JC | Configuration | General | LED Instead of Incandescent Lights |
Electrical came by today to see the lights. The issue may be the switches, but they will come by tomorrow to solve the issue. A couple light bulbs were noticed to be out, but they no longer have incandescent lights. . . only LED. I figured this would be preffered because of the reduction on noise. I would prefer to go ahead and ask to change all the incandescent bulbs to LED bulbs. Are there any objections to this? |
17323
|
Wed Nov 30 10:48:10 2022 |
JC | Configuration | General | LED Instead of Incandescent Lights |
All incondescent lightsbulbs have been switched over to LED.
Quote: |
Electrical came by today to see the lights. The issue may be the switches, but they will come by tomorrow to solve the issue. A couple light bulbs were noticed to be out, but they no longer have incandescent lights. . . only LED. I figured this would be preffered because of the reduction on noise. I would prefer to go ahead and ask to change all the incandescent bulbs to LED bulbs. Are there any objections to this?
|
|
17370
|
Wed Dec 21 12:35:49 2022 |
Chris | Configuration | CDS | Timing trigger test |
While recovering from the power outage, I took the opportunity to try having the timing system trigger on the rising edge of the 1 PPS signal from the GPS receiver (rather than the falling edge, as it had been doing since before the CDS upgrade). This was done in order to eliminate a timing offset between the clock used by the ADCs and the IRIG-B timestamps from the Spectracom boards. It was successful in that regard, and cleared the timing errors seen in the IOP statewords on most of the front ends.
The two exceptions were c1lsc and c1sus, where something is broken with the DuoTone readbacks. The attached plot shows the DuoTone signal in the last channel of ADC 0 on c1x01 (working normally) vs c1x02 and c1x04 (busted).
However, this change apparently also had some unexplained effect on the way the c1sbr model runs. There were frequent CPU time overruns and IPC errors. So on Sunday afternoon I reverted to the falling-edge trigger. This caused the timing errors to return, but allowed c1sbr to run normally. |
Attachment 1: duotone.png
|
|
17385
|
Wed Jan 4 15:10:19 2023 |
Koji | Configuration | CDS | unknown dhcp request to fb1 |
Jamie reported that:
The logs (/var/log/daemon.log) on fb1 are filling with this line:
Jan 03 14:11:51 fb1 dhcpd[1152]: DHCPDISCOVER from 3c:ec:ef:c8:44:78 via enp3s0: network 10.0.113.0/24: no free leases
It seems that some machine on the network is trying to get an IP address but can't
- The MAC address 3c:ec:ef:xx:xx:xx indicates this is one of the supermicro units.
- The IP address indicates this is on the DAQ network which fb1 is spanning.
- There is a switch for this DAQ network.
- There are 8 machines connected to the switch. fb1 is via optical, and the other 7 have yellow ethernet cables (Attachment 1).
- fb1 and other 6 RT machines already have 10.0.113.x assigned.
- The rest is c1shimmer. I can't ssh into it from martian. KVM on rack 1X7 shows a black screen assuming 1-7 is c1shimmer. I wonder what's the status of this machine, but left untouched so far.
|
Attachment 1: PXL_20230104_233907953.jpg
|
|
17386
|
Wed Jan 4 17:15:41 2023 |
Koji | Configuration | CDS | unknown dhcp request to fb1 |
The dhcpd error on the log file stopped when the yellow (DAQ) ethernet cable was removed. With Chris's permission I left it unconnected (Attachment 1).
Chris pinted that the IPMI on c1shimmer is supposed to be exposed to 192.168.113. net rather than DAQ net.
From dhcpd.conf on chiara:
host c1shimmer-ipmi {
hardware ethernet 3c:ec:ef:c8:44:78;
fixed-address 192.168.113.37;
}
So the ethernet connections of c1shimmer is still questionable. The next person to work with c1shimmer needs to check them.
This would also be related?
https://lanforge.wordpress.com/2015/11/10/turning-off-ipmi-dhcp/ |
Attachment 1: PXL_20230104_233926284.MP.jpg
|
|
17484
|
Sun Feb 26 00:13:55 2023 |
Alex | Configuration | ASC | IOO MC PIT/YAW gain change |
The following changes were made to the WFS MASTER IMC Pitch and Yaw gains:
Gain values for the pitch and yaw on MC1, MC2, and MC3 filters on the SUS ASC inputs have been carried over to the WFS MASTER output filters.
This was done such that Tomohiro and I could take AC measurements at an oscillation freq of 77 Hz on the pitch and yaw mirrors, while being sure that the amplitude of the AC signal being applied to each mirror is the same. The filters on the WFS output will have gains changed from 1.0 to the previously mentioned calibration values described in ELOG 17481.
The values calculated for each filter were inverses of the callibration constants. The filters at the SUS ASC inputs were modified to read gain values of 1.0 again.
See the table bellow for the values passed to each filter.
