40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Tue Dec 31 23:19:58 2013, Koji, Summary, General, linux1 RAID crash & recovery 
    Reply  Thu Jan 2 10:15:20 2014, Jamie, Summary, General, linux1 RAID crash & recovery 
    Reply  Thu Jan 2 10:50:24 2014, Steve, Update, VAC, vacuum monitor is still blank Help.pngvacation.png20131220lastRGAscan.png
       Reply  Thu Jan 2 13:35:06 2014, Koji, Update, VAC, vacuum monitor is still blank 
          Reply  Tue Jan 28 11:13:50 2014, Koji, Update, VAC, vacuum monitor is still blank 
             Reply  Tue Jan 28 16:26:40 2014, Steve, Update, VAC, vacuum computers are back without safety c1vac1_vac2areback.png
                Reply  Wed Feb 5 08:14:59 2014, Steve, Update, VAC, vacuum computers are back without safety 
       Reply  Mon Jan 13 16:50:55 2014, Steve, Update, VAC, Maglev controller needs service 
          Reply  Wed Apr 2 16:34:15 2014, Steve, Update, VAC, Maglev controller needs service 
             Reply  Thu Apr 3 17:05:52 2014, Steve, Update, VAC, Maglev controller swapped loanerControllerIn.png
                Reply  Thu Apr 10 16:09:29 2014, Steve, Update, VAC, RGA scan at 75% pumping speed 520HzpumpingSpeed.png
                   Reply  Tue May 27 11:00:43 2014, Steve, Update, VAC, RGA scan at day 111 pd77d111RGA.png
                      Reply  Thu Aug 21 15:07:48 2014, Steve, Update, VAC, RGA scan at day 197 RGAscan@d197.png
                         Reply  Mon Sep 22 15:20:32 2014, Steve, Update, VAC, RGA scan at day 229 RGA@229day.pngRGAscan229d.png
                Reply  Mon Apr 21 10:14:00 2014, Steve, Update, VAC, Maglev controller serviced ourControllerBack560Hz.png
             Reply  Wed Aug 29 09:56:00 2018, Steve, Update, VAC, Maglev controller needs service 
                Reply  Mon Oct 22 15:19:05 2018, Steve, Update, VAC, Maglev controller serviced our_controller_is_back.png
    Reply  Mon Jan 6 16:32:40 2014, Koji, Summary, General, linux1 RAID crash & recovery 
Message ID: 9776     Entry time: Wed Apr 2 16:34:15 2014     In reply to: 9550     Reply to this: 9782   14189
Author: Steve 
Type: Update 
Category: VAC 
Subject: Maglev controller needs service 

Quote:

Quote:

 The date is correct on this monitor.

Last stored RGA scan data Dec 20, 2013

IFO pressure at CC1 5.8e-6 Torr

Valve configuration: Vacuum Normal, confirmable only by manual checking of position indicators and pressure gauge controllers  readouts

 

 The Osaka TG390MCAB maglev turbo pump's controller TC010M has passed the 40,000 hrs of operation. This triggered the " alarm" LED  warning light to come on. 

It is normal maintenance.  Maglev TP-1 is running perfectly.  Osaka will send us a loaner-controller that we can use while they do the std maintenance.

I'm thinking of ~ February to do this.

 We just received the loaner controller that will be swapped in it tomorrow morning.

The vacuum pressure will rise somewhat during this action.

ELOG V3.1.3-