  3490   Mon Aug 30 22:45:49 2010 kiwamuUpdateCDSbinary outputs for the new CDS

{ Joe and Kiwamu }

Today we made some efforts to get the binary outputs (BOs) working.

They still are not working but the situation is getting better.

    So far the BO cards were not recognized by any realtime codes when we ran the codes on the new front end machine C1SUS.

We put some printk commands in an initialization code like Yoichi did (see this entry) to confirm if the initialization of the BOs properly happens or not.

Then we found that we had to put the BO modules also in an IOP model file which controls all the ADCs and the DACs.

We put the BO modules in the IOP file and then BOs started being recognized by the IOP, however they still are not fully recognized by the realtime control process.

We continue this work...

 

[Some notes]


[front end code]

First of all we looked at the front end c-code c1sus.c living under /cvs/cds/calech/cds/advLigoRTS/src/fe/c1sus/.

It was okay because there was a proper BO statement like

CDS_CARDS cards_used[] = { {CON_32DO,0}, {CON_32DO,2}};

 

[initialization code]

 There is an initialization code called map.c living under /cvs/cds/calech/cds/advLigoRTS/src/fe.

This code is complied when we do the make commands as described on the wiki.

Eventually the initialization code is executed only when the IOP starts up. This happens when we type startc1x02 at /cvs/cds/rtcs/caltech/c1/script/.

 

[printk statments]

   We made a backup file named map_20100830.c.back for map.c. Then we added to map.c some pintk statements in a while loop which looks for available BOs.   

After running the make commands for the IOP file and startc1x02, we basically can check the results of those printk statements by using dmesg.

We found that map.c was running correctly because  map.c went in the while loop 4 times which is exactly the same number as the BOs we put in the model file.

However the code failed to install the BOs each time.

 

[BO modules in IOP file]

  Joe pointed out the failure in map.c was caused by lack of the BO modules in the IOP file c1x02.mdl.

Indeed putting the BO modules in the IOP fixed the problem. 

Another thing we found at this time is that there is a maximum number of BOs we can put in a model file.

The maximum number is 4, which is not enough for us because we need to put 5 of them including a 16bit BIO and four 32bit BOs.

Now Joe is asking to Alex about this issue.

Anyway now the IOP can recognize the BO cards, this fact can be found if you look at the log file /cvs/cds/rtcds/caltech/c1/target/c1x02/logs/log.txt.

The log file saids "3 Contec 32ch PCIe DO cards found", which is a good sign. 

 

[BO modules in realtime code] 

Although the IOP started seeing the BO cards, the realtime code c1sus still didn't fully recognize the BO cards.

If we look at the log file log.txt at /cvs/cds/rtcds/caltech/c1/target/c1sus/logs/, there is an evidence that the code found some cards.

The log file saids  

   Model 6 = 10

   Model 7 = 4

   Model 8 = 4

   Model 9 = 4

   Model 10 = 0.

 It looks like these corresponds to the BO cards.

So the code found some cards, but doesn't know what they are.

We need few more debugging for the BOs... 

  3492   Tue Aug 31 02:50:45 2010 kiwamuUpdateCDSvertex suspensions controlled by the new CDS

I plugged the new CDS to the vertex suspensions. 

Now PRM, SRM, ITMs, MCs and BS are under the control of the new CDS. 

From now on we will never go back to the old system.

 

Though,  the watchdogs are still running on the old system.

So if you need to turn on/off the watchdogs, you can simply enable/disable them from the usual medm screens.

  3494   Tue Aug 31 11:50:14 2010 kiwamuUpdateCDSmaximum number of BIOs

 { Joe and Kiwamu },

 Now we  are able to compile the model file with more than 4 binary input/outputs (BIOs).

 As I wrote in a past entry (see here), the number of the BIOs was limited to 4, which is not enough for us.

 

  We modified a header file called "cdsHardware.h"  in order to allow model files having more than four BIOs.

The header file lives under /cvs/cds/caltech/advLigoRTS/src/include/drv/.

There was a sentence defining the maximum number in the file:

 #define MAX_DIO_MODULES         4.

We changed this to

 #define MAX_DIO_MODULES         8.

  3498   Tue Aug 31 16:42:26 2010 josephbUpdateCDSTemporarily reverting to CDS revision 2005

Apparently updating to the latest revision of the RCG has some issues with diaggui and awgtpman.  Alex had to do some recompiling up at Hanford which apparently took him some time.  He'll be coming by tomorrow to try to bring those codes to the front end machines.

As a temporary fix, until Alex gets here tomorrow, we're reverting to the 2005 revision in the svn of the cds code.  I'm placing it in the location it is supposed to go in the new advLIGO scheme, which is /opt/rtcds/caltech/c1/core/, which is where Keith had it at LLO.  Once we get the new codes working, we will do an svn update on that location and migrate our work to that install location, at which point I'll remove the old /cvs/cds/caltech/cds/advLigoRTS/ location.

  3507   Wed Sep 1 12:24:47 2010 josephbUpdateCDSTrying to get up to date CDS code runnning

Alex, Joe:

We copied the latest x02 to c1x02 and modified to our the config block in it.

We removed gds_node_id.  We just have one number now, the dcuid, which is unique for each controller, simulated plant and IOP.  Set site to C1 and host to c1sus.

