri)
  Start vent in the morning
  Look into PRC in the evening. If PRM was flipped, we will correct them. We'll use REFL to align the PRM. If PRM was not flipped, look into PR2,PR3 and other related optics.

June 30 (Sat)
July 1 (Sun)
  Thinking time. I can work if needed.

July 2 (Mon)
  If we need something else to do, do it.
  If not, start pumping.
  July 4th is the Independence Day. So, I need IFO working before July 4th.

Check List:
 We will just open the BS chamber.
  - PRM flipping
  - PR2, PR3 flipping
  - PRC suspensions
  - Cipping check in PRC

  6890   Thu Jun 28 22:08:57 2012 JenneBureaucracyLockingvent for PRC check, TOMORROW!

Quote:

Check List:
 We will just open the BS chamber.
  - PRM flipping
  - PR2, PR3 flipping
  - PRC suspensions
  - Cipping check in PRC

 What do you mean by PR2, PR3 flipping?  They are (supposed to be) flat mirrors, so obviously they should be installed correctly, but they won't change the mode matching in a huge way if they're backwards, right?

For the PRM, I recommend checking (a) the arrow inscribed on the thinner side of the optic and (b) that the arrow *actually* points to the HR side.  I'm pretty sure I installed all the optics with the arrow pointing away from the OSEMs, but I never did a thorough check that the arrow always actually pointed to the HR coated side.  I don't remember any optics where I said "hmmm, that's funny, the arrow is pointing backwards", but nor did I write down that I had checked.

Also, hopefully the PRM is correct.  If however it's not, that means that all of the magnets are glued onto the HR side, and we'll have to redo all of the magnet gluing.  The guiderods should be fine, but all 6 magnets would need redoing.  If we were very, very careful and didn't break any of the magnets off of the dumbbells, it's a 24 hour turnaround due to drying time.  Since inevitably we break magnets away from dumbbells, conservatively we should think about a 48 hour turnaround. 

  6891   Fri Jun 29 01:49:36 2012 yutaBureaucracyLockingvent for PRC check, TOMORROW!

Quote:

 What do you mean by PR2, PR3 flipping?  They are (supposed to be) flat mirrors, so obviously they should be installed correctly, but they won't change the mode matching in a huge way if they're backwards, right?

We see some ghost beam spots at POP. This may come from the back of PR2 and PR3. Also, they may change mode matching because of thermal lensing, mirror deformation, and other unexpected reasons. I thought we should check every mirrors in PRC, if PRM is not flipped.

We are going to check PRM just because we spent so much time for the PRC problem, and still don't have the solution or evidence.
PRM flipping is kind of the only idea for the root of all evil -- terrible beam shape, low PR gain, unstable PRMI lock.
So, I want to check with my eye during the stay.

I don't think we have to redo magnet gluing. It's okay to leave them on HR side.

  7849   Tue Dec 18 10:43:20 2012 SteveUpdateVACvent has completed

 The 40m vacuum envelope is at atm    It took 4.5 hours at ~3 Torr/min speed. Atm1

 

What I did:

Turned PZT voltages off: 84.1V at OMC-rack location

                                           -  99V at 1Y3 location as PZT_pitch,

                                             56.6V KEPCO at 1Y3 location as PZT_yaw                                           

Took screen shuts of SUS_SUMMARY, yesterday,  Atm3

Turned off OPLEV _SERVOs, today , Atm2

Closed PSL_SHUTTER and green shutters at the ends

 

Set vacuum valves for vent position and opened VM2 for the RGA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  7582   Fri Oct 19 16:45:39 2012 SteveUpdateVACvent has started

Quote:

 

 VENT NOW and FIX ALIGNMENT!

 PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now.  Jenne is taking over here.

  7584   Fri Oct 19 19:26:42 2012 JenneUpdateVACvent has started

Quote:

Quote:

 

 PSL shutter closed, manual block in place, HV turned off. P1 is at 200 Torr now.  Jenne is taking over here.

 Valves closed, 500 torr.  Steve will finish off Monday morning, then we'll take off doors and get to work.

  5111   Wed Aug 3 16:18:30 2011 steveUpdateVACvent is almost finished

P1 at 750 Torr,  Vent valve VV1 is left open to atm. It will reach equilibrium in an hour. The PSL power is not turned down yet. The beam path is blocked at two places inside the enclosure.

The low power 20 mW  input  MC can be locked tonight.

 

Next day's - Thursday notes:

We  reached 760 Torr of atm in 8 hrs at  1.7 Torr/ min with 5 cylinders of  instrument grade air.

