40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Message ID: 17009     Entry time: Sat Jul 16 02:44:10 2022
Author: Koji 
Type: Update 
Category: IOO 
Subject: IMC servo tuning 

I wasn't sure how the IMC servo was optimized recently. We used to have the FSS over all gain (C1:PSL-FSS_MGAIN) of +6dB a few years back. It is not 0dB. So I decided to do a couple of measurements.

1) Default setting:

C1:IOO-MC_REFL_GAIN +4
C1:IOO-MC_BOOST2 +3
C1:IOO-MC_VCO_GAIN +13
C1:PSL-FSS_MGAIN +0
C1:PSL-FSS_FASTGAIN +19

2) Looked at the power spectrum at TEST1A output (error signal)
TEST1A is the signal right after the input gain stage (C1:IOO-MC_REFL_GAIN). Prior to the measurement, I've confirmed that the UGF is ~100Hz even at +0dB (see next section). It was not too bad even with the current default. Just wanted to check if we can increase the gain a bit more.
The input gain was fixed at +4dB and the FSS overall gain C1:PSL-FSS_MGAIN was swept from +0 to +6.
At +5dB and +6dB, the servo bump was very much visible (Attachment 1).
I decided to set the default to be +4dB (Attachment 3).

3) Took OLTF at 0dB and 4dB for the FSS overall gain.

Now the comparison of the opel loop transfer functions (OLTF) for C1:PSL-FSS_MGAIN at 0dB and 4dB. The OLTF were taken by injectiong the network analyzer signal into EXCA and measure the ratio between TEST1A and TEST1B (A/B).

C1:PSL-FSS_MGAIN +0 -> UGF 100kHz / Phase Margin ~50deg
C1:PSL-FSS_MGAIN +4 -> UGF 200kHz / Phase Margin 25~30deg

The phase margin was a bit less but it was acceptable.

4) IMC FSR

Took the opportunity to check the FSR of the IMC. Connected a cable to the RF MON of the IMC REFL demod board. Looked at the peak at 40.56MHz (29.5MHz + 11.066MHz). The peak was not so clear at 11.066195MHz (see 40m ELOG 15845). The peak was anyway minimized and the new modulation frequency was set to be 11.066081MHz (new FSR). The change is 10ppm level and it is within the range of the temp drift.

Attachment 1: ErrorPSD.pdf  152 kB  Uploaded Sat Jul 16 17:35:32 2022  | Show | Hide all | Show all
Attachment 2: OLTF.pdf  135 kB  Uploaded Sat Jul 16 22:56:46 2022  | Hide | Hide all | Show all
OLTF.pdf
Attachment 3: Screen_Shot_2022-07-16_at_03.59.05.png  199 kB  Uploaded Sun Jul 17 18:00:07 2022  | Hide | Hide all | Show all
Screen_Shot_2022-07-16_at_03.59.05.png
ELOG V3.1.3-