Alex made the latest awgtpman backwards compatible, and checked that into svn.

We installed the latest framecpp onto c1sus from www.ldas-sc.ligo.caltech.edu/packages/ using wget.

wget www.ldas-sc.ligo.caltech.edu/packages/framecpp-1.18 and then used make.

This let us compile diagd on c1sus, using the command make stand in the /advLigoRTS/build area.

We copied gds from the seiteststand over at handford and are trying to build that on megatron.  However, there's a bunch of packages we need for it to install properly.  Alex said he'd work on that later, possibly trying to make some portable binaries.

Checked out the latest dataviewer into /opt/rtcds/caltech/c1/core/daq, however its not quite working yet either.  This is another thing Alex said he'll work on later.

We are also going to test Alex and Rolf's kernel patch over on c1iscex on Centos base kernel (apparently they've been using Gentoo up at hanford for the test stands...) and see how that works.

  3515   Thu Sep 2 16:45:48 2010 josephbUpdateCDSNumbering scheme of the PCI bus

Rolf has recently written a document describing how one should fill out an IO chassis and how the numbering works out.  This can be found in the DCC at Rolf's PCIe numbering guide (T1000523).

Basically it works out that slot 1 corresponds to PCIe number 1, but slot 2 corresponds to PCIe number 6.  And so forth.  The following table gives a quick summary.

Slot 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
PCIe Number 1 6 5 4 9 8 7 3 2 14 13 12 17 16 15 11 10

 

  3516   Thu Sep 2 17:43:30 2010 josephbUpdateCDSOne working BO output module, others not so much

 Joe and Kiwamu:

We found one bug in the RCG code, where the second input for the CDO32 part (32 binary output) was simply a repeat of the first input, and totally ignored the second input.  This was fixed in the /advLigoRTS/src/epics/util/lib/CDO32.pm file by changing 

$calcExp .= $::fromExp[0];

to

$calcExp .= $::fromExp[1];

This fix has been added to the svn.  Unfortunately, while we have a single working binary output module, the 2nd and later modules do not seem to be responding at all.  We've done the usual swaping parts of the path in both software and hardware and can't find any bad pieces in our model files or the actual hardware.   That leaves me wondering about the c code, specifically if the CDO32Output[1], CDO32Output[2], and so forth array entries in the code are being handled properly.  I'll try to get some thoughts on it from Alex tomorrow.

  3527   Mon Sep 6 20:38:58 2010 KojiUpdateCDSSusension model reviewed

I have reviewed the suspension model of C1SUS and refined it.

It is comaptible to the current one but has minor additions.

Attachment 1: suspension_model.pdf
suspension_model.pdf
  3528   Mon Sep 6 21:08:44 2010 ranaUpdateCDSSusension model reviewed

We must remember that we are using the Rev.B SOS Coil Drivers and not the Rev. A. 

The main change from A->B was the addition of the extra path for the bias inputs. These inputs were previously handled by the slow EPICS system and not a part of the front end. So we used to have a separate bias screen for these than the bias which is in the front end. The slow bias is what was used for the alignment to avoid overloading the range of the main coil driver path.

  3534   Tue Sep 7 15:31:28 2010 josephb, alexUpdateCDSBinary Output working/ IO chassis fixed

As noted previously, we were having problems with getting multiple 32 channel binary output cards working.  Alex came by and we eventually tracked the problem down to an incorrect counter in the c code.  This has been fixed and checked into the CDS svn repository.  I tested the actual hardware and we are in fact able to turn our test LEDs on with multiple binary output boards.

 

Alex and I also looked at the non-functional IO chassis (the one which wouldn't sync with the 1PPS signal and wasn't turning on when the computer turned on.  We discovered one corner of the trenton board wasn't screwed down and was in fact slightly warped.  I screwed it down properly, straightening the board out in the process.  After this, the IO chassis worked with a host interface board to the computer and started properly.  We were able to see the boards attached as well with lspci.  So that chassis looks to be in working condition now.

Onwards to the RFM test.

  3545   Wed Sep 8 11:56:24 2010 kiwamuSummaryCDSSeptember CDS test plan

 Joe and Kiwamu

We discussed about our CDS plan for this September. The summary of the plan and "to do list" are now on the wiki page;

http://lhocds.ligo-wa.caltech.edu:8000/40m/Upgrade_09/CDS/September_CDS_plan

 

  Basically there are three major missions that we will do in this month;

1. complete damping of the vertex suspensions
2. Preparation for Green locking
3. Development of Simulated Plants
 

 We also try to keep updating the wiki page.

  3546   Wed Sep 8 14:44:37 2010 josephbUpdateCDSUpdated parse_mdl_to_ipc.py and feCodeGen.pl

I updated parse_mdl_to_ipc.py to correctly work with the 3 new cdsIPCx parts, namely cdsIPCx_PCIE (for dolphin connections), cdsIPCx_RFM (for our traditional reflected memory connections), and cdsIPCx_SHMEM (local shared memory on the computer).  These parts replaced cdsIPCx awhile back (see here ).

The code now correctly counts each type independantly with regards to ipcNum (I.e. you can have ipcNum = 0 for RFM and ipcNum = 0 for SHMEM for example).

