Thu Aug 31 18:36:23 2017, gautam, Update, CDS, revisiting Acromag
|
Thu Nov 9 15:33:08 2017, johannes, Update, CDS, revisiting Acromag
|
Thu Jan 11 21:09:33 2018, gautam, Update, CDS, revisiting Acromag
|
|
Message ID: 13282
Entry time: Thu Aug 31 18:36:23 2017
Reply to this: 13422
13536
|
Author: |
gautam |
Type: |
Update |
Category: |
CDS |
Subject: |
revisiting Acromag |
|
|
Current status:
- There is a single Acromag ADC unit installed in 1X4
- It is presently hooked up to the PSL NPRO diagnostic connector channels
- I had (re)-started the acquisiton of these channels on August 16 - but for reasons unknown, the tmux session that was supposed to be running the EPICS server on megatron seems to have died on August 22 (judging by the trend plot of these channels, see Attachment #1)
- I had not set up an upstart job that restarts the server automatically in such an event. I manually restarted it for now, following the same procedure as linked in my previous elog.
- While I was at it, I also took the opportunity to edit the Acromag channel names to something more appropriate - all channels previously prefixed with C1:ACRO- have now been prefixed with C1:PSL-
Plan of action:
- Hardware - we have, in the lab, in addition to the installed ADC unit
- 3x 8 channel differential input ADC units
- 2x 8 channel differential output DAC units
- 1x 16 channel BIO unit
- 2U chassis + connectors + breakout boards + other misc hardware that I think Johannes and Lydia procured with the original plan to replace the EX slow controls.
- Some relevant elogs: Panel designs, breakout design, sketch for proposed layout, preliminary channel list.
So on the hardware side, it would seem that we have everything we need to go ahead with replacing the EX slow controls with an Acromag system, although Johannes probably knows more about our state of readiness from a hardware PoV.
- Software
- We probably want to get a dedicated machine that will handle the EPICS channel serving for the Acromag system
- Have to figure out the networking arrangement for such a machine
- Have to figure out how to set up the EPICS server protocol in such a way that if it drops for whatever reason, it is automatically restarted
|
|
|