In summary:
originally IOO-MC1,2,3_PIT/YAW_GAIN = 1.0. Now:
MC1,2,3_ASCPIT/ASCYAW_GAIN >> IOO-MC1,2,3_PIT/YAW_GAIN
IOO-MC1,2,3_PIT/YAW_GAIN >> 1.0 |
17492
|
Sat Mar 4 18:57:18 2023 |
Paco | Configuration | Calibration | FPMI DARM calibration run |
Locked FPMI, measured DARM and CARM OLTFs, locked YAUX and measured the analog loop TF at the cal line frequencies. Turned the cal lines on with the new filters Anchal added on MC2 (ResGain within and Notches outside the CARM bandwidth which is set to 200 Hz), and hope to get 3600 seconds of data this evening. Log and measurement data are saved under /opt/rtcds/caltech/c1/Git/40m/scripts/CAL/FPMI |
17499
|
Wed Mar 8 18:32:22 2023 |
Anchal | Configuration | Calibration | FPMI DARM calibration run set to happen at 1 am |
On rossa in tmux session name FPMI_DARM_Cal, a script is running to take FPMI DARM calibration data at 1:00 am on March 9th. Please do not disturb the experiment untill 6 am. To stop the script do following on rossa:
tmux a -t FPMI_DARM_Cal
ctrl-C
The script will lock both arms, run ASS, then lock FPMI, then tune beatnote frequency with Y AUX laser to around 40 MHz, set phase tracked UGF to 2 kHz, clear phase history, take OLTF of DARM from 2 kHz to 10 Hz, take OLTF of CARM and AUX loop at calibration line frequencies, turn on the calibration lines, and wait for FPMI to unlock or 5 hours to pass, whatever happens first. At the end it will turn off the calibration lines. |
17502
|
Thu Mar 9 19:20:44 2023 |
Anchal | Configuration | Calibration | FPMI DARM calibration run set to happen at 1 am |
Running this test again tonight. Will probably run it every night now.
|
17557
|
Fri Apr 21 19:07:07 2023 |
rana | Configuration | IOO | back on RL |
this afternoon I did some swapping around of linear and RL for IMC WFS.
In the end, I left in in the 'both' state:
- The WFS1,2,MC_TRANS PIT loops are all on but with -40, -40, -20 dB of nominal gain
- the RL is on for PIT
this is so that we have good DC control with integrators and good HF performance too. |
17573
|
Mon May 1 08:57:45 2023 |
JC | Configuration | IMC | Bad Alignment |
I had to realign the IMC today. When I came in, it was very bad, not much flashing at all, I had to do it from scratch. CH01 Camera on MON7 in the control room is completely white. Did the camera go out over the weekend? I will come back to poke around later, I have headed over to WB for a moment and will be back soon. sitemapsi |
Attachment 1: Screenshot_2023-05-01_15-55-33.png
|
|
17577
|
Tue May 2 10:39:49 2023 |
JC | Configuration | IMC | Bad Alignment |
It took a while, but I was finally able to align IMC. It seems like WFS has been getting really whacky lately when we arent in the lab watching it . The picture attached has an arrow of where the beam spot was at this morning |
Attachment 1: BB26DF83-5B6A-4BC1-A2A0-6E18E1A2B91E.jpeg
|
|
17630
|
Tue Jun 13 14:12:34 2023 |
Mayank | Configuration | | Restarted the NDS2 script on Megatron |
[Radhika, Mayank]
Restarted the NDS2 script on Megatron following the instructions here
Steps
1) SSH to megatron - "ssh megatron"
2) Switch to nds2mgr using "sudo su nds2mgr"
3) Stop and restart the service using
"sudo /etc/init.d/nds2 stop
sleep 20
sudo /etc/init.d/nds2 start" |
17669
|
Fri Jul 7 13:33:48 2023 |
JC | Configuration | Daily Progress | Alignment and restoring the IFO |
[Yuta, JC]
We are restoring the IFO alignment back to Nominal operating state
What we did:
- Fixed the IMC and got WFS back to running state.
- Returned all TMs to there original postion using the OPLEVs
- Used BurtRestore to bring back the C1:HPC.adl and C1:BAC.adc
- Align the OPLEVs.
Summary:
To start off the morning, I began to work on IMC which became misaligned ~6:00am. IMC WFS seemed to be the issue, so I turned these off and pushed worked to align IMC manually (This took a ton of time). After aligning, Yuta came in and showed me how to fix IMC WFS and we got it to work again. the main issue being that "Clear History" was stuck for a bit and the offsets were stuck to insane values.