 

I also went in and modified a few sections of the feCodeGen.pl (in /opt/rtcds/caltech/c1/core/advLigoRTS/src/epics/util/) so as to properly assign names to matrix adl files, matrix of filter bank adl files, and filter bank adl files.

  3553   Thu Sep 9 14:42:40 2010 josephbUpdateCDSUpdating suspensions model

I've been working on updating the suspensions model, incorporating Koji's refinements as well as trying to simplify the model and making it less cluttered. 

This had the side benefit of making an incorrect connection obvious.  I had incorrectly wired the ASCPIT input to be summed into the yaw path, and the ASCYAW input into the pitch path.  This has been corrected.

I've finished a single optic, and now I am in the process of propagating the changes to all the optics, as well as cleaning up the overall diagram using Rolf's new tags, which make things much less cluttered.  I've attached a screenshot of the PRM optic control model, and will be updating the Matlab web export once I've updated the full model.

Attachment 1: SingleSUS.png
SingleSUS.png
  3564   Mon Sep 13 10:22:48 2010 josephbUpdateCDSRCG bugs/feature request wiki page

I've started a wiki page under the Upgrade 09/New CDS section regarding known bugs and pending feature requests for the Real Time Code Generator.   It can be found at http://lhocds.ligo-wa.caltech.edu:8000/40m/Bugs_and_Pending_Feature_requests_for_the_RCG.  If you have any ideas to improve the RCG or encounter a bug in the code generation process (say a particular part doesn't work inside subsystems for example), please note them here.

Currently there are bugs with excitation points (they don't work inside of a subsystem block) and tags (they don't respect scope and only 1 "from" tag for each "goto" tag connected to the output of a subsystem block).

  3576   Wed Sep 15 14:34:57 2010 josephbSummaryCDSPlan for RFM switch over

Steps for RFM switch over:

1) Ensure the new frame builder code is working properly:

   A) Get Alex to finish compiling the frame builder and test on Megatron.

   B) Test the new frame builder code on fb40m (which is running Solaris) in a reversible way.  Change directory structure away from Data1, Data2, to use actual times.

   C) Confirm new frame builder code still records slow channels (c1dcuepics).

2) Ensure awg, tpman, and diagnostic codes (dtt) are working with the new front end code.

3) Physically move RFM cables from old front ends to the new front ends.  Remove excess connections from the network.

4) Merge the megatron/c1sus/c1iscex/c1ioo network with the main network.

   A) Update all the network settings on the machines as well as Linux1

   B) Remove the network switch separating the networks.

4) Start the new frame builder code on fb40m.

  3583   Fri Sep 17 12:11:42 2010 josephbUpdateCDSDowns update

In doing a re-inventory prior to the IOO chassis installation, I re-discovered we had a missing interface board that goes in an IO chassis.  This board connects the chassis to the computer and lets them talk to each other.  After going to Downs we remembered Alex had taken a possibly broken interface board back to downs for testing. 

Apparently the results of that testing was it was broken.  This was about 2.5 months ago and unfortunately it hadn't been sent back for repairs or a replacement ordered.  Its my fault for not following up on that sooner.

I asked Rolf what the plan for the broken one was.  His response was  they were planning on repairing it, and that he'd have it sent back for repairs today.  My guess the turn around time for that is on the order of 3-4 weeks (based on conversations with Gary), however it could be longer.  This will affect when the last IO chassis (LSC) can be made fully functional.  I did however pickup the 100 foot fiber cable for going between the LSC chassis and the LSC computer (which will be located in 1X3).

As a general piece of information, according to Gary the latest part number for these cards is OSS-SHB-ELB-x4/x8-2.0 and they cost 936 dollars (latest quote).

  3584   Fri Sep 17 14:55:01 2010 josephbUpdateCDSTook 5565 RFM card from IOVME to place in the new IOO chassis

I took the 5565 RFM card out of the IOVME machine to so I could put it in the new IO chassis that will be replacing it.  It is no longer on the RFM network.  This doesn't affect the slow channels associated with the auxilliary crate.

  3589   Mon Sep 20 11:39:45 2010 josephbUpdateCDSSwitch over

I talked to with Alex this morning, discussing what he needed to do to have a frame builder running that was compatible with the new front ends.

 

1) We need a heavy duty router as a separate network dedicated to data acquisition running between the front ends and the frame builder.  Alex says they have one over at downs, although a new one may need to be ordered to replace that one.

2) The frame builder is a linux machine (basically we stop using the Sun fb40m and start using the linux fb40m2 directly.).

3) He is currently working on the code today.  Depending on progress today, it might be installable tomorrow.

  3590   Mon Sep 20 16:59:26 2010 josephbUpdateCDSMegatron in 1X2 rack, to be come c1ioo

[Rana, Koji, Joe]

We pulled the phase shifters in the 1X2 rack out to make room for megatron.  Megatron will be converted into c1ioo, and the 8 core, 1U computer will be used as c1lsc.  A temporary ethernet cable was run from 1X2 to 1X3 to connect megatron to the same sub-network.

The c1lsc machine was worked on today, setting it up to run the real time code, along with the correct controls accounts, passwords, .cshrc files, etc.  It needs to be moved from 1X1 to 1X4 tomorrow.