Used 500 PSI of nitrogen to get to 20 Torr at first.  This flow  and the first cylinder of N2  has to be slower next time.

 

We did the following:

1, oplevs were centered on locked caveties 2 days ago

2, just before vent we rechecked arms  pointing, they wre still locking

3,eloged strain gages  and turned HVs off at PZT-steering   at 1Y3 rack and OMC-PZT ps at 1X2 aux rack. They were actually off.

4,,checked jam nuts 6 places x 3

5, turned oplev servos off

6, eloged SUS summery page

7, checked particle counts at ITMY: 1 micron 300,  0.5 micron 3K,  0.3 micron  30K particles / cft-min. All three cranes were wiped 2 days ago.

8, blocked laser into IFO: main 1064 in 1.25W were blocked by manual 2 blocks on PSL table. The PSL output shutter was left open to be triggered by interlock  at P1 3 mTorr. It did!

    Aux NPRO-AP and green light  input at both ends were blocked.

  2636   Tue Feb 23 19:07:43 2010 kiwamu and steveConfigurationVACvent is completed

Quote:

Kiwamu and Steve have started venting the 40m vacuum envelope.

Preparation:

centered oplevs at resonating cavities,

ITM references were set by green pointer from the ends by Koji,

closed  PSL shutter and placed manual block into beam path,

checked  jamnuts in locked positions on bellows,

turned  HV off at PZT-Jena "steering mirror" power supply and OMC HV ps

checked  particle counts,

switched oplev servos off,

set up N2 cylinder to start vent from 1e-6 Torr to 25 Torr,

have ~ 6 cylinders of instrument grade compressed air to bring envelope from 25 Torr to 760 Torr

 

All three cranes were wiped off today.

 

 Kiwamu has completed the vent.

  10532   Wed Sep 24 13:28:48 2014 SteveUpdateVACvent is completed

 The vent is completed. ITMX was kicked up accidentally. Valve configuration: chamber open, RGA is pumped through VM2  Maglev

  10533   Wed Sep 24 16:02:58 2014 JenneUpdateVACvent is completed

[Steve, EricQ, Jenne]

ITMY and BS heavy doors are off, light doors are on.  Q is aligning the IFO.

  5698   Wed Oct 19 14:03:41 2011 kiwamuUpdateGeneralvent prep : dichroic mirrors

Status update on dichroic mirror:

 I got the specification sheet of an aLIGO 2" dichroic mirror from Lisa.

https://dcc.ligo.org/cgi-bin/private/DocDB/ShowDocument?docid=25232

This is the one from ATF. It has low loss, a high R for 1064 nm and high T for 532 nm. So it matches our needs.

Based on this sheet we may reset some of the parameters in the specification (e.g. incident angle and etc.,) and will get a quote from ATF.

We will buy 3 of them, including 1 spare. First I need to review the specification.

  7249   Wed Aug 22 15:47:34 2012 jamieSummaryGeneralvent prepartion for fast-track vent

We are discussing venting first thing next week, with the goal of
diagnosing what's going on in the PRC.

Reminder of the overall vent plan:

https://wiki-40m.ligo.caltech.edu/vent

Since we won't be prepared for tip-tilt installation (item 2), we should
focus most of the effort on diagnosing what's going on in the PRC.  Of
the other planned activities:

(1) dichroic mirror replacement for PR3 and SR3

  Given that we'll be working on the PRC, we might consider going ahead
  with this replacement, especially if the folding mirror becomes
  suspect for whatever reason.  In any case we should have the new
  mirrors ready to install, which means we should get the phase map
  measurements asap.

(3) black glass beam dumps:

  Install as time and manpower permits.  We need to make sure all needed
  components are baked and ready to install.

(4) OSEM mount screws:

  Delay until next vent.

(5) new periscope plate:

  Delay until next vent.

(6) cavity scattering measurement setup

  Delay until next vent.

  7255   Thu Aug 23 10:38:12 2012 SteveUpdateGeneralvent prepartion for fast-track vent

Quote:

We are discussing venting first thing next week, with the goal of
diagnosing what's going on in the PRC.

Reminder of the overall vent plan:

https://wiki-40m.ligo.caltech.edu/vent

Since we won't be prepared for tip-tilt installation (item 2), we should
focus most of the effort on diagnosing what's going on in the PRC.  Of
the other planned activities:

(1) dichroic mirror replacement for PR3 and SR3

  Given that we'll be working on the PRC, we might consider going ahead
  with this replacement, especially if the folding mirror becomes
  suspect for whatever reason.  In any case we should have the new
  mirrors ready to install, which means we should get the phase map
  measurements asap.