Next we moved forward with viewing the BHD PDs. Yuta knew there was an issue with the BurtRestore Yehonathan and I did yesterday because there were no values on the C1:HPC.adl page. To fix this, in the terminal we typed -->
~> cd /opt/rtcds/caltech/c1/burt/autoburt/snapshots/2023/Jun/9
Now, you land in whichever date you chose, for us it was the 9th of June:
9> burtgooeyC1:HPC.adl
This will pull up BURT. from here go Restore-> Snapshot Files-> (Select your time) -> (Select which files you want to restore) -> Ok -> Cancel -> Restore. (Keywords: How to burtrestore )
This will restore the files of which you have chosen back to the date you selected.
Yuta and I restored C1:HPC.adl and C1:BAC.adl.
Following, now that all the BurtRestoring is done, we moved forward with aligning single arms. We had a very trashy mode on BHD and decided to align TT1 and TT2.
I tried to align the Y arm to start off, but ETMy was acting very hectic. I was trying to align the OPLEVs to start off, but ETMY Oplev was VERY FAR OFF. It was very weird that I was moving YAW for a very good amount and yet the Red Beam would not move one bit in the YAW direction! I couldnt get it even close to hit the steering mirror to hit the ETMY_OPLEV_QPD. I asked Yuta for help and it turns out that the gain for the alignment offesets were 0! After Yuta found this, he restored the original offset values by using:
restoreAlignment -o ETMY -t 'now 14days'
(Keywords: How to restoreAlignment)
After this issue was fixed, I was able to align the OPLEV beam with ease and we started to get some flashing on the Y Arm. Yuta now has the Y Arm locked with flashing on the X Arm. We plan to align nicely and realign the OPLEVs before the end of the day. |
17670
|
Fri Jul 7 15:24:38 2023 |
Koji | Configuration | Daily Progress | Alignment and restoring the IFO |
The incompleteness of burtrestore is a critical issue. We need to track down what is the issue.
|
17753
|
Thu Aug 3 21:35:50 2023 |
Koji | Configuration | PEM | PSL Flow speed sensor channels added |
As the preparation of the flow sensor installation, I added two slow channels via c1psl (Acromag IOC).
C1:PEM-HEPA_FLOW_PSL1
C1:PEM-HEPA_FLOW_PSL2
This entry explains how this was done because there is a tricky hidden process that is scarcely explained elsewhere upon adding the slow channels
Tag: How to add slow channels / C0ECDU.ini / Acromag / Advanced LIGO RTS stand-alone EPICS data concentrator
1. Edited the db file
I learned that the spare ADC channels ADC4 CH5 and CH6 are available on c1psl
(See http://nodus.ligo.caltech.edu:8080/40m/[ELOG 17727] )
Created /cvs/cds/caltech/target/c1psl/psl_pem.db
c1psl>cat psl_pem.db
# Greated for Acromag PEM - Koji Arai 2023/8/3
#
grecord(ai,"C1:PEM-HEPA_FLOW_PSL1")
{
field(DESC,"HEPA Air Flow Speed Monitor Unit 1")
field(SCAN,".1 second")
field(DTYP,"asynInt32")
field(INP,"@asynMask(C1PSL_XT1221_ADC04 5 -16)MODBUS_DATA")
field(PREC,"3")
field(LINR,"LINEAR")
field(EGUF,"10")
field(EGUL,"-10")
field(EGU,"Volts")
field(HOPR,"10")
field(LOPR,"-10")
field(ASLO,"1.09225")
}
grecord(ai,"C1:PEM-HEPA_FLOW_PSL2")
{
field(DESC,"HEPA Air Flow Speed Monitor Unit 2")
field(SCAN,".1 second")
field(DTYP,"asynInt32")
field(INP,"@asynMask(C1PSL_XT1221_ADC04 6 -16)MODBUS_DATA")
field(PREC,"3")
field(LINR,"LINEAR")
field(EGUF,"10")
field(EGUL,"-10")
field(EGU,"Volts")
field(HOPR,"10")
field(LOPR,"-10")
field(ASLO,"1.09225")
}
2. Added the db file to cmd file.
Added the following line to /cvs/cds/caltech/target/c1psl/C1_PSL.cmd as
dbLoadDatabase("/cvs/cds/caltech/target/c1psl/psl_pem.db")
3. Restart modbusIOC at c1psl
c1psl>ssh c1psl
controls@c1psl's password:
...
controls@c1psl:~$ sudo systemctl restart modbusIOC.service
4. Added the channels to C0EDCU.ini
Add the following lines to /opt/rtcds/caltech/c1/chans/daq/C0EDCU.ini
Leave the first ~20 channels untouched, as they appears on dataviewer as the default channels.
#HEPA Air Flow Mon channels @c1psl
[C1:PEM-HEPA_FLOW_PSL1]
[C1:PEM-HEPA_FLOW_PSL2]
5. Restart fb
telnet fb 8087
Trying 192.168.113...
Connected to fb.martian.