  3593   Tue Sep 21 16:05:21 2010 josephbUpdateCDSFirst pass at rack diagram

I've made a first pass at a rack diagram for the 1X1 and 1X2 racks, attached as png.

Gray is old existing boards, power supplies etc.  Blue is new CDS computers and IO chassis, and gold is for the Alberto's new RF electronics.  I still need to double check on whether some of these boards will be coming out (perhaps the 2U FSS ref board?).

Attachment 1: 1X1_1X2_racks.png
1X1_1X2_racks.png
  3594   Wed Sep 22 16:35:45 2010 josephbUpdateCDSFibers pulled, new FB install tomorrow

[Aidan, Tara, Joe]

We pulled out what used to be the LSC/ASC fiber from the 1Y3 arm rack, and then redirected it to the 1X1 rack.  This will be used as the c1ioo 1PPS timing signal.  So c1ioo is using the old c1iovme fiber for RFM communications back to the bypass switch, and the old LSC fiber for 1PPS.

The c1sus machine will be using the former sosvme fiber for communications to the RFM bypass switch.  It already had a 1 PPS timing fiber.

The c1iscex machine had a new timing fiber already put in, and will be using the c1iscey vme crate's RFM for communication.

We still need to pull up the extra blue fiber which was used to connect c1iscex directly to c1sus, and reuse it as the 1PPS signal to the new front end on the Y arm. 

Alex has said he'll come in tomorrow morning to install the new FB code.

 

  3600   Thu Sep 23 12:05:20 2010 josephb, alexUpdateCDSfb40m down, new fb in progress

Alex came over this morning and we began work on the frame builder change over.  This required fb40m be brought down and disconnected from the RAID array, so the frame builder is not available.

He brought a Netgear switch which we've installed at the top of the 1X7 rack.  This will eventually be connected, via Cat 6 cable, to all the front ends.  It is connected to the new fb machine via a 10G fiber.

Alex has gone back to Downs to pickup a Symmetricon (sp?) card for getting timing information into the frame builder.  He will also be bringing back a harddrive with the necessary framebuilder software to be copied onto the new fb machine.

He said he'd like to also put a Gentoo boot server on the machine.  This boot server will not affect anything at the moment, but its apparently the style the sites are moving towards.  So you have a single boot server, and diskless front end computers, running Gentoo.  However for the moment we are sticking with our current Centos real time kernel (which is still compatible with the new frame builder code).  However this would make a switch over to the new system possible in the future.

At the moment, the RAID array is doing a file system check, and is going slowly while it checks terabytes of data.  We will continue work after lunch. 

 Punchline: things still don't work.

  3602   Thu Sep 23 21:01:11 2010 josephb, alexUpdateCDSfb40m still down, new fb still in progress
Unfortunately, copying the data to the USB/SATA drive over at downs took longer than expected for Alex. We will be installing the new code on the new fb machine tomorrow and running it. We will be running off of a timer on that machine until Monday. On Monday, a Symmetricom card will be arriving from LLO so that we can connect an IRIG-B timing signal into the frame builder and use a proper time signal. There is no running frame builder for tonight and thus will be no trends until we get the new FB running tomorrow morning.
  3606   Fri Sep 24 22:58:40 2010 josephbUpdateCDSModified front end medm screens

To startup medm screens for the new suspension front end, do the following:

1) From a control room machine, log into megatron

ssh -X megatron

2) Move to the new medm directory, and more specifically the master sub-directory

cd /opt/rtcds/caltech/c1/medm/master/

3) Run the basic sitemap in that directory

medm -x sitemap.adl

 

The new matrix of filters replacing the old ULPOS, URPOS, etc type filters is now on the screens.  This was previously hidden.  I also added the sensor input matrix entry for the side sensor.

Lastly, the C1SUS.txt filter bank was updated to place the old ULPOS type filters into the correct matrix filter bank.

 

The suspension controls still need all the correct values entered into the matrix entries (along with gains for the matrix of filter banks), as well as the filters turned on.  I hope to have some time tomorrow morning to do this, which basically involves looking at the old screens copying the values over.  The watch dogs are still controlled by the old control screens.  This will be fixed on Monday when I finish switching the front ends over from their sub-network to the main network, at which point logging into megatron will no longer be necessary.

  3609   Sun Sep 26 18:29:23 2010 rana, JohnUpdateCDSModified front end medm screens

Issues I notice on first glance:

  1. The OSEM Sensor Input matrix and the DOF2COIL Output matrix screens should be their own screens and linked from the overview. Right now they are not. Where is the input matrix?
  2. The SIDE GAIN looks like zero on the main screen, but the side OSEM signal seems to be getting through to the SIDE filter bank. . I think the wiring of the SIDE signal through the input matrix is bogus.
  3. The OUTPUT matrix seems to be the transpose of the previous OUTPUT matrix and we have lost the wires that connect the inputs and outputs to the matrix. We ought to think about how best to represent things on the OVERVIEW screen; probably only need to have a minimal representation and allow power users to open up the detailed screen.
  4. The TIME string is whited out. How will this be done? Does each FE display its local time on its EPICS screens?
  5. So far unable to get any channels on DV. How do we look at channels / test points?
  6. As far as we can tell, there is no connection between the output of the SUSPOS, etc. filter banks and the OUTPUT MATRIX. So....nothing actually goes to the coil driver. Its hard to imagine that this new SUS could have ever worked. Is there any evidence that the damping actually worked in the past, or was it something like "well, the watchdog values came down to small numbers eventually..." ???
  7. We are trying to debug the simulink file, but....the wiki entry on how to do this is out of date (yet updated as recently as August!) some path stuff just probably needs to be edited.

 megamind-poster3.jpg

Basically the suspensions are not functioning yet and we can't attempt locking of the MC.

