[Mirko / Jenne / Kiwamu]
Just a quick update. All the realtime processes on the c1lsc and c1sus machine didn't run at all.
Somehow the c1xxxfe.ko kernel module, where xxx is x04, x02, lsc, ass, sus, mcs, pem and rfm failed to be insmod.
The timing indicators on the c1lsc and c1sus machine are saying NO SYNC.
- According to log files (target/c1lsc/logs/log.txt)
insmod: error inserting '/opt/rtcds/caltech/c1/target/c1lsc/bin/c1lscfe.ko': -1 Unknown symbol in module
- dmesg on c1lsc (c1sus also dumps the same error message):
[ 45.831507] DXH Adapter 0 : sci_map_segment - Failed to map segment - error=0x40000d01
[ 45.833006] c1x04: DIS segment mapping status 1073745153
DXH dapter is a part of the Dolphine connections.
When a realtime codes is waking up, the code checks the Dolphin connections.
The checking procedure is defined by dolphin.c (/src/fe/doplhin.c).
According to a printk sentence in dolphin.c the second error message listed above will return status "0" if everything is fine.
The first error above is an error vector from a special dolphin's function called sci_map_segment, which is called in dolphin.c.
So something failed in this sci_map_segment function and is preventing the realtime code from waking up.
Note that sci_map_segment is defined in genif.h and genif.c which reside in /opt/srcdis/src/IRM_DSX/drv/src. |