Escape character is '^]'.
daqd> shutdown
6. Ssh into c1sus and run the following command:
This is a new process. Until this is done, the channels are not recorded.
controls@nodus|daq> ssh c1sus
controls@c1sus:~$ sudo systemctl restart rts-edc_c1sus
|
17892
|
Tue Oct 10 14:10:11 2023 |
Paco | Configuration | LSC | ETMY actuation calibration using ALSY |
[Vittoria, Paco]
This work was done yesterday ~ 8 PM. After we aligned YARM and locked using POY11, Vittoria turned on the SRCL osc at 1 kHz and steadily increased the gain while looking at the BEATY demod signal. The noise floor of the BEATY was estimated to be 6.6 Hz/rtHz at 1kHz, and the line appeared with 300 counts with an average magnitude (Tavg= 25 s) of 25.5 +- 1.3 Hz. Using the approximate (overestimated) length of L=40 m and the (also overestimated) frequency of the laser f=281.9 THz, we inferred a displacement magnitude of 3.62 +0.18 - 0.37 pm at 1 kHz. This is in agreement with Yuta's recent calibration coefficient of 10.66e-9 / f^2 m/count from which we expect 3.19 pm at 1 kHz.
After this we aligned XARM and configured the interferometer to lock "electronic" FPMI but were not successful.
Next:
- Lock FPMI, use high-BW Common mode board for CARM feedback
- Turn on lines.
|
17956
|
Fri Nov 3 17:05:10 2023 |
Paco | Configuration | IOO | Low power IMC locked |
[Paco, yuta]
We opened the PSL shutter and verified the power behind the shutter is 92 mW. Then, we changed the IMC autolocker parameter file to lower the transmission threshold from 5000 counts to 300 using the instructions from the wiki. We then slightly aligned MC2 in YAW and maximized the flashing in transmission and also changed the parameters for the inputGain slider by +20 dB in both unlocked and locked states so we compensate for the decrease in optical gain. The changes have been pushed here.
After these changes in the config file we ssh into optimus and restart the docker container running the autolocker script in this case by running:
sudo docker restart scripts_AL_MC_1
|
17958
|
Fri Nov 3 17:16:14 2023 |
Paco | Configuration | IOO | Low power IMC locked |
[Paco, yuta]
We continued with the alignment recovery by looking for arm cavity flashing. To do this it was very helpful to restore the OpLev centering and use the AUX lasers -- After some further alignment on both arms, we just needed to increase the LSC gains (XARM and YARM) by a factor of ~ 1.5x and lower the TRX/TRY DC matrix elements for triggering from 1.0 to 10.0 in order to engage the IR locks (See Attachment #1).
Attachment #2 shows the screenshot of MEDM screens after both arms are aligned with low power mode.
Next:
- Measure beam spots in low power mode
- In-vac work to center the beams on vertex optics |
Attachment 1: lowpower_arm_lock_20231103.png
|
|
Attachment 2: Screenshot_2023-11-03_17-39-31_botharms.png
|
|
94
|
Mon Nov 12 14:09:19 2007 |
rob | DAQ | General | tpman dead on fb40m |
The testpoint manager was dead on fb40m. I know I re-started it sometime after the power outage, so something must have killed it. If you get an error from DTT like
"diagnostic kernel does not support: testpoints", then log into fb40m as root, check for the tpman with a ps -ef | grep tpman. If it's not there, then run /usr/controls/tpman & and close the terminal window. |
152
|
Fri Nov 30 21:27:24 2007 |
rana | DAQ | PEM | weather / stacis / c1pem1 |
I was trying to add some Seis BLRMS channels to the c1pem1 processor so that we could have DMT trends.
Then I found that none of the Weather channels have been working for a year or so. I could also not
telnet into it. I tried resetting it but no luck. There was no entry in the Wiki for it so I added
a place holder.
Have the weather channels ever worked? Do we have those sensors? I think I've never actually looked
for this. Seems like a fine ugrad job. |
157
|
Mon Dec 3 00:10:42 2007 |
rana | DAQ | Computer Scripts / Programs | linemon |
I've started up one of our first Matlab based DMT processes as a test.
There's a matlab script running on Mafalda which is measuring the height of the 60 Hz peak
in the MC1 UL SENSOR and writing it to an unused EPICS channel (PZT1_PIT_OFFSET).
The purpose of this is just to see if such a thing is stable over long periods of time. Its
open on a terminal on linux3 so it can be killed at any time if it runs amok.
Right now the code just demods the channel and tracks the absolute value of the peak. The
next upgrade will have it track the actual frequency once per minute and then report that
as well. We also have to figure out how to make it a binary and then make a single script
that launches all of the binaries.
For now you can watch its progress on the StripTool on op540m; its cheap and easy DMT viewer. |
160
|
Mon Dec 3 19:06:49 2007 |
rana | DAQ | Computer Scripts / Programs | linemon |
I turned up my nose at Matlab's special tools. I modified the linetracker to use the
relationship phase = 2*pi*f*t to estimate the frequency each minute. The
code uses 'polyfit' to get the mean and trend of the unwrapped phase and then determines
how far the initial frequency estimate was off. It then uses the updated number as the
initial guess for the next minute.