  3612   Mon Sep 27 17:35:13 2010 josephbUpdateCDSUpdated Suspension screens/Megatron now c1ioo/Further work on fb

The medm screens have been updated further, with the hidden matrices added in bright colors.  An example screen shot is attached.

Megatron has been renamed c1ioo and moved to martian network.  Similarly, c1sus and c1iscex are also on the martian network.  Medm screens can be run on any of the control machines and they will work.

Currently the suspension controller is running on c1sus.

The frame builder is currently running on the fb machine *however* it is not working well.  Test points and daq channels on the new front ends tended to crash it when Alex started the mx_stream to the fb via our new DAQ network (192.168.114.XXX, accessible through the front ends or fb - has a dedicated 1 gigabit network with up to 10 gigabit for the fb).  So for the moment, we're running without front end data. Alex will be back tomorrow to work on it. 

Alex claimed to have left the frame builder in a state where it should be recording slow data, however, I can't seem to access recent trends (i.e. since we started it today).  The frame builder throws up an error "Couldn't open raw minute trend file '/frames/trend/minute_raw/C1:Vac-P1_pressure', for example.  Realtime seems to work for slow channels however.  Remember to connect to fb, not fb40m. So it seems the fb is still in a mostly non-functional state.

Alex also started a job to convert all the old trends to the correct new data format, which should finish by tomorrow.

RA: Nice screen work. The old screens had a 'slow' slider effect when ramping the bias so that we couldn't whack the optic too hard. Is the new one instantaneous?

Attachment 1: MC1_Example_Screen.png
MC1_Example_Screen.png
  3615   Tue Sep 28 10:07:29 2010 josephbUpdateCDSUpdated Suspension screens/Megatron now c1ioo/Further work on fb

Quote:

RA: Nice screen work. The old screens had a 'slow' slider effect when ramping the bias so that we couldn't whack the optic too hard. Is the new one instantaneous?

 Looking at the sliders, I apparently still need to connect them properly.  There's a mismatch between the medm screen channel name and the model name.  At the moment there is no "slow" slider effect implemented, so they are effectively instantaneous.  Talking with Alex, he suggests writing a little c-code block and adding it to the model.  I can use the c code used in the filter module ramps as a starting point.

  3619   Wed Sep 29 11:18:36 2010 josephbUpdateCDSApps code changes

After asking Alex specifically what he did yesterday after I left, he indicated he copied  a bunch of stuff from Hanford, including the latest gds, fftw, libframe, root.  We also now have the new dtt code as well.  But those apparently were for the Gentoo build   After asking Alex about the ezca tools this morning, he discovered they weren't complied in the gds code he brought over.  We are in the process of getting the source over here and compiling the ezca tools. 

 

Alex is indicating to me that the currently compiled new gds code may not run on the Centos 5.5 since it was compiled Gentoo (which is what our new fb is running and apparently what they're using for the front ends at Hanford).  We may need to recompile the source on our local Centos 5.5 control machines to get some working gds code.  We're in the process of transferring the source code from Hanford.  Apparently this latest code is not in SVN yet, because at some point he needs to merge it with some other work other people have been doing in parallel and he hasn't had the time yet to do the work necessary for the merge.

For the moment, Alex is undoing the soft link changes he did pointing gds at the latest gds code he copied, and pointing back at the original install we had.

  3620   Wed Sep 29 12:08:28 2010 josephb, alexSummaryCDSLast burt save of old controls

This is being recorded for posterity so we know where to look for the old controls settings.

The last good burt restore that was saved before turning off scipe25 aka c1dcuepics was on September 29, 11:07.

  3625   Thu Sep 30 11:07:20 2010 josephb, alexUpdateCDStest points starting to work

The centos 5.5 compiled gds code is currently living on rosalba in the /opt/app directory (this is local to Rosalba only).  It has not been fully compiled properly yet.  It is still missing ezcaread/write/ and so forth.  Once we have a fully working code, we'll propagate it to the correct directories on linux1.

So to have a working dtt session with the new front ends, log into rosalba, go to opt/apps/, and source gds-env.bash in /opt/apps (you need to be in bash for this to work, Alex has not made a tcsh environment script yet).  This will let get testpoints and be able to make transfer function measurements, for example

Also, to build the latest awgtpman, got to fb, go to /opt/rtcds/caltech/c1/core/advLigoRTS/src/gds, and type make.  This has been done and mentioned just as reference.

The awgtpman along with the front end models should startup automatically on reboot of c1sus (courtesy of the /etc/rc.local file).

  3628   Thu Sep 30 16:29:35 2010 josephb, alexUpdateCDSfb update

There currently seems to be a timing issue with  the frame builder.  We switched over to using a symmetricom card to get an IRIG-B signal into the fb machine, but the gps time stamp is way off (~80 years Alex said).

