40m
QIL
Cryo_Lab
CTN
SUS_Lab
TCS_Lab
OMC_Lab
CRIME_Lab
FEA
ENG_Labs
OptContFac
Mariner
WBEEShop
|
40m Log |
Not logged in |
 |
|
Tue Jul 16 16:00:01 2019, gautam, Update, CDS, c1iscaux Supermicro setup
|
Wed Jul 17 21:22:41 2019, gautam, Update, CDS, CM board Latch Enable subtlety
|
Sun Jul 21 12:55:38 2019, gautam, Update, CDS, CM board Latch Enable test script 
|
Fri Aug 9 08:59:04 2019, gautam, Update, CDS, Prep for install of c1iscaux
|
Sun Aug 11 11:47:42 2019, gautam, Update, CDS, Bench test of c1iscaux
|
Mon Aug 12 17:36:04 2019, gautam, Update, CDS, More bench test of c1iscaux
|
Mon Aug 12 21:25:19 2019, Koji, Update, CDS, More bench test of c1iscaux
|
Tue Aug 13 08:07:09 2019, gautam, Update, CDS, P1--->P2
|
Tue Aug 13 14:36:17 2019, gautam, Update, CDS, P1--->P2
|
Fri Aug 16 16:40:04 2019, gautam, Update, CDS, 1Y3 work  
|
Sat Aug 17 16:49:23 2019, gautam, Update, CDS, More 1Y3 work   
|
Mon Aug 19 14:36:21 2019, gautam, Update, CDS, c1iscaux remaining work
|
Tue Aug 20 19:05:24 2019, Koji, Update, CDS, MC1 (and MC3) troubleshoot 
|
Thu Aug 22 12:54:06 2019, Koji, Update, CDS, MC1 glitch removed (for now) and IMC locking recovered 7x
|
Thu Aug 22 20:56:51 2019, Koji, Update, CDS, MC1 glitch removed (for now) and IMC locking recovered
|
Fri Aug 23 18:46:17 2019, Jon, Update, CDS, c1iscaux remaining work
|
Sun Aug 25 14:18:08 2019, gautam, Update, CDS, c1iscaux remaining work
|
Thu Jul 18 10:46:04 2019, gautam, Update, CDS, Database files made
|
Thu Jul 18 19:58:56 2019, gautam, Update, CDS, Work on Acromag chassis  
|
Fri Jul 19 19:44:03 2019, gautam, Update, CDS, Database file test
|
|
Message ID: 14781
Entry time: Fri Jul 19 19:44:03 2019
In reply to: 14773
|
Author: |
gautam |
Type: |
Update |
Category: |
CDS |
Subject: |
Database file test |
|
|
Summary:
The database files for C1ISCAUX seem to work file - the exception being the mbbo channels for the CM board.
Details:
This was just a software test - the actual functionality of the channels will have to be tested once the Acromag crate has been installed in the rack. One change I had to make on the MEDM screen for the LSC PD whitening gains was to get rid of the "NMS" suffix on the EPICS channel names for whitening gain sliders/drop-down-menus. I suspect this has to do with the EPICS version we are using, 7.0.1. Furthermore, AS165 and POP55 no longer exist - I hold off removing them from the MEDM screen for the moment.
Next steps:
From the software point of view, the major steps are:
- Fix the mbbo channel notation in the database files
- Write and test the latch enabling code
- Figure out what scripted tests can be done to test the functionality of the new Acromag box.
I am stopping the EPICS server on the new machine and restarting the old VME crate over the weekend. |
|
|