I looked at a couple hours of data before letting it run. It looks like the phase of the
'60 Hz' peak varies at 20 second time scales but not much faster or rather anything faster
would be a glitch and not a monotonic frequency drift.
From the attached snapshot you can see that the amplitude (PZT1_PIT) varies by ~10 %
and the frequency by ~40 mHz in a couple hour span. |
Attachment 1: spd64d1.jpg
|
|
170
|
Wed Dec 5 19:25:07 2007 |
rana | DAQ | CDS | DMF |
I made a database file on C1AUX called dmf.db. It has 9 DMF EPICS channels which are also trended
so that one can now write data to those channels from a DMF Monitor and the data will be records.
New channels:[C1:DMF-SEIS_1]
[C1:DMF-SEIS_2]
[C1:DMF-SEIS_3]
[C1:DMF-LINE_1]
[C1:DMF-LINE_2]
[C1:DMF-LINE_3]
[C1:DMF-MC_1]
[C1:DMF-MC_2]
[C1:DMF-MC_3]
I added these to C1AUX because it doesn't do much and can be booted without having much effect.
(it controls Mech Shutters, Video, and Illuminators. It used to also do the EO Shutter but I
removed that from its startup.cmd and it will no longer load those records). |
204
|
Wed Dec 19 20:28:27 2007 |
Andrey | DAQ | PEM | Names for all 6 accelerometers have been changed |
I eventually changed the names for all 6 accelerometers (see my ELOG entry # 172 from Dec. 05 about my intent to do that).
I removed the word "BS" from their names,
and I changed the word combination "ACC_BS_EAST" in the old name for "ACC_ITMX" in the new name;
as well "ACC_BS_WEST" is now replaced by "ACC_ETMX".
(the reasoning behind such a change should become clear from my ELOG entry #172).
New accelerometer names are:
(note: there are no spaces (nowhere!) in the names of accelerometers, but ELOG replaces ": P" written without a space by a strange symbol )
C1 : PEM - ACC _ ETMX _ X ;
C1 : PEM - ACC _ ETMX _ Y ;
C1 : PEM - ACC _ ETMX _ Z ;
C1 : PEM - ACC _ ITMX _ X ;
C1 : PEM - ACC _ ITMX _ Y ;
C1 : PEM - ACC _ ITMX _ Z .
One can find them in "C1 : PEM - ACC" in Dataviewer.
|
312
|
Tue Feb 12 16:34:07 2008 |
rob | DAQ | DMF | seisBLRMS 1.1 |
The compiled version of seisBLRMS had been running ~2 weeks without crashing as of last night, when I killed it
so it wouldn't interfere with alignment scripts. I added an EPICS channel C1:DMF-ENABLE, and updated the DMF
executables to check this channel while running. So far it seems to work. When you're running alignment acripts,
simply click the DISABLE button on the C1DMF_MASTER.adl screen, and then re-ENABLE when the scripts finish.
It's not clear why this is necessary though. Theories include the constant disk access is keeping the
framebuilder busy, reducing its ability to deal with ezcademod commands and DMF programs just flooding the
network with so much traffic that ezcademod-related packets run late and get ignored.
Also, for reasons of aesthetics, I changed the data delay from 6 minutes to 5 minutes. We'll see if that's enough. |
316
|
Thu Feb 14 15:04:53 2008 |
rob | DAQ | DMF | DMF delay |
Sometime ago I edited seisBLRMS to keep of track of how long it was taking to write RMS data (that is, the delay between the accelerometer data and the write of the EPICS rms data). Here's a plot of that info, showing how the delay increases over time. I think this indicates a logical flaw in the timing of the seisBLRMS program, which sort of relies on everything running well consistently; this should not be difficult to fix. I'll maybe try increasing the delay to ~10 minutes, and making it relatively inflexible. |
Attachment 1: DMFdelay.png
|
|
317
|
Thu Feb 14 15:05:18 2008 |
rob | DAQ | DMF | seisBLRMS 1.1 |
>
> Also, for reasons of aesthetics, I changed the data delay from 6 minutes to 5 minutes. We'll see if that's enough.
5 minutes didn't work. |
358
|
Tue Mar 4 23:22:32 2008 |
rob | DAQ | Computers | c1susvme1&2 rebooted |
I found that some channels from c1susvme1 and c1susvme2 were not being recording by the DAQ (and were not showing up in DV). I rebooted these processors, which fix the problem. If you see other cases of this (signal exactly zero, but not a testpoint problem), just reboot the corresponding processor. |
440
|
Wed Apr 23 22:39:54 2008 |
Andrey | DAQ | Computer Scripts / Programs | Problem with "get_data" and slow PEM channels |
It turns out that I cannot read minute trends for the slow weather channels for more than 1000 seconds back (roughly more than 15 minutes ago) using "get_data" script.