If there is a frame buiilder issue, its currently often necessary to kill the associated mx_stream processes, since they don't seem to restart gracefully.  To fix it the following steps should be taken:

Kill frame builder, kill the two mx_stream processes, then /etc/restart_streams/, then restart the frame builder (usual daqd -c ./daqdrc >& ./daqd.log in /opt/rtcds/caltech/c1/target/fb).

To restart (or start after a boot) the nds server, you need to go to /opt/rtcds/caltech/c1/target/fb and type

./nds /opt/rtcds/caltech/c1/target/fb/pipe

At this time, testpoints are kind of working, but timing issues seem to be preventing useful work being done with it.  I'm leaving with Alex working on the code.

 

  3629   Thu Sep 30 17:11:01 2010 alex iUpdateCDSDAQ system update

The frame builder is timed from the Symmetricom GPS card now, which is getting the IRIGB timecode from the freq. distribution amplifier (from the VME GPS receiver card).

I have adjusted the GPS seconds to match the real GPS time and the DTT seems to be happy: sweeping MC2 MCL filter module produces nice plot.

Test points are working on SUS.

Excitations are working on SUS.

I am leaving the frame builder running and acquiring the data.

 

Alex

 

  3631   Thu Sep 30 21:55:31 2010 ranaUpdateCDSDAQ sys update

Its pretty exciting to see that Joe got Alex to actually use the ELOG. Its a proof that even rare events occur if you are patient enough.

1) I fixed the MEDM links to point to the new sitemap.adl in /opt/rtcds. There is a link on the new sitemap which points to the old sitemap so that there is nothing destroyed yet.

2) Some of the fields in the screen are white. These are from the new c1sus processor, not issues with the slow controls. I think its just stuff that has not yet been created in the C1SUS simulink module.

Untitled.png

3) The PZT steering controls are gone. Without this we cannot get the beam down the arm. Must fix before aliging things after the MC. Since PZT used to be controlled by ASC, we'll have to wire the Piezo Jena PZT controls in from a different VME 4116. Possibly c1iool0's crate?

4) Also, the IPANG and IPPOS are somehow not working right. I guess this is because they are part of the ASC / the old ETMX system. We'll have to wire the IPANG QPD into the new ETMY ADC system if we want to get the initial alignment into the Y-arm correct.

5) I've started migrating things over from the old SITEMAP. Please just use the new SITEMAP. it has a red link to the old one, but eventually everything on the new one will work after Joe, Alex, me, and Kiwamu are done tweaking.


 

  3632   Fri Oct 1 10:56:30 2010 josephb,alexUpdateCDSfb work continued

Alex fixed the time issue with the IRIG-B signal being far off, apparently their IRIG-B signal in downs seems to be different.  He simply corrected for the difference in the two signals in the code.

For debugging purposes we uncommented the following line in the feCodeGen.pl script (in /opt/rtcds/caltech/c1/advLigoRTS/src/epics/util/):

print EPICS "test_points ONE_PPS $dac_testpoint_names $::extraTestPoints\n" 

This is to make every ADC testpoint available from the IOP (such as c1x02).

  3633   Fri Oct 1 11:33:15 2010 josephb, alexConfigurationCDSChanging gds code to the new working version

Alex is installing the newly compiled gds code (compiled on Centos 5.5 on Rosalba) which does in fact include the ezca type tools. 

At the moment we don't have a solaris compile, although that should be done at somepoint in the future.  It means the gds tools (diaggui, foton, etc) won't work on op440m.  On the bright side, this newer gds code has a foton that doesn't seem to crash all the time on Linux.

 

  3634   Fri Oct 1 11:53:42 2010 josephbConfigurationCDSAdded RCG simlink files to the 40m svn

I've added a new directory in /opt/rtcds/caltech/c1/core called rts_simlink.  This directory is now in the 40m svn.  Unfortunately, the simlink files used to generate the front end c codes live in a directory controlled by the CDS svn.  So I've copied the .mdl files from /opt/rtcds/caltech/c1/core/advLigoRTS/src/epics/simLink/ into this new directory and added them into the 40m svn.  When making changes to the simlink files, please copy them to this new directory and check them in so we can a useful history of the models.

 

  3635   Fri Oct 1 14:13:29 2010 josephb, alexUpdateCDSfb work that still needs to be done

1) Need to check 1 PPS signal alignment

2) Figure out why 1PPS and ADC/DAC testpoints went away from feCodeGen.pl?

3) Fix 1PPS testpoint giving NaN data

4) Figure out why is daqd printing "making gps time correction" twice?

5) Need to investigate why mx_streams are still getting stuck

6) Epics channels should not go out on 114 network (seen messages when doing
burt restore/save).

7) Dataviewer leaves test points hanging, daqd does not deallocate them
(net_Writer.c shutdown_netwriter call)

8) Need to install wiper scripts on fb

9) Need to install newer kernel on fb to avoid loading myrinet firmware
(avoid boot delay)

  3636   Fri Oct 1 16:34:06 2010 josephbUpdateCDSc1sus not booting due to fb dhcp server not running

For some reason, the dhcp server running on the fb machine which assigns the IP address to c1sus (since its running a diskless boot) was down.  This was preventing c1sus from coming up properly.  The symptom was an error indicated no DHCP offers were made(when I plugged a keyboard and monitor in).

