Message ID: 7811     Entry time: Tue Dec 11 19:51:36 2012
Author: Koji 
Type: Update 
Category: PSL 
Subject: PMC gain was too low / EPICS alerting value for PMC updated 

[Ayaka, Koji]

Ayaka pointed out that the PMC has too low unity gain frequency. We checked the history of "C1:PSL-PMC_GAIN"
and found that the gain was minimum from the Friday night. It was returned to nominal gain of 10.

The PMC screen had the gain status indicator always red. This was because C1:PSL-STAT_PMC_NOM_GAIN was 2 instead of 10.
This was fixed by the following command.

ezcawrite C1:PSL-STAT_PMC_NOM_GAIN 10

This will be recorded by the snapshot in an hour.

Another annoying false alerm on the PMC screen was the PMC transmission monitor.
In order to fix this, the following commands were executed.

ezcawrite C1:PSL-PMC_PMCTRANSPD.LOLO 0.75
ezcawrite C1:PSL-PMC_PMCTRANSPD.LOW 0.8
ezcawrite C1:PSL-PMC_PMCTRANSPD.HIGH 0.9
ezcawrite C1:PSL-PMC_PMCTRANSPD.HIHI 0.95

Also the corresponding EPICS database (/cvs/cds/caltech/target/c1psl/psl.db) has been updated accordingly.