For comparison, I tried MC1 slow channels, and similar problem did not arise there. Probably, something is wrong with the memory of slow weather channels. At the same time, I can see minute-trends in Dataviewer as long ago as I want.
In response to
>>get_data('C1: PEM-weather_outsideTemp', 'minute', gps('now') - 3690, 3600);
I get the error message:
"Warning: Missong C1: PEM-weather_outsideTemp M data at 893045156". |
456
|
Sun Apr 27 18:11:58 2008 |
rob | DAQ | Computers | br40m? |
The testpoint manager (which runs on fb40m) crashed this afternoon. Upon re-starting it, I found there was a rogue dtt process on op440m and also a daqd daemon running on br40m. One or both of these caused the tpman to crash. br40m is the frame broadcaster, which is never used here as we don't run DMT. I killed the daqd process there.
The way to find if there is a rogue process is to watch the output to the console from the tpman when you start it:
Allocate new TP handle 56 by 131.215.113.203
Allocate new TP handle 57 by 131.215.113.203
Allocate new TP handle 58 by 131.215.113.203
Allocate new TP handle 59 by 131.215.113.203
Allocate new TP handle 60 by 131.215.113.203
Allocate new TP handle 61 by 131.215.113.203
Allocate new TP handle 62 by 131.215.113.203
Allocate new TP handle 63 by 131.215.113.203
Allocate new TP handle 64 by 131.215.113.203
Allocate new TP handle 65 by 131.215.113.203
Allocate new TP handle 66 by 131.215.113.203
Allocate new TP handle 67 by 131.215.113.203
Allocate new TP handle 68 by 131.215.113.203
If you see something like this, with a new TP handle being allocated every few seconds, you need to log in to the corresponding host and kill whatever process has run away. |
457
|
Sun Apr 27 22:57:15 2008 |
ajw | DAQ | Computers | br40m? |
Quote: |
The testpoint manager (which runs on fb40m) crashed this afternoon. Upon re-starting it, I found there was a rogue dtt process on op440m and also a daqd daemon running on br40m. One or both of these caused the tpman to crash. br40m is the frame broadcaster, which is never used here as we don't run DMT. I killed the daqd process there.
The way to find if there is a rogue process is to watch the output to the console from the tpman when you start it:
Allocate new TP handle 56 by 131.215.113.203
Allocate new TP handle 57 by 131.215.113.203
Allocate new TP handle 58 by 131.215.113.203
Allocate new TP handle 59 by 131.215.113.203
Allocate new TP handle 60 by 131.215.113.203
Allocate new TP handle 61 by 131.215.113.203
Allocate new TP handle 62 by 131.215.113.203
Allocate new TP handle 63 by 131.215.113.203
Allocate new TP handle 64 by 131.215.113.203
Allocate new TP handle 65 by 131.215.113.203
Allocate new TP handle 66 by 131.215.113.203
Allocate new TP handle 67 by 131.215.113.203
Allocate new TP handle 68 by 131.215.113.203
If you see something like this, with a new TP handle being allocated every few seconds, you need to log in to the corresponding host and kill whatever process has run away. |
I *think* Alex is responsible for the daqd daemon running on br40m (he set up some new stuff recently, a data concentrator and broadcaster); I'll make sure he sees this post. |
459
|
Tue Apr 29 21:09:12 2008 |
rana | DAQ | CDS | FE Filters |
These are new FE filters for downsampling and upsampling. We will be going from native hardware sampling rates of 64k down to 32k, 16k, and 2k.
The attached plot shows these filters. They are 3dB ripple, 40 dB stopband, 4th order elliptic filters in which I have moved the zeros around
into good places (e.g. to the Nyquist frequency).
I'm also attaching the .txt file containg the filter coefficients and the design strings. The filters are called x2, x4, and x32, for the
D2, D4, and D32 downsampling, respectively. |
Attachment 1: fefilters.jpg
|
|
Attachment 2: fefilters.txt
|
# FILTERS FOR ONLINE SYSTEM
#
# Computer generated file: DO NOT EDIT
#
# MODULES ULYAW
#
################################################################################
### ULYAW ###
################################################################################
# SAMPLING ULYAW 65536
... 28 more lines ...
|
583
|
Fri Jun 27 15:20:52 2008 |
rob | DAQ | LSC | .ini file change |
I removed C1:LSC-XARM_CTRL from the frames and added C1:LSC-CARM_ERR |
640
|
Mon Jul 7 13:58:37 2008 |
Eric, josephb | DAQ | PEM | Using unused PEM channels to test camera code |
Joe and I have taken control of the EPICS channels C1:PEM-Stacis_EEEX_geo and C1:PEM-Stacis_EEEY_geo since we heard that they are no longer in use. We are currently
using them to test the ability for the Snap camera code to read and write from EPICS channels. Thus, the information being written to these channels is completely unrelated
to their names or previous use. This is only temporary; we'll create our own channels for the camera code shortly (probably within the next couple of days).
