40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Wed Aug 31 11:37:56 2011, steve, Update, Green Locking, shutter in place at east end 
    Reply  Wed Oct 19 16:28:35 2011, steve, Update, Green Locking, ETMY mechanical shutter is working 
       Reply  Wed Oct 19 17:33:07 2011, kiwamu, Update, Green Locking, ETMY mechanical shutter : fully functional MechShutter.png
Message ID: 5704     Entry time: Wed Oct 19 17:33:07 2011     In reply to: 5701
Author: kiwamu 
Type: Update 
Category: Green Locking 
Subject: ETMY mechanical shutter : fully functional 

The mechanical shutter on the Y end is now fully functional.

 

 It is newly named to 'C1AUX_GREEN_Y_Shutter' in the EPICS world.

It uses the same binary output channel which had been served for the POY shutter.

To change the EPICS name I edited a db file called ShutterInterLock.db, which resides in /cvs/cds/caltech/target/c1aux.

After editing the file I rebooted the c1aux machine, by telnet and the reboot command in order to make the change effective.

Also I added this new shutter on the ALS overview screen (see the attachment below)

MechShutter.png

Quote from #5701

The ETMY  shutter can be remotely switched from medm screen POY of mechanical shutters.

The new cable from ETMY controller goes to east vertex EV-ISCT where it is connected to POY shutter hook up BNC cable.