Entry  Fri Dec 8 23:31:31 2017, johannes, Frogs, ASS, c1ass slow channel offloading scripts with small  
    Reply  Wed Dec 13 09:49:23 2017, johannes, Update, ASS, wiring diagram 1Y9.pdf
       Reply  Thu Dec 14 00:32:56 2017, johannes, Update, ASS, Acromag new crate; c1auxex2 configured as gateway server for acromag fp_mod_4U.pdfIMG_20171213_171541850_HDR.jpg
          Reply  Thu Dec 14 23:27:46 2017, johannes, Update, DAQ, aux chassis design auxdaq_40m_4U_front.pdfauxdaq_40m_4U_rear.pdfauxdaq_40m_4U_DSub37x2.pdfauxdaq_40m_4U_IDC50.pdf
             Reply  Tue Jan 9 00:07:03 2018, johannes, Update, DAQ, etmx slow daq chassis 
                Reply  Wed Jan 10 22:24:28 2018, johannes, Update, DAQ, etmx slow daq chassis 
                   Reply  Thu Jan 11 09:57:17 2018, Steve, Update, DAQ, acromag at ETMX Acromg_in_action.png
                   Reply  Thu Jan 11 20:59:41 2018, gautam, Update, DAQ, etmx slow daq chassis 
                      Reply  Wed Jan 17 14:32:51 2018, gautam, Update, DAQ, Acromag checks OSEMPDmon_Acro.png
                         Reply  Wed Jan 17 22:44:14 2018, johannes, Update, DAQ, Acromag checks 
                            Reply  Sun Jan 21 13:11:25 2018, johannes, Update, DAQ, Acromag checks 
                   Reply  Fri Jan 12 10:02:05 2018, johannes, Update, DAQ, etmx slow daq chassis 
                      Reply  Fri Jan 12 19:15:34 2018, johannes, Update, DAQ, etmx slow daq chassis 
                         Reply  Wed Jan 24 18:12:31 2018, johannes, Update, DAQ, ETMX auxiliary DAQ work IMG_20180124_120202019.jpgIMG_20180124_120123064.jpgIMG_20180124_120219278.jpgIMG_20180124_120059765.jpg
                            Reply  Wed Jan 24 19:17:06 2018, johannes, Update, DAQ, c1auxex2 startup behavior 
                               Reply  Wed Jan 24 23:13:30 2018, johannes, Update, DAQ, c1auxex2 startup behavior 
    Reply  Thu Dec 14 19:33:20 2017, gautam, Frogs, ASS, c1ass slow channel offloading scripts with small  
Message ID: 13530     Entry time: Thu Jan 11 09:57:17 2018     In reply to: 13529
Author: Steve 
Type: Update 
Category: DAQ 
Subject: acromag at ETMX 

Good going Johannes!

Quote:

This evening I transitioned the slow controls to c1auxex2.

  1. Disconnected satellite box
  2. Turned off c1auxex
  3. Disconnected DIN cables from backplace connectors
  4. Attached purple adapter boards
  5. Labeled DSub cables for use
  6. Connected DSub cables to adapter boards and chassis
  7. Initiated modbus IOC on c1auxex2

Gautam and I then proceeded to test basic functionality

  1. Pitch bias sliders move pitch, yaw moves yawyes.
  2. Coil enable and monitoring channels work yes
  3. Watchdog seems to work. yes We set the treshold for tripping low, excited the optic, watchdog didn't disappoint and triggered.
  4. All channels Initialize with "0" upon machine/server script restart. This means the watchdog happens to be OFF, which is good yes. It would be great if we could also initialize PIT and YAW to retain their value from before to avoid kicking the optic. This is not straightforward with EPICS records but there must be a way.
  5. We got the local damping going yes.
  6. There is some problem with the routing of the fast BIO channels through the new chassis - so the ANALOG de-whitening filter seems to be always engaged, despite our toggling the software BIO bits no. Something must be wrongly wired, as we confirmed by returning only the FAST BIO wiring to the pre-acromag state (but everything else is now controlled by acromag) and didn't have the problem anymore. Or some electrical connection is not made (I had to use gender changers on these connectors due to lack of proper cabling)
  7. The switches for the QPD gain stages did not work. no I suspect a wiring problem, since the switching of the coil enables did work.

Arms are locked, have been for ~1hour with no hickups. We will leave it like this overnight to observe, and debug further tomorrow.

 