Fri Nov 17 16:31:11 2017, aaron, Omnistructure, Computers, Acromag wired up
|
Fri Nov 17 17:10:53 2017, rana, Omnistructure, Computers, Acromag wired up
|
Wed Nov 22 00:54:18 2017, johannes, Omnistructure, Computers, Slow DAQ replacement computer progress
|
Wed Nov 29 21:40:30 2017, johannes, Omnistructure, Computers, Slow DAQ replacement computer progress
|
Mon Dec 4 22:06:07 2017, johannes, Omnistructure, Computers, Acromag XEND progress
|
Thu Dec 7 22:24:04 2017, johannes, Omnistructure, Computers, Acromag XEND progress  
|
Fri Dec 8 12:06:59 2017, johannes, Omnistructure, Computers, c1auxex2 ready - but need more cables
|
|
Message ID: 13434
Entry time: Fri Nov 17 16:31:11 2017
Reply to this: 13435
13443
|
Author: |
aaron |
Type: |
Omnistructure |
Category: |
Computers |
Subject: |
Acromag wired up |
|
|
Acromag Wireup Update
I finished wiring up the Acromags to replace the VME boxes on the x arm. I still need to cut down the bar and get them all tidy in the box, but I wanted to post the wiring maps I made.
I wanted to note specifically that a few of the connections were assigned to VME boxes but are no longer assigned in this Acromag setup. We should be sure that we actually do not need to use the following channels:
Channels no longer in use
- From the VME analog output (VMIVME 4116) to the QPD Whitening board (no DCC number on the front), 3 channels are no longer in use
- From the anti-image filter (D000186) to the ADC (VMIVME 3113A) 5 channels are no longer in use (these are the only channels from the anti-image filter, so this filter is no longer in use at all?)
- From the universal dewhitening filter (D000183) to a binary I/O adapter (channels 1-16), 4 channels are no longer in use. These are the only channels from the dewhitening filter
- From a second universal dewhitening filter (D000183) to another the binary I/O adapter (channels 1-16), one channel is no longer in use (this was the only channel from this dewhitening filter).
- From the opti-lever (D010033) to the VME ADC (VMIVME 3113A), 7 channels are no longer in use (this was all of the channels from the opti lever)
- From the SUS PD Whitening/Interface board (D000210) to a binary I/O adapter (channels 1-16), 5 channels are no longer in use.
- Note that none of the binary I/O adapter channels are in use.
|
|
|