(3) black glass beam dumps:

  Install as time and manpower permits.  We need to make sure all needed
  components are baked and ready to install.

(4) OSEM mount screws:

  Delay until next vent.

(5) new periscope plate:

  Delay until next vent.

(6) cavity scattering measurement setup

  Delay until next vent.

 Bob is back. Cleaning and baking all our posts and clamps. They will be ready for use Tuesday next week. Therefore beam dumps will be available for installation.

  7558   Tue Oct 16 16:46:20 2012 Vent Czar and CzarinaSummaryGeneralvent stuff

We're discussing the plan for the next vent.  Now that we have all the tip-tilt stuff in hand, we should get ready for the big TT installation vent ASAP.  The question is what remains to be done, and when can we be ready

Stuff that needs doing:

* characterize TTs, check electrical connection of quadrupus cables, bake cables and base plates - a week or so (not including baking)

* phase map of LaserOptik mirrors (decide on needed resolution) - a week or so?

* get ready to swap G&H mirrors with LaserOptik mirrors (PR2, PR3, SR2, SR3)

* assembly of black glass beam dumps - one afternoon

* green periscope moving - day or so to make sure greens are resonant in arms, so we have something to align to

* redraw of REFL path?? (rotate 2nd refl mirror to reflect beam to the east, then add mirror to get beam out of IOO chamber viewport), cut hole in BS oplev table's box, install black beam tube

* FI camera mount - make sure it's here, baked

* active TT pitch damping plan

* passive TT weight addition and pitch alignment plan

* camera plan for taking in-chamber photos without touching the tables

* look at layout of ITMY table.  POY pick-off too close to main beam.  Can we move POY pick-off to BS table?

* remount black glass baffles on SOS cages.

 

Stuff to bake:

* Quadrupus cables

* TT base plates

* FI mirror mount for FI camera

* stuff to add to active TTs

* stuff to add to passive TTs

 

  7560   Tue Oct 16 17:13:23 2012 CzarinaSummaryGeneralvent stuff - 4 paths

I see 4+ possible paths for us to take, in terms of a possible vent in the next few weeks:

No Vent - Just do FPPRMI, using AS55

Mini Vent - Fix REFL path, nothing else.  ~1 day at atmosphere

Medium Vent - Fix REFL path, swap G&H mirrors for LaserOptik mirrors (so also resuspend passive TTs, maybe add pitch adjustment option). ~1 week or so at atmosphere - do this rather than Mini if Jan's Finesse calc says the G&H mirrors are too rough

Mega Vent - Fix all the things, do all the things.  Long time at atmosphere

The "+" is to take into account all the possible variations on "medium vent".  The No, Mini and Medium options assume we'll do the Mega option later, just not immediately.

  66   Tue Nov 6 09:45:22 2007 steveSummarySUSvent sus trend
The mc optics dragwippings were done by locking optics by eq stops and rotating-moving
cages so access were good. This technic worked well with mc1 & mc2
MC3 osems were reoriented only.
  2631   Tue Feb 23 13:37:04 2010 kiwamu and steveConfigurationVACventing the 40m vac envelope

Kiwamu and Steve have started venting the 40m vacuum envelope.

Preparation:

centered oplevs at resonating cavities,

ITM references were set by green pointer from the ends by Koji,

closed  PSL shutter and placed manual block into beam path,

checked  jamnuts in locked positions on bellows,

turned  HV off at PZT-Jena "steering mirror" power supply and OMC HV ps

checked  particle counts,

switched oplev servos off,

set up N2 cylinder to start vent from 1e-6 Torr to 25 Torr,

have ~ 6 cylinders of instrument grade compressed air to bring envelope from 25 Torr to 760 Torr

 

All three cranes were wiped off today.

 

  3616   Tue Sep 28 14:12:14 2010 steveUpdateGeneralvertex crane drive is out of order

The vertex crane drive is overheating, it stopped functioning. Service man will be here tomorrow morning.

I crane was just turned  on for for may be  about 5 minutes. The vertical drive was fine for a while, but the horizontal did not worked at all.

The crane is tagged out again and the controller box is cooling down.

  9146   Fri Sep 20 16:37:30 2013 SteveUpdateVACvertex crane folding arm is back on

Quote:

 The folding beam removed as shown. Two man supporting it while I hammering it out. Pin was dry and it gulled into supporting hinges.

