Message ID: 1570     Entry time: Sat May 9 15:19:10 2009     In reply to: 1569     Reply to this: 1573
Author: rana 
Type: Update 
Category: PSL 
Subject: Laser head temperature oscillation 
This is 8 days of 10-minute trend.

DTEC is just the feedback control signal required to keep the NPRO's pump diode at a constant temperature.
Its not the amplifier or the actual NPRO crystal's temperature readout.

There is no TEC for the amplifier. It looks like to me that by opening up the flow to the NPRO some more
we have reduced the flow to the amplifier (which is the one that needs it) and created these temperature
fluctuations.

What we need to do is choke down the needle valve and ream out the NPRO block.