Entry  Tue Oct 26 22:57:37 2010, Jenne, Configuration, Computers, Why doesn't DTT work?!? 
    Reply  Wed Oct 27 10:53:03 2010, josephb, Configuration, Computers, Why doesn't DTT work?!? 
Message ID: 3793     Entry time: Wed Oct 27 10:53:03 2010     In reply to: 3790
Author: josephb 
Type: Configuration 
Category: Computers 
Subject: Why doesn't DTT work?!? 

Test points for the SUS channels should be there.  They have been working previously this week.  Possibly break down points include awgtpman, mx_streams, and the fb itself.  I'll look into that.

As far as other fast channels, there are no other fast front ends running than the suspensions ones we have.  Until additional channels get connected to the front ends and the models updated, those are the channels we have available.  However I am working on getting c1ioo up and running, and we can try connecting in some PEM channels today to the c1sus front end's 4th ADC.

 

Edit:

I tried starting a fresh instance of the frame builder, but when I brought the old copy down, it left a pair of zombie or dead mx_stream processes running on c1sus . Basically c1mcs and c1rms were still running, while c1x02 and c1sus came down.  I tried to kill the processes but this caused the c1sus machine to crash.  In the past I've killed left over mx_stream processes running after the frame builder has gone down, but I've never seen them crash the computer.  I'm unsure why this happened since we haven't done any updates of the code, just updated models and daq configuration files.

Quote:

DTT has only SUS and "X02" channels under C1 in the drop down channel selection menu.  Basically, we can't measure any fast channels with DTT.  I keep getting the error: "Unable to select testpoints."  Sadface.

Similar things are true for DataViewer.  The same limited number of fast channels, and no data found:

Server error 13: no data found
datasrv: DataWriteRealtime failed: daq_send: Illegal seek

Is this a framebuilder problem?  Is this something that the CDS team has on the to-do list?

 