- Eric |
660
|
Fri Jul 11 20:16:01 2008 |
Eric | DAQ | Cameras | Taking data from the GC 750 Camera |
Mafalda has been set up with a background process to constantly take data from the GC 750 camera (at the end of the x-arm) for the weekend. This camera will otherwise be inoperable until then.
In the small chance that this slows either Mafalda or the network to a crawl, the process to kill should have PID 26265. |
671
|
Tue Jul 15 10:09:42 2008 |
Eric | DAQ | Cameras | Did anyone kill the picture taking process on Mafalda? |
Did anyone kill the process on Mafalda that was taking pictures of the end mirror of the x-arm last Friday? I need to know whether or not it crashed of its own accord. |
673
|
Tue Jul 15 11:47:56 2008 |
Jenne | DAQ | PEM | Accelerometer channels in ASS Adapt MEDM screen |
Jenne, Sharon
We have traced which accelerometers correspond to which channels in the C1ASS_TOP MEDM screen.
Accelerometer Channel
------------- --------------------------
MC1-X C1:ASS-TOP_PEM_2_ADAPT_IN1
MC1-Y C1:ASS-TOP_PEM_3_ADAPT_IN1
MC1-Z C1:ASS-TOP_PEM_4_ADAPT_IN1
MC2-X C1:ASS-TOP_PEM_5_ADAPT_IN1
MC2-Y C1:ASS-TOP_PEM_6_ADAPT_IN1
MC2-Z C1:ASS-TOP_PEM_7_ADAPT_IN1
SEISMOMETER C1:ASS-TOP_PEM_1_ADAPT_IN1 |
684
|
Wed Jul 16 17:36:51 2008 |
John | DAQ | PSL | FSS input offset |
I changed the nominal FSS input offset to 0 from 0.3. Tolerance remains unchanged at +/-0.05. |
700
|
Fri Jul 18 19:43:55 2008 |
Yoichi | DAQ | Computers | PSL fast channels cannot be read by dataviewer |
At this moment only the PSL fast channels have trouble.
Rob restarted fb40m, c1IOVME, but no effect. |
826
|
Mon Aug 11 19:09:28 2008 |
Jenne | DAQ | PEM | Seismometer DAQ is being funny |
While looking at the Ranger seismometer's output to figure out what our max typical ground motion is, Rana and I saw that the DAQ output is at a weird level. It looks like even though the input to the DAQ channel is being saturated, the channel isn't outputing as many counts as expected to Dataviewer.
Sharon and I checked that the output of the seismometer looks reasonable - sinusoidal when I tap on the seismometer, and the the output of the SR560 (preamp) is also fine, and not clipping. If I stomp on the floor, the output of the SR560 goes above 2V (to about 3V ish), so we should be saturating the DAQ, and getting the max number of counts out. However, as you can see in the first figure, taken when I was tapping the seismometer, the number of counts at saturation is well beneath 32768counts. (16 bit machine, so the +-2V of the DAQ should have a total range of 65536. +2V should correspond to +32768counts.) The second figure shows 40 days of seismometer data. It looks like we saturate the DAQ regularly.
I did a check of the DAQ using an HP6236B power supply. I sent in 1V, 2V and 2.2V (measuring the output of the power supply with a 'scope), and measured the number of counts output on the DAQ.
Input Voltage [V] | Counts on Dataviewer | Expected counts from 16 bit machine
|
1 | 18983 | 16384
|
2 | 29331 | 32768
|
2.2 | 29347 | 32768
|
I'm not sure why the +1V output more than the expected number of counts (unless I mis-measured the output from the power supply).
Moral of the story is...when the DAQ is saturated, it is not outputting the expected number of counts. To be explored further tomorrow... |
Attachment 1: SeisDAQ.png
|
|
Attachment 2: SeisData.png
|
|
917
|
Wed Sep 3 19:09:56 2008 |
Yoichi | DAQ | Computers | c1iovme power cycled |
When I tried to measure the sideband power of the FSS using the scan of the reference cavity, I noticed that the RC trans. PD signal was not
properly recorded by the frame builder.
Joe restarted c1iovme software wise. The medm screen said c1iovme is running fine, and actually some values were recorded by the FB.
Nonetheless, I couldn't see flashes of the RC when I scanned the laser frequency.
I ended up power cycling the c1iovme and run the restart script again. Now the signals recorded by c1iovme look fine.
Probably, the DAQ boards were not properly initialized only by the software reset.
I will re-try the sideband measurement tomorrow morning. |
1028
|
Mon Oct 6 12:45:41 2008 |
Alberto | DAQ | LSC | C1LSC in coma |
Alberto, Joe,
The C1LSC medm screen is frozen and the C1LSC computer is down. We tried to reboot and to restart it first turning off the power and then just rebooting remotely. None of them worked. We check whether any of the cable was unplugged but they were ok. Also all the led turned on to green after rebooting.
