Finally got the SIMPLANT damping to work following Rana's suggestion to try damping one DoF at a time, woo-hoo!
At first, things didn't look good even when we only focus on the POS DoF. I then noticed that the input value (X1:SUS-OPT_PLANT_TM_RESP_1_1_IN1) to the plant was always zero. This was odd bcos it meant the control signal was not making its way to the plant. So I decided to look at the sensor data
(X1:SUS-OPT_PLANT_COIL_IN_UL_OUTPUT, X1:SUS-OPT_PLANT_COIL_IN_UR_OUTPUT, X1:SUS-OPT_PLANT_COIL_IN_LR_OUTPUT, X1:SUS-OPT_PLANT_COIL_IN_LL_OUTPUT)
that adds up via the C2DOF matrix to give the POS DoF and I noticed that these interior nodes can take on large values but always sum up to zero because the pair (UL, LL) was always the negative of (UR,LR). These things should have the same sign, at least in our case where only the POS DoF is excited, so I tracked the issue back to the alternating (-,+,-,+,-) convention for the gains
(X1:SUS-OPT_CTRL_ULCOIL_GAIN, X1:SUS-OPT_CTRL_URCOIL_GAIN, X1:SUS-OPT_CTRL_LRCOIL_GAIN, X1:SUS-OPT_CTRL_LLCOIL_GAIN, X1:SUS-OPT_CTRL_SDCOIL_GAIN)
of the Coil Output filters used in the real system, which we adopted in the hopes that all was well. Anyways, I changed them all back to +1. This also means that we need to change the sign of the gain for the SIDE filter, which I have done also (and check that it damps OK). I decided to reduce the magnitude of the SIDE damping from 1 to 0.1 so that we can see the residuals since the value of -1 quickly sends the error to zero. I also increased the gain magnitude for the other DoF to 4.
When looking at the plot remember that the values actually represent counts with a scaling of 2^15 (or 32768) from the ADC. I switched back to the original filters on FM1 (e.g. pit_pit ) without damping coefficients present in the FM2 filter (e.g. pit_pit_damp).
FYI, Rana used the ETMY suspension MEDM screen to illustrate the working of the single suspension to me and changed maybe POS and PITCH gains while doing so.