40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Fri Dec 8 23:31:31 2017, johannes, Frogs, ASS, c1ass slow channel offloading scripts with small  
    Reply  Wed Dec 13 09:49:23 2017, johannes, Update, ASS, wiring diagram 1Y9.pdf
       Reply  Thu Dec 14 00:32:56 2017, johannes, Update, ASS, Acromag new crate; c1auxex2 configured as gateway server for acromag fp_mod_4U.pdfIMG_20171213_171541850_HDR.jpg
          Reply  Thu Dec 14 23:27:46 2017, johannes, Update, DAQ, aux chassis design auxdaq_40m_4U_front.pdfauxdaq_40m_4U_rear.pdfauxdaq_40m_4U_DSub37x2.pdfauxdaq_40m_4U_IDC50.pdf
             Reply  Tue Jan 9 00:07:03 2018, johannes, Update, DAQ, etmx slow daq chassis 
                Reply  Wed Jan 10 22:24:28 2018, johannes, Update, DAQ, etmx slow daq chassis 
                   Reply  Thu Jan 11 09:57:17 2018, Steve, Update, DAQ, acromag at ETMX Acromg_in_action.png
                   Reply  Thu Jan 11 20:59:41 2018, gautam, Update, DAQ, etmx slow daq chassis 
                      Reply  Wed Jan 17 14:32:51 2018, gautam, Update, DAQ, Acromag checks OSEMPDmon_Acro.png
                         Reply  Wed Jan 17 22:44:14 2018, johannes, Update, DAQ, Acromag checks 
                            Reply  Sun Jan 21 13:11:25 2018, johannes, Update, DAQ, Acromag checks 
                   Reply  Fri Jan 12 10:02:05 2018, johannes, Update, DAQ, etmx slow daq chassis 
                      Reply  Fri Jan 12 19:15:34 2018, johannes, Update, DAQ, etmx slow daq chassis 
                         Reply  Wed Jan 24 18:12:31 2018, johannes, Update, DAQ, ETMX auxiliary DAQ work IMG_20180124_120202019.jpgIMG_20180124_120123064.jpgIMG_20180124_120219278.jpgIMG_20180124_120059765.jpg
                            Reply  Wed Jan 24 19:17:06 2018, johannes, Update, DAQ, c1auxex2 startup behavior 
                               Reply  Wed Jan 24 23:13:30 2018, johannes, Update, DAQ, c1auxex2 startup behavior 
    Reply  Thu Dec 14 19:33:20 2017, gautam, Frogs, ASS, c1ass slow channel offloading scripts with small  
Message ID: 13553     Entry time: Wed Jan 17 14:32:51 2018     In reply to: 13535     Reply to this: 13554
Author: gautam 
Type: Update 
Category: DAQ 
Subject: Acromag checks 
  1. I take back what I said about the OSEM PD mon at the meeting - there does seem to be to be some overall calibration factor (Attachment #1) that has scaled the OSEM PD readback channels, by a factor of (20000/2^15), which Johannes informs me is some strange feature of the ADC, which he will explain in a subsequent post.
  2. The coil redback fields on the MEDM screen have a "30Hz HPF" text field below them - I believe this is misleading. Judging by the schematic, we are monitoring, on the backplane (which is what these channels are reading back from), the coil to the voltage with a gain of 0.5. We can reconfirm by checking the ETMX coil driver board, after which we should remove the misleading label on the MEDM screens.
Quote:

Some suggestions of checks to run, based on the rightmost colum in the wiring diagram here - I guess some of these have been done already, just noting them here so that results can be posted.

  1. Oplev quadrant slow readouts should match their fast DAQ counterparts.
  2. Confirm that EX Transmon QPD whitening/gain switching are working as expected, and that quadrant spectra have the correct shape.
  3. Watchdog tripping under different conditions.
  4. Coil driver slow readbacks make sense - we should also confirm which of the slow readbacks we are monitoring (there are multiple on the SOS coil driver board) and update the MEDM screen accordingly.
  5. Confirm that shadow sensor PD whitening is working by looking at spectra.
  6. Confirm de-whitening switching capability - both to engage and disengage - maybe the procedure here can be repeated.
  7. Monitor DC alignment of ETMX - we've seen the optic wander around (as judged by the Oplev QPD spot position) while sitting in the control room, would be useful to rule out that this is because of the DC bias voltage stability (it probably isn't).
  8. Confirm that burt snapshot recording is working as expected - this is not just for c1auxex, but for all channels, since, as Johannes pointed out, the 2018 directory was totally missing and hence no snapshots were being made.
  9. Confirm that systemd restarts IOC processes when the machine currently called c1auxex2 gets restarted for whatever reason.

 

 

 

Attachment 1: OSEMPDmon_Acro.png  87 kB  | Hide | Hide all
OSEMPDmon_Acro.png