Tue Jan 12 08:21:47 2021, anchal, HowTo, CDS, Acromag wiring investigation  
|
Tue Jan 12 11:42:38 2021, gautam, HowTo, CDS, Acromag wiring investigation
|
Wed Jan 13 16:09:29 2021, Anchal, HowTo, CDS, Acromag wiring investigation
|
Tue Jan 26 12:59:51 2021, Anchal, HowTo, CDS, Acromag wiring investigation
|
Tue Jan 26 15:37:25 2021, Anchal, HowTo, CDS, Acromag wiring investigation  
|
Fri Jan 29 17:57:17 2021, Anchal, HowTo, CDS, Acromag wiring investigation  
|
|
Message ID: 15785
Entry time: Fri Jan 29 17:57:17 2021
In reply to: 15779
|
Author: |
Anchal |
Type: |
HowTo |
Category: |
CDS |
Subject: |
Acromag wiring investigation |
|
|
I found a white paper from Acromag which discusses how to read differential signal using Acromag units. The document categorically says that differential signals are always supposed to be transmitted in three wires. I provides the two options of either using the RTN to connect to the signal ground (as done in Attachment 3) or locally place 10k-100k resistors between return and IN+ and IN- both (Attachment 2).
I have provided possible scenarios for these.
Using two wires to carry differential signal (Attachment 1):
- I assume this is our preferential way to connect.
- We can also assume all single-ended inputs as differential and do a signal condition agnostic wiring.
- Attachment 3 show what were the results for different values of resistors when a 2Hz 0.5V amplitude signal from SR785 which as converted to differential signal using D1900068 was measured by acromag.
- The connection to RTN is symmetrical for both inputs.
Using three wires to carry differential signal (Attachment 2):
- This is recommended method by the document in which it asks to carry the GND from signal source and connect it to RTN.
- If we use this, we'll have to be very cautious on what GND has been shorted through the acromag RTN terminals.
- This would probably create a lot of opportunities for ground loops to form.
Using an acromag card without making any connection with RTN is basically not allowed as per this document. |
|
|
|