40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Thu Feb 10 21:51:02 2022, Koji, Update, CDS, [Solved] Huge random numbers flowing into ETMX/ETMY ASC PIT/YAW Screenshot_2022-02-10_21-46-02.pngScreen_Shot_2022-02-10_at_21.54.21.pngScreen_Shot_2022-02-10_at_22.14.23.png
    Reply  Fri Feb 11 10:56:38 2022, Anchal, Update, CDS, [Solved] Huge random numbers flowing into ETMX/ETMY ASC PIT/YAW 
       Reply  Fri Feb 11 12:22:19 2022, rana, Update, CDS, [Solved] Huge random numbers flowing into ETMX/ETMY ASC PIT/YAW 
          Reply  Fri Feb 11 17:07:19 2022, Anchal, Update, CDS, [Solved] Huge random numbers flowing into ETMX/ETMY ASC PIT/YAW 
Message ID: 16666     Entry time: Fri Feb 11 12:22:19 2022     In reply to: 16664     Reply to this: 16668
Author: rana 
Type: Update 
Category: CDS 
Subject: [Solved] Huge random numbers flowing into ETMX/ETMY ASC PIT/YAW 

you can hand edit the autoBurt file which the FE uses to set the values after boot up. Just make a python script that amends all of the OFF or ZERO that are needed to make things safe. This would be the autoBurt snap used on boot up only, and not the hourly snaps.

 

Yeah, this is a known issue actually. We go to ASC screen and manually swich off all the outputs after every reboot. We haven't been able to find a way to set default so that when the model comes online, these outputs remain switched off. We should find a way for this.

 

ELOG V3.1.3-