To check if the dhcp server is running, run ps -ef | grep dhcpd.  If its not, it can be started with "sudo /etc/init.d/dhcpd start"

  3638   Fri Oct 1 18:19:24 2010 josephb, kiwamuUpdateCDSc1sus work

The c1sus model was split into 2, so that c1sus controls BS, PRM, SRM, ITMX, ITMY, while c1mcs controls MC1, MC2, MC3.  The c1mcs uses shared memory to tell c1sus what signals to the binary outputs (which control analog whitening/dewhitening filters), since two models can't control a binary output.

This split was done because the CPU time was running above 60 microseconds (the limit allowable since we're trying to run at 16kHz). Apparently the work Alex had done getting testpoints working had put a greater load on the cpu and pushed it over an acceptable maximum.    After removing the MC optics controls, the CPU time dropped to about 47 microseconds from about 67 microseconds.  The c1mcs is taking about 20 microseconds per cycle.

The new model is using the top_names functionality to still call the channels C1SUS-XXX_YYY.  However, the directory to find the actual medm filter modules is /opt/rtcds/caltech/c1/medm/c1mcs, and the gds testpoint screen for that model is called C1MCS-GDS_TP.adl.  I'm currently in the process of updating the medm screens to point to the correct location.

Also, while plugging in the cables from the coil dewhitening boards, we realized I (Joe) had made a mistake in the assignment of channels to the binary output boards.  I need to re-examine Jay's old drawings and fix the simulink model binary outputs.

  3639   Fri Oct 1 18:53:33 2010 josephb, kiwamuUpdateCDSThings needing to be done next week

We realized we cannot build code with the current RCG compiler on c1ioo or c1iscex, since these are not Gentoo machines.  We need either to get a backwards compatible code generator, or change the boot priority (removing the harddrives also probably works) for c1ioo and c1iscex so they do the diskless Gentoo thing.  This would involve adding some MAC address to the framebuilder dhcpd.conf file in /etc/dhcp along with the computer IPs, and then modifying the /diskless/root/etc/rtsystab with the right machine names and models to start.

I also need to bring some of the older, neglected models up to current build standards. I.e. use cdsIPCx_RFM instead of cdsIPCx and so forth. 

Need to fix the binary outputs for c1sus/c1mcs.  Need to actually get the RFM running, since Kiwamu was having some issues with his green RFM test model.  We have the latest checkout from Rolf, but we have no proof that it actually works.

  3642   Mon Oct 4 11:20:45 2010 josephbUpdateCDSFixed Suspension binary output list and sus model

I've updated the CDS wiki page listing the wiring of the 40m suspensions with the correct binary output channels.  I previously had confused the wiring of the Auxillary crate XY220 (watchdogs) with the SOS coil dewhitening bypasses.  So I had wound up with the wrong channels (the physical cables we plugged in were correct, just what I thought was going on channel X of that cable was wrong).  This has been corrected in the plan now.  The updated channel/cable list is at http://lhocds.ligo-wa.caltech.edu:8000/40m/Upgrade_09/CDS/Suspension_wiring_to_channels

  3644   Mon Oct 4 15:28:10 2010 josephbUpdateCDSTrying to get c1ioo booting as Gentoo.

I modified the dhcpd.conf file in /etc/dhcp on the fb machine.  I added a entry for c1ioo, listing its MAC address and ip number near the bottom of the file.  I then restarted the dhcp server using "sudo /etc/init.d/dhcpd restart" while on the fb machine.

I also modified the rtsystab, which is used to determine which front end codes start on boot up of a machine.  I added a line: c1ioo   c1x03  c1ioo

I am now in the process of getting c1ioo to come up as a Gentoo machine so I can build a model with an RFM connection in it and test the communication between c1sus and c1ioo.  This involves removing the hard drives and checking to make sure the boot priority is correct (i.e. it checks for a network boot).

  3648   Tue Oct 5 13:46:26 2010 josephb, alexUpdateCDSRestarted fb trending

Fb is now once again actually recording trends.

A section of the daqdrc file (located in /opt/rtcds/caltech/c1/target/fb/ directory) had been commented out by Alex and never uncommented.  This section included the commands which actually make the fb record trends.

The section now reads as:

# comment out this block to stop saving data

#
start frame-saver;
sync frame-saver;
start trender;
start trend-frame-saver;
sync trend-frame-saver;
start minute-trend-frame-saver;
sync minute-trend-frame-saver;
start raw_minute_trend_saver;
#start frame-writer "225.225.225.1" broadcast="131.215.113.0" all;
#sleep 5;

  3649   Tue Oct 5 13:52:15 2010 ranaUpdateCDSproof of trend

Untitled.png

  3651   Tue Oct 5 14:11:09 2010 josephb, alexUpdateCDSGoing to from rtlinux to Gentoo requires front end code clean out

Apparently when updating front end codes from rtlinux to the patched Gentoo, certain files don't get deleted when running make clean, such as the sysfe.rtl files in the advLigoRTS/src/fe/sys directories.  This fouls the start up scripts by making it think it should be configured for rtlinux rather than the Gentoo kernel module.

