Entry  Wed Dec 9 20:14:49 2020, gautam, Update, VAC, UPS failure rackBeforenAfter.pdfIMG_0008.jpgIMG_0009.jpgvacStatus.png
    Reply  Thu Dec 10 13:05:52 2020, Jon, Update, VAC, UPS failure TP2_time_history.pngslow_controls_monitors.png
       Reply  Thu Dec 10 14:29:26 2020, gautam, Update, VAC, UPS failure vacDiag1.png
Message ID: 15721     Entry time: Wed Dec 9 20:14:49 2020     Reply to this: 15724
Author: gautam 
Type: Update 
Category: VAC 
Subject: UPS failure 

Summary:

  1. The (120V) UPS at the vacuum rack is faulty.
  2. The drypump backing TP2 is faulty.
  3. Current status of vacuum system: 
    • The old UPS is now powering the rack again. Sometime ago, I noticed the "replace battery" indicator light on this unit was on. But it is no longer on. So I judged this is the best course of action. At least this UPS hasn't randomly failed before...
    • main vol is being pumped by TP1, backed by TP3.
    • TP2 remains off.
    • The annular volumes are isolated for now while we figure out what's up with TP2.
    • The pressure went up to ~1 mtorr (c.f. ~600utorr that is the nominal value with the stuck RV2) during the whole episode but is coming back down now.
  4. Steve seems to have taken the reliability of the vacuum system with him.

Details:

Around 7pm, the UPS at the vacuum rack seems to have failed. Don't ask me why I decided to check the vacuum screen 10 mins after the failure happened, but the point is, this was a silent failure so the protocols need to be looked into.

Going to the rack, I saw (unsurprisingly) that the 120V UPS was off. 

  • Pushed the power on button - the LCD screen would briefly light up, say the line voltage was 120 V, and then turned itself off. Not great.
  • I traced the power connection to the UPS itself to a power strip under the rack - then I moved the plug from one port to another. Now the UPS stays on. okay...
  • but after ~3 mins while I'm hunting for a VGA cable, I hear an incessant beeping. The UPS display has the "Fault" indicator lit up. 
  • I decided to shift everything back to the old UPS. After the change was made, I was able to boot up the c1vac machine again, and began the recovery process.
  • When I tried to start TP2, the drypump was unusually noisy, and I noticed PTP2 bottomed out at ~500 torr (yes torr). So clearly something is not right here. This pump supposedly had its tip-seal replaced by Jordan just 3 months ago. This is not a normal lifetime for the tip seal - we need to investigate more in detail what's going on here...
  • Decided that an acceptable config is to pump the main volume (so that we can continue working on other parts of the IFO). The annuli are all <10mtorr and holding, so that's just fine I think.

Questions:

  1. Are the failures of TP2 drypump and UPS related? Or coincidence? Who is the chicken and who is the egg?
  2. What's up with the short tip seal lifetime?
  3. Why did all of this happen without any of our systems catching it and sending an alert??? I have left the UPS connected to the USB/ethernet interface in case anyone wants to remotely debug this.

For now, I think this is a safe state to leave the system in. Unless I hear otherwise, I will leave it so - I will be in the lab another hour tonight (~10pm).

Some photos and a screen-cap of the Vac medm screen attached.

Attachment 1: rackBeforenAfter.pdf  2.795 MB  | Show | Hide all | Show all
Attachment 2: IMG_0008.jpg  1.102 MB  | Show | Hide all | Show all
Attachment 3: IMG_0009.jpg  242 kB  | Show | Hide all | Show all
Attachment 4: vacStatus.png  42 kB  | Hide | Hide all | Show all
vacStatus.png
ELOG V3.1.3-