40m
QIL
Cryo_Lab
CTN
SUS_Lab
TCS_Lab
OMC_Lab
CRIME_Lab
FEA
ENG_Labs
OptContFac
Mariner
WBEEShop
|
40m Log |
Not logged in |
 |
|
Wed Sep 29 17:10:09 2021, Anchal, Summary, CDS, c1teststand problems summary
|
Thu Sep 30 14:09:37 2021, Anchal, Summary, CDS, New way to ssh into c1teststand
|
Thu Mar 3 15:37:40 2022, Anchal, Summary, CDS, c1teststand restructured
|
Mon Oct 4 11:05:44 2021, Anchal, Summary, CDS, c1teststand problems summary
|
Mon Oct 4 18:00:16 2021, Koji, Summary, CDS, c1teststand problems summary
|
Tue Oct 5 17:58:52 2021, Anchal, Summary, CDS, c1teststand problems summary
|
Tue Oct 5 18:00:53 2021, Anchal, Summary, CDS, c1teststand time synchronization working now
|
Mon Oct 11 17:31:25 2021, Anchal, Summary, CDS, Fixed mounting of mx devices in fb. daqd_dc is running now.
|
Mon Oct 11 18:29:35 2021, Anchal, Summary, CDS, Moving forward?
|
Tue Oct 12 17:20:12 2021, Anchal, Summary, CDS, Connected c1sus2 to martian network
|
Tue Oct 12 23:42:56 2021, Koji, Summary, CDS, Connected c1sus2 to martian network
|
Wed Oct 13 11:25:14 2021, Anchal, Summary, CDS, Ran c1sus2 models in martian CDS. All good!
|
Tue Oct 19 18:20:33 2021, Ian MacMillan, Summary, CDS, c1sus2 DAC to ADC test 
|
Tue Oct 19 23:43:09 2021, Koji, Summary, CDS, c1sus2 DAC to ADC test   
|
Wed Oct 20 11:48:27 2021, Anchal, Summary, CDS, Power supple configured correctly.
|
Tue Oct 26 18:24:00 2021, Ian MacMillan, Summary, CDS, c1sus2 DAC to ADC test 
|
Wed Dec 22 17:40:22 2021, Anchal, Summary, CDS, c1su2 model updated with SUS damping blocks for 7 SOSs
|
Wed Dec 29 20:09:40 2021, rana, Summary, CDS, c1su2 model updated with SUS damping blocks for 7 SOSs
|
Fri Mar 4 11:04:34 2022, Anchal, Summary, CDS, c1susaux2 system setup and running
|
Mon Mar 7 19:38:47 2022, Anchal, Summary, CDS, c1susaux2 slow controls issues
|
Mon Mar 14 12:20:05 2022, Anchal, Summary, CDS, c1susaux2 slow controls acromag chassis installed 
|
Thu Mar 17 19:12:44 2022, Anchal, Summary, CDS, c1auxey1 slow controls acromag chassis installed, not powered
|
Fri Mar 18 18:39:13 2022, Yehonathan, Summary, CDS, c1auxey1 slow controls acromag chassis installed, powered
|
Fri Mar 18 19:10:51 2022, Anchal, Summary, CDS, c1auxey1 slow controls issues
|
Mon Mar 21 18:42:06 2022, Anchal, Summary, CDS, c1auxey1 slow controls issues
|
Mon Apr 4 17:03:47 2022, Anchal, Summary, CDS, c1susaux2 slow controls acromag chassis fixed and installed
|
Wed Jul 6 22:40:03 2022, Tega, Summary, CDS, Use osem variance to turn off SUS damping instead of coil outputs
|
Thu Jul 7 21:25:48 2022, Tega, Summary, CDS, Use osem variance to turn off SUS damping instead of coil outputs
|
Tue Mar 15 11:52:34 2022, Anchal, Summary, CDS, c1su2 model updated for sending Run/Acquire Binary Output to Binary Interface card
|
Tue Mar 15 14:10:41 2022, Anchal, Summary, CDS, c1su2 model remade, reinstalled, restarted after the update
|
Tue Oct 12 17:10:56 2021, Anchal, Summary, CDS, Some more information
|
|
Message ID: 16712
Entry time: Mon Mar 7 19:38:47 2022
In reply to: 16700
|
Author: |
Anchal |
Type: |
Summary |
Category: |
CDS |
Subject: |
c1susaux2 slow controls issues |
|
|
I tried to perform a simple enabling test of coils using c1susaux2 modbus channels but failed. I'm able to do the enabling of coils using the windows GUI of acromag card but I can not do it when the cards are connected to the computer subnetwork. The issue is two-fold:
- The enable channels such as C1:SUS-LO1_UL_ENABLE are not changing values when their DOL changes a value. In this case, I created a calc channel C1:SUS-LO1_ALL_CALC which takes the AND of all coil's individual CALC channels which are normally used as DOL for the ENABLE channels. But even though the changes are reflected properly to C1:SUS-LO1_ALL_CALC, it does not affect C1:SUS-LO1_UL_ENABLE. See the db files here for more info.
- I tried to directly change the value of C1:SUS-LO1_UL_ENABLE using caput and even though in soft value the channel changes, it does not propagate a change at the output of Acromag card. So my suspicion is that something might be off with the setting of the Acromag card or c1susuaux2.cmd file. I followed this wiki page instructions, but if anyone can find an error, it would be useful.
There's also an issue in reading back the ENABLE_MON channels. Here we suspect that one of the optical isolator box that we have been using might have a short in one of it's output channel. I'll investigate this more tomorrow. Again, the issue is two-fold. The EPICS channel values do not really change. So there is clearly some issue of communicating with the acromag cards. |