40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Mon Aug 12 21:27:03 2013, manasa, Update, CDS, c1iscex needs help 
    Reply  Tue Aug 13 07:40:53 2013, Steve, Update, CDS, c1iscex needs help c1iscexSick.png
       Reply  Tue Aug 13 17:20:54 2013, Koji, Update, CDS, [Fixed] c1iscex needs help 
          Reply  Mon Nov 25 10:57:14 2013, Koji, Update, CDS, woes on the X-end hosts Screenshot.png
             Reply  Mon Nov 25 12:57:54 2013, Jamie, Update, CDS, timing problem at c1iscex IO chassis 
                Reply  Mon Nov 25 17:28:33 2013, Jenne, Update, CDS, timing problem at c1iscex IO chassis 
                Reply  Wed Nov 27 14:45:49 2013, Jenne, Update, CDS, timing problem at c1iscex IO chassis 
                   Reply  Wed Nov 27 16:29:21 2013, Jenne, Update, CDS, Accidentally turned off SUS IO chassis 
                Reply  Mon Dec 2 16:04:47 2013, Jamie, Update, CDS, c1iscex timing problem mysteriously disappears??? (thanksgiving miracle???) festatus.png
                   Reply  Mon Dec 2 17:05:13 2013, Jenne, Update, CDS, c1iscex timing problem mysteriously disappears??? (thanksgiving miracle???) 
                      Reply  Tue Dec 3 07:42:23 2013, Steve, Update, CDS, c1iscex timing problem mysteriously disappears??? (thanksgiving miracle???) 
             Reply  Wed Dec 4 13:37:34 2013, Jenne, Update, CDS, c1auxex down again 
Message ID: 9007     Entry time: Tue Aug 13 17:20:54 2013     In reply to: 9002     Reply to this: 9425
Author: Koji 
Type: Update 
Category: CDS 
Subject: [Fixed] c1iscex needs help 

c1x01 timing issue was solved. Now all of the models on c1iscex are nicely running.

Symptons

- c1x01 was synchronized to 1PPS in stead of TDS

- C1:DAQ-DC0_C1X01_STATUS (Upper right indicator) was red. The bits were 0x4000 or 0x2bad.
  C1:DAQ-DC0_C1X01_CRC_SUM kept increasing

 - c1scx, c1spx, c1asx could not get started.

Solution

- login to c1iscex "ssh c1iscex"

- Run "sudo shutdown -h now"

- Walk down to the x end rack

- Make sure the supply voltages for the electronics are correct (See Steve's entry)

- Make sure the machine is already shutdown.

- Unplug two AC power supply of the machine.

- Turn off the front panel switch of the IO chassis

- Wait for 10sec

- Turn on the IO chassis

- Plug the AC power supply cables to the machine

- Push the power switch of the realtime machine