Trying to reboot we get the following error message: init_module: device or resource busy.
We called Alex who first suggested to check all the connection and then to swap the timing cable between two Pentek boards but the computer was still down.
It is possible that the board is dead. Alex and Rolf are going to look into this problem and for any spare board.
by now we can't lock any DOF of the IFO. |
1029
|
Mon Oct 6 16:41:33 2008 |
Alberto | DAQ | LSC | C1LSC in coma |
Quote: | Alberto, Joe,
The C1LSC medm screen is frozen and the C1LSC computer is down. We tried to reboot and to restart it first turning off the power and then just rebooting remotely. None of them worked. We check whether any of the cable was unplugged but they were ok. Also all the led turned on to green after rebooting.
Trying to reboot we get the following error message: init_module: device or resource busy.
We called Alex who first suggested to check all the connection and then to swap the timing cable between two Pentek boards but the computer was still down.
It is possible that the board is dead. Alex and Rolf are going to look into this problem and for any spare board.
by now we can't lock any DOF of the IFO. |
Alex, Rob, Alberto,
Alex replaced the Pentek board used by C1LSC with a spare one that they had at the Wilson house. That fixed the DMA failure but since the board had a channel broken, one of the channels (POY) was still not available.
Looking at the wiring diagram of the ASC crate, we found that one of the Pentek boards in it was actually not used by anything and thus available to replace the bad one in LSC. We switched the two boards so that now the one that Alex installed is mounted in the ASC crate and it is connected to the cable labeled 1x2-ASC 6.
C1LSC is up again and all the channels in the C1LSC screen, including POY, now seem to be working properly. |
1066
|
Wed Oct 22 09:42:41 2008 |
Alberto | DAQ | Computers | c1iool0 rebooted and MC autolocker restarted |
This morning I found the MC unlocked. The MC-Down script didn't work because of network problems in communicating with scipe7, a.k.a. c1iool0. Telneting to the computer was also impossible so I power cycled it from its key switch. The first time it failed so I repeated it a second time and then it worked.
Yoichi then restarted c1iovme. It was also necessary to restart the MC autolocker script according to the following procedure:
- ssh into op440m
- from op440m, ssh into op340m
- restart /cvs/cds/caltech/scripts/scripts/MC/autolockMCmain40 |
1114
|
Tue Nov 4 17:58:42 2008 |
Alberto | DAQ | PSL | MC temperature sensor |
I added a channel for the temperature sensor on the MC1/MC3 chamber: C1:PSL-MC_TEMP_SEN.
To do that I had to reboot the frame builder. The slow servo of the FSS had to get restarted, the reference cavity locked and so the PMC and MZ. |
1124
|
Fri Nov 7 18:38:19 2008 |
Alberto | DAQ | PSL | MC temperature sensor hooked up |
Alberto, Rana,
we found that the computer handling the signals from ICS-110B was C1IOVME so we restarted it. We changed the name of the channel to C1:PEM_TEMPS and the number to 16349. We tracked it up to the J14 connector of the DAQ.
We also observed the strange thing that both of the differential pairs on J13 are read by the channle. Also, if you connect a 50 Ohm terminator to one of the pairs, the signal even get amplified.
(The name of the channel is PEM-MC1_TEMPS) |
1130
|
Wed Nov 12 11:14:59 2008 |
Caryn | DAQ | PSL | MC temp sensor hooked up incorrectly |
MC Temperature sensor was not hooked up correctly. It turns out that for the 4 pin LEMO connections on the DAQ like J13, J14, etc. the channels correspond to horizontal pairs on the 4 pin LEMO. The connector we used for the temp sensor had vertical pairs connected to each BNC which resulted in both the differential pairs on J13 being read by the channel.
To check that a horizontal pair 4 pin LEMO2BNC connector actually worked correctly we unlocked the mode cleaner, and borrowed a connector that was hooked up to the MC servo (J8a). We applied a sine wave to each of the BNCs on the connector, checked the J13 signal and only one of the differential pairs on J13 was being read by the channel. So, horizontal pairs worked. |
1143
|
Tue Nov 18 13:28:08 2008 |
Caryn | DAQ | IOO | new channel for MC drum modes |
Alberto has added a channel for the Mode Cleaner drum modes.
C1:IOO-MC_DRUM1
sample rate-2048
chnum-13648 |
1228
|
Wed Jan 14 15:53:32 2009 |
steve | DAQ | PSL | MC temperature sensor |
Quote: | I added a channel for the temperature sensor on the MC1/MC3 chamber: C1:PSL-MC_TEMP_SEN.
To do that I had to reboot the frame builder. The slow servo of the FSS had to get restarted, the reference cavity locked and so the PMC and MZ. |
Where is this channel? |