The rotating hinge will be machined and bushing will be added with Zerk fitting or similar. This will allow lubrication in the future.

 see elog #9111

Atm1,  The folding arm is back on with 0.1" misalignment at no load in the trolly's way. The other side of the I beam is 0.02" higher than the main beam.. New bushing and pin were greased up  with Krytox before installation.

The axial Zerk 1/8" pipe in the pin upper end can not take any fitting. There is no room. It is taped off.

This gap comes down to ~ 1/16" at fully extended arm with 225 lbs load at the end of it.

The present plan is to grind down the  the misalignment of 0.1"  for a slow-loaded trolly.

Steve Baker of Konacranes will be back to grind down this ridge and load test at 500 lbs on Tuesday,  OCT  1, 2013

 

 

 

  9139   Wed Sep 18 14:57:12 2013 SteveUpdateVACvertex crane folding arm removed

 The folding beam removed as shown. Two man supporting it while I hammering it out. Pin was dry and it gulled into supporting hinges.

The rotating hinge will be machined and bushing will be added with Zerk fitting or similar. This will allow lubrication in the future.

 see elog #9111

  9111   Thu Sep 5 10:47:58 2013 SteveUpdateVACvertex crane folding issue

 

 [Fred Goldbar, Mike Gerfen, Dennis Coyne and Steve]

We inspected the hinge, 1.25" cross pin and I-beams. It is hard to explain what is  causing the folding I-beam corner to jam against the main I-beam.

To limit the motion of the folding I-beam  cross pin bushing will be added. This will take a week to complete.

 

 

 

 

 

  9185   Wed Oct 2 14:25:39 2013 SteveUpdateVACvertex crane is still out of order

 

The smoke alarms were turned off and surrounding areas were covered with plastic.

The folding I-beam was ground down to be in level with the main beam.

Load bearing cable moved into correct position. New folding spring installed.

Crane calibration was done at 500 lbs at the end of the fully extended jib.

Than we realized that the rotating wheel limit switch stopped working.

This means that the crane is still out of order.

 

  9372   Wed Nov 13 08:46:03 2013 SteveUpdateVACvertex crane repair completed

nullQuote:

 

The smoke alarms were turned off and surrounding areas were covered with plastic.

The folding I-beam was ground down to be in level with the main beam.

Load bearing cable moved into correct position. New folding spring installed.

Crane calibration was done at 500 lbs at the end of the fully extended jib.

Than we realized that the rotating wheel limit switch stopped working.

This means that the crane is still out of order.

 

New limit switch installed and tested. The crane is back in full operational mode. Two spare limit switches on hand.

  9117   Mon Sep 9 15:33:06 2013 SteveUpdateVACvertex crane repair is scheduled

Quote:

 

 [Fred Goldbar, Mike Gerfen, Dennis Coyne and Steve]

We inspected the hinge, 1.25" cross pin and I-beams. It is hard to explain what is  causing the folding I-beam corner to jam against the main I-beam.

To limit the motion of the folding I-beam  cross pin bushing will be added. This will take a week to complete.

 

 

 

 

 

 KoneCrane contact John McDaniel (562) 903 - 1371,

Wednesday, September 18,  folding I-beam will be removed.  KoneCrane will start working at 7:30am and they should be out by 12:30pm

 Friday,  September 20, reinstalling machined hinge on the I-beam. Same timing schedule as Wednesday.

  9173   Mon Sep 30 08:53:22 2013 SteveUpdateVACvertex crane repair schedule has changed

Quote:

Quote:

 The folding beam removed as shown. Two man supporting it while I hammering it out. Pin was dry and it gulled into supporting hinges.

The rotating hinge will be machined and bushing will be added with Zerk fitting or similar. This will allow lubrication in the future.

 see elog #9111

Atm1,  The folding arm is back on with 0.1" misalignment at no load in the trolly's way. The other side of the I beam is 0.02" higher than the main beam.. New bushing and pin were greased up  with Krytox before installation.

The axial Zerk 1/8" pipe in the pin upper end can not take any fitting. There is no room. It is taped off.

This gap comes down to ~ 1/16" at fully extended arm with 225 lbs load at the end of it.

The present plan is to grind down the  the misalignment of 0.1"  for a slow-loaded trolly.

Steve Baker of Konecranes will be back to grind down this ridge and load test at 500 lbs on Tuesday,  OCT  1, 2013

 

 

 

 Konecranes rescheduled the completion of the Vertex crane to Wednesday, Oct. 2

ELOG V3.1.3-