I updated the SUS DRIFT screen again, this time with a new feature.
I used Rolf's idea for the AdvLIGO status system and just made the nominals be an
unused sub-field (.SVAL) of the main INMON record. Then I wrote a .csh script to
use tdsavg to average the current INMON vals and insert that as the .SVAL. The next
script should read the .SVAL and set the HIHI and LOLO based on this.
Of course, the values I have just entered are no good because our suspensions are in
a bad state but we can run this script (SUS/setDriftNoms) next time things are good.
And...even better would be if someone were to do the same but used mDV to grab the
minute trend in the past good times instead of the tdsavg (which can't go in the past). |