  3652   Tue Oct 5 16:30:00 2010 josephb, yutaHowToCDSScreen settings and medm screens for new system

You can find the sitemap medm screen in

/opt/rtcds/caltech/c1/medm/master

The settings for the screens were last saved by burt in the original system on Sept 29, 2010 at 11:07.  So go to the

/cvs/cds/caltech/burt/autoburt/snapshots/2010/Sep/29/11:07

directory.  You can grep for the channels in the files in this directory.

You can also then use the autoBurt.req file in the /opt/rtcds/caltech/c1/target/sysname/sysnameepics (c1sus/c1susepics) to backup the settings entered.  Save to the /opt/rtcds/caltech/c1/target/snapshots directory for now.

 

 

  3653   Tue Oct 5 16:58:41 2010 josephb, yutaUpdateCDSc1sus front end status

We moved the filters for the mode cleaner optics over from the C1SUS.txt file in /opt/rtcds/caltech/c1/chans/ to the C1MCS.txt file, and placed SUS_ on the front of all the filter names.  This has let us load he filters for the mode cleaner optics.

At the moment, we cannot seem to get testpoints for the optics (i.e. dtt is not working, even the specially installed ones on rosalba). I've asked Yuta to enter in the correct matrix elements and turn the correct filters on, then save with a burt backup.

  3658   Wed Oct 6 11:03:51 2010 josephb, yutaHowToCDSHow to start diaggui for right now

I'm hoping to get a proper install this week done, but for now, this a stop gap.

To start diagnostic test tools, go to rosalba.  (Either sit at it, or ssh -X rosalba).

cd /opt/apps

type "bash", this starts a bash shell

source gds-env.bash

diaggui

 --------- Debugging section ------

If that throws up errors, try looking with "diag -i" and see if there's a line that starts with nds.  In the case last night, Alex had not setup a diagconf configuration file in the /etc/xinetd.d directory, which setups up the diagconf service under the xinit service.  To restart that service (if for example the nds line doesn't show up), go to /etc/init.d/ and type "sudo xinit start" (or restart).

Other problems can include awg and/or tpman not running for a particular model on the front end machine.  I.e. diag -i should show 3 results from 192.168.113.85 (c1x02, c1sus, c1mcs) at the moment , for both awg and tp.  If not, that means awg and tpman need to be restarted for those.

These can be started manually by going to the front end, to the /opt/rtcds/caltech/c1/target/gds/bin/ directory, and running awgtpman -s sysname (or in the case of IOP files [c1x02, c1x03, etc], awgtpman -s sysname -4.  Better is probably to run the start scripts which live /opt/rtcds/caltech/c1/scripts/ which kills and restarts all the process for you.

 

 

  3659   Wed Oct 6 12:00:23 2010 josephb, yuta, kiwamuUpdateCDSFound and fixed filter sampling rate problem with suspensions

While we looking using dtt and going over the basics of its operation, we discovered that the filter sample rates for the suspensions were still set to 2048 Hz, rather than 16384 Hz which is the new front end.  This caused the filters loaded into the front ends to not behave as expected.

After correcting the sample rate, the transfer functions obtained from dtt are now looking like the bode plots from foton.

We fixed the C1SUS.txt and C1MCS.txt files in the /opt/rtcds/caltech/c1/chans/ directory, by changing the SAMPLING lines to have 16384 rather than 2048.

  3661   Wed Oct 6 15:56:14 2010 josephbHowToCDSHow to load matrices quickly and easily

Awhile ago I wrote several scripts for reading in medm screen matrix settings and then writing them out.  It was meant as kind of a mini-burt just for matrices for switching between a couple of different setups quickly.

Yuta has expressed interest in having this instruction available.

In /cvs/cds/caltech/scripts/matrix/ there are 4 python scripts:

saveMatrix.py, oldSaveMatrix.py, loadMatrix.py, oldLoadMatrix.py

The saveMatrix.py and loadMatrix.py are for use with the current front end codes (which start counting from 1), where as the old*.py files are for the old system.

To use saveMatrix.py you need to specify the number of inputs, outputs, and the base name of the matrix (i.e. C1:LSP-DOF2PD_MTRX is the base of C1:LSP-DOF2PD_MTRX_0_0_GAIN for example), as well as an ouptut file where the values are stored.

So to save the BS in_matrix setting you could do (from /cvs/cds/caltech/scripts/matrix/)

./saveMatrix.py -i 4 -o 5 -n "C1:SUS-BS_TO_COIL_MTRX" -f -d ./to_coil_mtrx.txt

The -i 4 indicates 4 inputs, the -o 5 indicates 5 outputs, -n "blah blah" indicates the base channel name, -f indicates a matrix bank of filters (if its just a normal matrix with no filters, drop the -f flag), and -d ./to_coil_mtrx.txt indicates the destination file.

To write the matrix, you do virtually the same thing:

./loadMatrix.py -n "C1:SUS-PRM_TO_COIL_MTRX" -f -d ./to_coil_mtrx.txt

In this case, you're writing the saved values of the BS, to the PRM.  This method might be faster if you're trying to fill in a bunch of new matrices that are identical rather than typing 1's and -1's 20 times for each matrix.

I'll have Yuta add his how-to of this to the wiki.

ELOG V3.1.3-