40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Fri Sep 20 12:55:02 2019, gautam, Update, CDS, c1iscaux testing 
    Reply  Mon Sep 23 10:49:34 2019, rana, Update, CDS, c1iscaux testing 
    Reply  Wed Sep 25 20:10:13 2019, Koji, Update, CDS, c1iscaux testing testDetectMons_190925.pngtestIPPOS_190925.png
       Reply  Thu Sep 26 20:09:40 2019, Koji, Update, CDS, c1iscaux testing Wht1.pdfWht2.pdfWht3.pdfWht4.pdflock.png
          Reply  Fri Sep 27 15:59:53 2019, gautam, Update, CDS, c1iscaux testing 
          Reply  Wed Oct 2 01:11:40 2019, Koji, Update, CDS, c1iscaux testing 8x
             Reply  Fri Oct 4 01:57:09 2019, Koji, Update, CDS, c1iscaux testing P_20191003_172956_vHDR_On.jpgTF.pdfPSD.pdf191003_AA_Filter.zip
                Reply  Sat Oct 5 00:03:21 2019, Koji, Update, CDS, c1iscaux testing REFL1_GAIN1.pdfREFL1_GAIN2.pdfREFL2_GAIN1.pdfREFL2_GAIN2.pdf
                   Reply  Tue Oct 8 03:32:42 2019, Koji, Update, CDS, CM servo board testing 7x
                      Reply  Tue Oct 8 17:59:29 2019, Koji, Update, CDS, CM servo board testing (portal) 6x
                         Reply  Tue Oct 8 18:42:39 2019, Koji, Update, CDS, CM servo board testing boosts.pdf
                            Reply  Mon Oct 14 16:06:28 2019, Koji, Update, CDS, CM servo board testing pole_zero_filter.pdf
                               Reply  Mon Oct 14 16:19:30 2019, Koji, Update, CDS, CM servo board testing testb2.pdf
                                  Reply  Mon Oct 14 16:25:03 2019, Koji, Update, CDS, CM servo board testing servo_out.pdf
                                     Reply  Mon Oct 14 16:34:42 2019, Koji, Update, CDS, CM servo board testing in12_output_offset.pdfin12_input_offset.pdfin12_input_offset2.pdf
                                        Reply  Mon Oct 14 17:32:28 2019, Koji, Update, CDS, Portal Elog entry for the recent CM servo board tests CM_Servo_Diagram.png
                         Reply  Tue Oct 8 20:23:03 2019, gautam, Update, CDS, c1iscaux testing 
    Reply  Mon Sep 30 11:20:43 2019, gautam, Update, CDS, c1iscaux testing - CM board code updated CMsoftTest.png
       Reply  Mon Sep 30 15:51:59 2019, gautam, Update, CDS, c1iscaux - some admin 
Message ID: 14967     Entry time: Mon Oct 14 16:25:03 2019     In reply to: 14966     Reply to this: 14968
Author: Koji 
Type: Update 
Category: CDS 
Subject: CM servo board testing 

The output stage (and AO GAIN stage) of the MC board was modelled. The transfer function was measured with the injection from EXC B. The denominator was TESTB2, and the numerator was SERVO OUT.

This stage is AC coupled by 2x 1st order HPFs. Firstly, this transfer function was measured with AO GAIN set to be 0dB. (Attachment 1)
This TF was used to characterize the cutoffs of the HPF stages, represented as the following ZPK:

zero 1m
zero 1m
pole 6.0502599855
pole 6.0624642854
factor -26.2725046079n

Then the AO GAIN was already measured as seen in [ELOG 14948]. The AO gain TF was then modeled by LISO with the above HPF as the preset. This allows us to characterize the time delay of the AO GAIN part.

Attachment 1: servo_out.pdf  151 kB  Uploaded Mon Oct 14 17:29:12 2019  | Hide | Hide all