[Jenne, Mirko]
To reiterate: We changed the OSEM loop shape for MC1-MC3. Below in black is the old loop shape, which simulated pendulum response in there. In red is the new loop shape.

The differences are due to extra filter in C1:SUS-MC?_SUSPOS module 6,7,9
6: Elliptical LP @ 2.5Hz
7: Inverse Chebychev HP @0.3Hz
8: 1st order LP @ 10Hz
This has the potential to be unstable, but is not. At some point these filters should be tuned further. |