Tue Jul 5 18:57:10 2011, Jamie, Update, SUS, More normalization of all sus controllers
|
Tue Jul 5 21:26:51 2011, rana, Update, SUS, More normalization of all sus controllers
|
Wed Jul 6 02:12:36 2011, kiwamu, Update, SUS, Re : More normalization of all sus controllers
|
Wed Jul 6 10:35:35 2011, Jamie, Update, SUS, Re : More normalization of all sus controllers
|
Wed Jul 6 15:32:32 2011, Jamie, Update, SUS, Re : More normalization of all sus controllers
|
Wed Jul 6 11:45:20 2011, Jamie, Update, SUS, More normalization of all sus controllers
|
|
Message ID: 4945
Entry time: Wed Jul 6 11:45:20 2011
In reply to: 4942
|
Author: |
Jamie |
Type: |
Update |
Category: |
SUS |
Subject: |
More normalization of all sus controllers |
|
|
Quote |
I'm attaching a screenshot of some of the problems I see so far with MC3.
|
I tried to fix all of the problems that I could identify in this screen shot:
- Fixed the TO_COIL output filter matrix screen to correctly point to the matrix element filter screens (all SUS)
- Removed MCL sections from SUS_XXX_POSITION screens, except for MC2. I also modified the _POSITION screens for the ETMs to refer to ALS instead of MCL.
- Zeroed out all of the lockin gains in the TO_COIL matrices (MC SUS)
- Made sure all whitening filter were ON (all SUS)
- Made sure all cts2um calibration filters were on (all SUS)
- Made sure all oplev servos were on (all SUS)
|